DIRECTORATE GENERAL FOR GAS POWER

PLANT PROJECTS

24-May-2011-16:49
MEGA DEAL PROJECT C

NAINAWA POWER PLANT


CONTRACT N° 8
[6 x 125 MW]

al
SE
REFERENCE NUMBER : E0876 100 I90 DM 002 REVISION : A

ci
ECH / SCALE DATE 26/06/2009 30/06/2009
None

R
NOM / NAME JOANNES CEDRIC FLORENTZ CHRISTIAN

ffi
FO
FORMAT / SIZE VISA JOANNES CEDRIC FLORENTZ CHRISTIAN
A3 REDIGE / MADE VERIFIE / CHECKED APPROUVE / APPROVED

O
TITRE / TITLE

GAS TURBINE WITH ASSOCIATES ITEMS-SYSTEM DESIGN MANUAL

E
4108, DESIGN MAN, GT & AUXILIARIES CONTROL HIERARCHY

VALIDE
GERALDES JESSICA
Ce document, propriété exclusive de REVISION
GE Energy Products France SNC
est strictement confidentiel. Il ne peut
être communiqué, copié ou reproduit
sans son autorisation écrite préalable
GE Energy A
INSTRUCTION DE
MODIFICATION

This document, exclusive property of


GE Energy Products France SNC N° 132B8269 Section Doc.
is strictly confidential. It must not be
communicated, copied or reproduced
without our previous written consent.
GRD X
SHEET. N°
SIZE DWG. NO. SH. REV.
A3 132B8266 1 A

NOTES FOR SHEETS 2 - 7:


THIS DOCUMENT SHALL BE
1. LENGTHS OF CAT-6 UTP, AND FIBER OPTIC CABLE TO BE DETERMINED AT INSTALLATION. REVISED IN ITS ENTIRETY. ALL
SHEETS OF THIS DOCUMENT
2. THE (1) SYMBOL DEFINES CUSTOMER'S SUPPLIED EQUIPMENT. ARE THE SAME REVISION
LEVEL AS INDICATED IN THE
3. EACH OPERATOR INTERFACE: HMI AND OSM COMES WITH 50 FEET CAT-6 UTP (100 BASE-T) REVISION BLOCK.
CABLE FOR ETHERNET CONNECTION. THE CUSTOMER CAN USE THESE PRE-CUT CABLES
TO SATISFY THE AS-INSTALLED CABLE LENGTH NEEDS.

4. IF REQUIRED, THE CUSTOMER IS RESPONSIBLE FOR UPS (UNINTERUPTIBLE POWER


SUPPLY) FOR NETWORK EQUIPMENT.

APPROX. POWER @ APPROX. POWER @


DEVICE
120VAC / 60 HZ 230VAC / 50 HZ
HMI (WITH MONITOR) 7 AMPS (EACH) 3,5 AMPS (EACH)
ETHERNET SWITCHES < 1 AMP (EACH) < 0,5 AMP (EACH)
NETWORK TIME SERVER < 1 AMP (EACH) < 0,5 AMP (EACH)
NETWORK PRINTER < 7 AMPS (EACH) < 3,5 AMPS (EACH)

5. REMOTE HARDWARE SUPPLIED BY GE IS SHIPPED LOOSE. THIS HARDWARE IS LOCATED


AND INSTALLED BY THE CUSTOMER.

6. THE UNIVERSAL ON-SITE MONITOR (uOSM), WHICH CONSISTS OF BOTH HARDWARE AND
SOFTWARE, IS PROVIDED AT NO CHARGE TO THE CUSTOMER ON CLASS-F FOR THE
LENGTH OF THE STANDARD WARRANTY PERIOD OR THE LENGTH OF ANY EXTENDED
CONTRACT SERVICE AGREEMENT (CSA). THE uOSM IS USED TO PERIODICALLY MONITOR
SELECTED UNIT AND FLEET DATA. IT IS TYPICALLY LOCATED IN ODD NUMBERED PEECCS
AND THROUGH USE OF A MONITOR SWITCH. THE uOSM WILL SHARE A KEYBOARD,
CURSOR POSITIONING DEVICE AND MONITOR WITH THE NEIGHBORING LOCAL OPERATOR
INTERFACE (HMI). GE WILL ALSO PROVIDE A DEDICATED UPS, SIZED ONLY TO
ACCOMMODATE THE uOSM. THE MONITORING SERVICE DOES NOT NECESSITATE
OPERATOR INTERACTION FROM THE SITE. GE REQUIRES THAT THE CUSTOMER SUPPLY
TWO DEDICATED ANALOG PHONE LINES TO THE uOSM (NO LONG DISTANCE CHARGES) TO
ALLOW MONITORING TO BE CONDUCTED. FOR MULTI-UNIT SITES WITH MORE THAN ONE
uOSM, ADDITIONAL PHONE LINES MAY BE REQUIRED. IN THE EVENT THAT A CSA IS SIGNED,
THE ADDITION OF A HIGH SPEED CONNECTION MAY BE REQUIRED (AT GE EXPENSE), IN
ADDITION TO THE ANALOG PHONE LINES, IN ORDER TO ACCOMMODATE CERTAIN SITE
CIRCUMSTANCES AND ENSURE CONTINUED MONITORING. THE HARDWARE AND
SOFTWARE THAT IS INSTALLED FOR REMOTE MONITORING PURPOSES REMAINS THE
PROPERTY OF GE AND WILL BE REMOVED OR OTHERWISE DISABLED AT THE COMPLETION
OF THE MONITORING PERIOD (UNLESS EXTENDED MONITORING HAS BEEN FURTHER
NEGOTIATED).
7. ALL OPERATOR INTERFACES, INCLUDING THE HMI AND OSM ARE TO BE LOADED WITH
HARDWARE AND SOFTWARE SPECIFIED BY GE POWER SYSTEMS ONLY. THE
INSTALLATION OF ANY SOFTWARE OR HARDWARE NOT AUTHORIZED BY GE POWER
SYSTEMS WILL VOID GE WARRANTY AGREEMENTS AND MAY CAUSE NETWORK INTERFACE
PROBLEMS.

Hardware link (documented in Customer Interface list document )


g A M,Falaki First Issue 06/24/2009
UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.
Rev Originator Revision History Date
PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
1
SIZE DWG. NO. SH. REV.
A3 132B8266 2 A

Single Line Diagram :

GAS #15 GAS #16 GAS #18 GAS #19


GAS #17 GAS #20

GCP15 TCP TCP GCP17 TCP GCP18 TCP GCP19 TCP


GCP16 GCP20 TCP
G17 G18 G19
G15 G16 G20

UNIT DATA HIGHWAY (UDH)-A

Network Time Server NTP1

M M M

OSM Local HMI Local HMI Local HMI Local HMI Local HMI Remote HMI
Local HMI OSM System One System One

20"
UPS- UPS-
230VAC 230VAC
KVM

Inkjet
color
printer

ADH ADH

DCS(1)
PLANT DATA
HIGHWAY
input (PDH)-A
(1)

(1)

NOTE : IF APPLICABLE , THE "M " DENOTES MULTI-UNIT CAPABILITY OF THE HMI
Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
2
SIZE DWG. NO. SH. REV.
A3 132B8266 3 A

Customer Control Room : CCR : Customer Control Room

Network Time Server

IRIG-B NTP1
DCS (1) Server UPS-
230VAC
(1)
Note for Ethernet Standard Protocol :
For MKVIe : OPC Ethernet

(1)
HMI
CRM1_SVR Bently Nevada Bently Nevada
(1) Multi-Unit System One System One
Server
20"
UPS- UPS-
20" 230VAC 230VAC
UDH PDH
KVM
Alarm Printer

PDH1
(1) UPS-
PDH2
Inkjet
PDH1 PDH2

230VAC color
printer

SW65

SW67
SW66
PDH UDH ADH TRUNK
PDH UDH ADH TRUNK PDH UDH ADH TRUNK

UPS- UPS- UPS-


230VAC 230VAC 230VAC

(1)

GT#15 GT#16 GT#17 GT#18 GT#19 GT#20

For details , For details , For details , For details , For details , For details ,
see sheet 4 see sheet 5 see sheet 6 see sheet 7 see sheet 8 see sheet 9

Hardware link (documented in Customer Interface list document )


(1)
UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
3
SIZE DWG. NO. SH. REV.
A3 132B8266 4 A

PEECC For details , see sheet 3 For details , see sheet 3


GT#15 PEECC : GT#15 CCR CCR
(1) (1)
(1)

SW1 UPS-
230VAC

PDH
230VAC
BNG15 GCP15 TCP

AVR Mark VIe G15


GPP
EX2100

UDH
G60A15

G60B15
T60A15
T S R

RIM
EPM15 E15R E15
(M2) (M1)

ADH
TRUNK
Customer
Modem Phone Line
UDH PDH UDH ADH

20"

UPS-
UPS- 230VAC
Uosm
230VAC KVM
HMI
GT15_SVR Uosm is For
Commissioning only
Single-Unit
Alarm Printer

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
4
SIZE DWG. NO. SH. REV.
A3 132B8266 5 A

GT#16 PEECC :
PEECC For details , see sheet 3 For details , see sheet 3
GT#16 CCR CCR
(1) (1) (1)

SW7 UPS-
230VAC

PDH
230VAC
BNG16 GCP16 TCP

GPP
AVR Mark VIe G16
EX2100

UDH
G60A16

G60B16
T60A16
T S R

RIM
EPM16 E16R E16
(M2) (M1)

ADH
TRUNK
UDH PDH

20"

UPS-
HMI 230VAC

GT16_SVR
Single-Unit
Alarm Printer

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
5
SIZE DWG. NO. SH. REV.
A3 132B8266 6 A

GT#17 PEECC :

PEECC For details , see sheet 3 For details , see sheet 3


GT#17 CCR CCR
(1) (1)
(1)

SW13 UPS-
230VAC

PDH
230VAC
BNG17 GCP17 TCP

AVR Mark VIe G17


GPP
EX2100

UDH
G60A17

G60B17
T60A17
T S R

RIM
EPM17 E17R E17
(M2) (M1)

ADH
TRUNK
UDH PDH

20"

UPS-
230VAC
HMI
GT17_SVR
Single-Unit
Alarm Printer

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
6
SIZE DWG. NO. SH. REV.
A3 132B8266 7 A

GT#18 PEECC :

PEECC For details , see sheet 3 For details , see sheet 3


GT#18 CCR CCR
(1) (1) (1)

SW19 UPS-
230VAC

PDH
230VAC
BNG18 GCP18 TCP

GPP
AVR Mark VIe G18
EX2100

UDH
G60A18

G60B18
T60A18
T S R

RIM
EPM18 E18R E18
(M2) (M1)

ADH
TRUNK
Customer
UDH PDH Modem Phone Line
UDH ADH

20"

UPS- UPS-

HMI 230VAC KVM


230VAC Uosm
GT18_SVR
Uosm is For
Single-Unit Commissioning only
Alarm Printer

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
7
SIZE DWG. NO. SH. REV.
A3 132B8266 8 A

GT#19 PEECC :
PEECC For details , see sheet 3 For details , see sheet 3
GT#19 CCR CCR
(1) (1)
(1)

SW25 UPS-
230VAC

PDH
230VAC
BNG19 GCP19 TCP

AVR Mark VIe G19


GPP
EX2100

UDH
G60A19

G60B19
T60A19
T S R

RIM
EPM19 E19R E19
(M2) (M1)

ADH
TRUNK
UDH PDH

20"

UPS-
230VAC
HMI
GT19_SVR
Single-Unit
Alarm Printer

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
8
SIZE DWG. NO. SH. REV.
A3 132B8266 9 A

GT# 20 PEECC : PEECC For details , see sheet 3 For details , see sheet 3
GT#20 CCR CCR
(1) (1) (1)

SW31 UPS-
230VAC

PDH
230VAC
BNG20 GCP6 TCP

GPP
AVR Mark VIe G20
EX2100

UDH
G60A20

G60B20
T60A20
T S R

RIM
EPM20 E20R E20
(M2) (M1)

ADH
TRUNK
UDH PDH

20"

UPS-
HMI 230VAC

GT20_SVR
Single-Unit
Alarm Printer

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
9
SIZE DWG. NO. SH. REV.
A3 132B8266 10 A

Network_Switches_
CCR_1/2 : 1 2 3
PDH
4 5 6 7 8
UDH ADH TRUNK
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26
F.O.

Switch : SW65 Location : CCR IP : Switch : SW66 Location : CCR IP :


192.168.201.185 192.168.201.184
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10 Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems. "8624A.txt". For use in multi vlan systems.
Port_1 CRM1_SVR\PDHA Cat 6 PDH Port_1 Not Used PDH
Port_2 DCS\1 PDH Port_2 Not Used PDH
Port_3 NTP1\LAN1 Cat 6 PDH Port_3 Not Used PDH
Port_4 Not Used Cat 6 PDH Port_4 Not Used PDH
Port_5 Not Used Cat 6 PDH Port_5 Not Used PDH
Port_6 System 1-2\PDHA Cat 6 PDH Port_6 Not Used PDH
Port_7 System 1\PDHA Cat 6 PDH Port_7 Not Used PDH
Port_8 Not Used Cat 6 PDH Port_8 Not Used PDH

Port_9 NTP1\LAN0 Cat 6 UDH Port_9 Not Used UDH


Port_10 Not Used UDH Port_10 Not Used UDH
Port_11 CRM1_SVR\UDHA Cat 6 UDH Port_11 Not Used UDH
Port_12 Not Used Cat 6 UDH Port_12 Not Used UDH
Port_13 Not Used Cat 6 UDH Port_13 Not Used UDH
Port_14 Not Used UDH Port_14 Not Used UDH
Port_15 Not Used UDH Port_15 Not Used UDH
Port_16 Not Used UDH Port_16 Not Used UDH

Port_17 Not Used ADH Port_17 Not Used ADH


Port_18 Not Used ADH Port_18 Not Used ADH
Port_19 Not Used ADH Port_19 Not Used ADH

Port_20 Not Used Crossover Trunk Port_20 SW65\Port_21 Crossover Trunk


Port_21 SW66\Port_20 Crossover Trunk Port_21 SW67\Port_20 Crossover Trunk
Port_22 Not Used Trunk Port_22 Not Used Trunk
Port_23 Not Used Trunk Port_23 Not Used Trunk
Port_24 Not Used Trunk Port_24 Not Used Trunk

FOPort_25 PEECC GT#15\SW1\FOPort_25 Fiber FO FOPort_25 PEECC GT#17\SW13\FOPort_25 Fiber FO


FOPort_26 PEECC GT#16\SW7\FOPort_25 Fiber FO FOPort_26 PEECC GT#18\SW19\FOPort_25 Fiber FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
10
SIZE DWG. NO. SH. REV.
A3 132B8266 11 A

Network_Switches
CCR_2/2 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26
F.O.

Switch : SW67 Location : CCR IP :


192.168.201.183
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 Not Used PDH
Port_2 Not Used PDH
Port_3 Not Used PDH
Port_4 Not Used PDH
Port_5 Not Used PDH
Port_6 Not Used PDH
Port_7 Not Used PDH
Port_8 Not Used PDH

Port_9 Not Used UDH


Port_10 Not Used UDH
Port_11 Not Used UDH
Port_12 Not Used UDH
Port_13 Not Used UDH
Port_14 Not Used UDH
Port_15 Not Used UDH
Port_16 Not Used UDH

Port_17 Not Used ADH


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 SW66\Port_21 Crossover Trunk


Port_21 Not Used Crossover Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used Trunk

FOPort_25 PEECC GT#19\SW25\FOPort_25 Fiber FO


FOPort_26 PEECC GT#20\SW31\FOPort_25 Fiber FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
11
SIZE DWG. NO. SH. REV.
A3 132B8266 12 A

Network_Switches_
GT#15 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26
F.O.

Switch : SW1 Location : PEECC GT#15 IP :


192.168.201.249
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 GT15_SVR\PDHA Cat 6 PDH
Port_2 Not Used PDH
Port_3 GCP15\GPP G60A15 Cat 6 PDH
Port_4 GCP15\GPP T60A15 Cat 6 PDH
Port_5 GCP15\GPP G60B15 Cat 6 PDH
Port_6 GCP15\EPM15 Cat 6 PDH
Port_7 BNG15_RIM Cat 6 PDH
Port_8 Not Used PDH

Port_9 GT15_SVR\UDHA Cat 6 UDH


Port_10 G15\R Cat 6 UDH
Port_11 G15\S Cat 6 UDH
Port_12 G15\T Cat 6 UDH
Port_13 GCP15\AVR_EX2100 M1 Cat 6 UDH
Port_14 GCP15\AVR_EX2100 M2 Cat 6 UDH
Port_15 Not Used UDH
Port_16 uOSM\UDHA Cat 6 UDH

Port_17 uOSM Cat 6 ADH


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 Not Used Trunk


Port_21 Not Used Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used Trunk

FOPort_25 CCR\SW65\FOPort_25 Fiber FO


FOPort_26 Not Used FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
12
SIZE DWG. NO. SH. REV.
A3 132B8266 13 A

Network_Switches_
GT#16 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26
F.O.

Switch : SW7 Location : PEECC GT#16 IP :


192.168.201.243
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 GT16_SVR\PDHA Cat 6 PDH
Port_2 Not Used PDH
Port_3 GCP16\GPP G60A16 Cat 6 PDH
Port_4 GCP16\GPP T60A16 Cat 6 PDH
Port_5 GCP16\GPP G6016 Cat 6 PDH
Port_6 GCP16\EPM16 Cat 6 PDH
Port_7 BNG16_RIM Cat 6 PDH
Port_8 Not Used PDH

Port_9 GT16_SVR\UDHA Cat 6 UDH


Port_10 G16\R Cat 6 UDH
Port_11 G16\S Cat 6 UDH
Port_12 G16\T Cat 6 UDH
Port_13 GCP16\AVR_EX2100 M1 Cat 6 UDH
Port_14 GCP16\AVR_EX2100 M2 Cat 6 UDH
Port_15 Not Used UDH
Port_16 Not Used UDH

Port_17 Not Used ADH


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 Not Used Trunk


Port_21 Not Used Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used

FOPort_25 CCR\SW65\FOPort_26 Fiber FO


FOPort_26 Not Used FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
13
SIZE DWG. NO. SH. REV.
A3 132B8266 14 A

Network_Switches_
GT#17 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
F.O.

Switch : SW13 Location : PEECC GT#17 IP :


192.168.201.237
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 GT17_SVR\PDHA Cat 6 PDH
Port_2 Not Used PDH
Port_3 GCP17\GPP G60A17 Cat 6 PDH
Port_4 GCP17\GPP T60A17 Cat 6 PDH
Port_5 GCP17\GPP G60B17 Cat 6 PDH
Port_6 GCP17\EPM17 Cat 6 PDH
Port_7 BNG17_RIM Cat 6 PDH
Port_8 Not Used PDH

Port_9 GT17_SVR\UDHA Cat 6 UDH


Port_10 G17\R Cat 6 UDH
Port_11 G17\S Cat 6 UDH
Port_12 G17\T Cat 6 UDH
Port_13 GCP17\AVR_EX2100 M1 Cat 6 UDH
Port_14 GCP17\AVR_EX2100 M2 Cat 6 UDH
Port_15 Not Used UDH
Port_16 Not Used UDH

Port_17 Not Used ADH


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 Not Used Trunk


Port_21 Not Used Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used

FOPort_25 CCR\SW66\FOPort_25 Fiber FO


FOPort_26 Not Used FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
14
SIZE DWG. NO. SH. REV.
A3 132B8266 15 A

Network_Switches_
GT#18 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
F.O.

Switch : SW19 Location : PEECC GT#18 IP :


192.168.201.231
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 GT18_SVR\PDHA Cat 6 PDH
Port_2 Not Used PDH
Port_3 GCP18\GPP G60A18 Cat 6 PDH
Port_4 GCP18\GPP T60A18 Cat 6 PDH
Port_5 GCP18\GPP G60B18 Cat 6 PDH
Port_6 GCP18\EPM18 Cat 6 PDH
Port_7 BNG18_RIM Cat 6 PDH
Port_8 Not Used PDH

Port_9 GT18_SVR\UDHA Cat 6 UDH


Port_10 G18\R Cat 6 UDH
Port_11 G18\S Cat 6 UDH
Port_12 G18\T Cat 6 UDH
Port_13 GCP18\AVR_EX2100 M1 Cat 6 UDH
Port_14 GCP18\AVR_EX2100 M2 Cat 6 UDH
Port_15 Not Used UDH
Port_16 uOSM\UDHA Cat 6 UDH

Port_17 uOSM Cat 6 ADH


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 Not Used Trunk


Port_21 Not Used Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used

FOPort_25 CCR\SW66\FOPort_26 Fiber FO


FOPort_26 Not Used FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
15
SIZE DWG. NO. SH. REV.
A3 132B8266 16 A

Network_Switches_
GT#19 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26
F.O.

Switch : SW25 Location : PEECC GT#19 IP :


192.168.201.225
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 GT19_SVR\PDHA Cat 6 PDH
Port_2 Not Used PDH
Port_3 GCP19\GPP G60A19 Cat 6 PDH
Port_4 GCP19\GPP T60A19 Cat 6 PDH
Port_5 GCP19\GPP G60B19 Cat 6 PDH
Port_6 GCP19\EPM19 Cat 6 PDH
Port_7 BNG19_RIM Cat 6 PDH
Port_8 Not Used PDH

Port_9 GT19_SVR\UDHA Cat 6 UDH


Port_10 G19\R Cat 6 UDH
Port_11 G19\S Cat 6 UDH
Port_12 G19\T Cat 6 UDH
Port_13 GCP19\AVR_EX2100 M1 Cat 6 UDH
Port_14 GCP19\AVR_EX2100 M2 Cat 6 UDH
Port_15 Not Used UDH
Port_16 Not Used

Port_17 Not Used


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 Not Used Trunk


Port_21 Not Used Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used

FOPort_25 CCR\SW67\FOPort_25 Fiber FO


FOPort_26 Not Used FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
16
SIZE DWG. NO. SH. REV.
A3 132B8266 17 A

Network_Switches_
GT#20 :
PDH UDH ADH TRUNK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26
F.O.

Switch : SW31 Location : PEECC GT#20 IP :


192.168.201.219
Type :323A4747NZP50A Allied Telesyn AT-8624T/2M-10
Switch with Qty 2 AT-A45/SC Modules, Configuration
"8624A.txt". For use in multi vlan systems.
Port_1 GT20_SVR\PDHA Cat 6 PDH
Port_2 Not Used PDH
Port_3 GCP20\GPP G60A20 Cat 6 PDH
Port_4 GCP20\GPP T60A20 Cat 6 PDH
Port_5 GCP20\GPP G60B20 Cat 6 PDH
Port_6 GCP20\EPM20 Cat 6 PDH
Port_7 BNG20_RIM Cat 6 PDH
Port_8 Not Used PDH

Port_9 GT20_SVR\UDHA Cat 6 UDH


Port_10 G20\R Cat 6 UDH
Port_11 G20\S Cat 6 UDH
Port_12 G20\T Cat 6 UDH
Port_13 GCP20\AVR_EX2100 M1 Cat 6 UDH
Port_14 GCP20\AVR_EX2100 M2 Cat 6 UDH
Port_15 Not Used UDH
Port_16 Not Used UDH

Port_17 Not Used ADH


Port_18 Not Used ADH
Port_19 Not Used ADH

Port_20 Not Used Trunk


Port_21 Not Used Trunk
Port_22 Not Used Trunk
Port_23 Not Used Trunk
Port_24 Not Used

FOPort_25 CCR\SW67\FOPort_26 Fiber FO


FOPort_26 Not Used FO

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
17
SIZE DWG. NO. SH. REV.
A3 132B8266 18 A

IP ADDRESSES : Control Room (CCR) :

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.14 CRM1_SVR Control Room HMI server #1 CCR
192.168.201.81 System 1 Bently Nevada - System 1-2 CCR
192.168.201.82 System 1 Bently Nevada - System 1 CCR
192.168.201.250 NTP1 NTP Time Synch Server #1 CCR
192.168.201.185 SW65 Network Switch - CCR - Primary #1 CCR
192.168.201.184 SW66 Network Switch - CCR - Primary #2 CCR
192.168.201.183 SW67 Network Switch - CCR - Primary #3 CCR

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.14 UCRM1_SVR Control Room HMI server #1 CCR
192.168.101.250 UNTP1 NTP Time Synch Server #1 CCR

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
18
SIZE DWG. NO. SH. REV.
A3 132B8266 19 A

IP ADDRESSES : GT#15 PEECC

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.2 GT15_SVR Local HMI for Gas Turbine #15 GT#15 PEECC
192.168.201.70 BNG15 Bently Nevada 3500 - GT15 GT#15 PEECC
192.168.201.20 G60A15 GCP15 Generator Protection Relay GT#15 PEECC
192.168.201.21 G60B15 GCP15 Generator Protection Relay GT#15 PEECC
192.168.201.22 T60A15 GCP15Transformer Protection Relay GT#15 PEECC
192.168.201.83 EPM15 GCP15 Electrical Power Monitor GT#15 PEECC
192.168.201.249 SW1 Network Switch - GT PEECC 15 - Primary GT#15 PEECC

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.2 UGT15_SVR Local HMI for GT#15 GT#15 PEECC
192.168.101.111 G15-R Gas Unit 1 <R> Controller GT#15 PEECC
192.168.101.112 G15-S Gas Unit 1 <S> Controller GT#15 PEECC
192.168.101.113 G15-T Gas Unit 1 <T> Controller GT#15 PEECC
192.168.101.116 E15 Primary EX2100 Unit 15 GT#15 PEECC
192.168.101.117 E15R Secondary EX2100 Unit 15 GT#15 PEECC
192.168.101.80 UOSM15 On Site Monitoring GT#15 PEECC

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
19
SIZE DWG. NO. SH. REV.
A3 132B8266 20 A

IP ADDRESSES : GT#16 PEECC

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.3 GT16_SVR Local HMI for Gas Turbine #16 GT#16 PEECC
192.168.201.71 BNG16 Bently Nevada 3500 - GT16 GT#16 PEECC
192.168.201.25 G60A16 GCP16 Generator Protection Relay GT#16 PEECC
192.168.201.26 G60B16 GCP16 Generator Protection Relay GT#16 PEECC
192.168.201.27 T60A16 GCP16 Transformer Protection Relay GT#16 PEECC
192.168.201.84 EPM16 GCP16 Electrical Power Monitor GT#16 PEECC
192.168.201.243 SW7 Network Switch - GT PEECC 16 - Primary GT#16 PEECC

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.3 UGT16_SVR Local HMI for GT#16 GT#16 PEECC
192.168.101.121 G16-R Gas Unit 16 <R> Controller GT#16 PEECC
192.168.101.122 G16-S Gas Unit 16 <S> Controller GT#16 PEECC
192.168.101.123 G16-T Gas Unit 16 <T> Controller GT#16 PEECC
192.168.101.126 E16 Primary EX2100 Unit 16 GT#16 PEECC
192.168.101.127 E16R Secondary EX2100 Unit 16 GT#16 PEECC

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
20
SIZE DWG. NO. SH. REV.
A3 132B8266 21 A

IP ADDRESSES : GT#17 PEECC

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.4 GT17_SVR Local HMI for Gas Turbine #17 GT#17 PEECC
192.168.201.72 BNG17 Bently Nevada 3500 - GT17 GT#17 PEECC
192.168.201.30 G60A17 GCP17 Generator Protection Relay GT#17 PEECC
192.168.201.31 G60B17 GCP17 Generator Protection Relay GT#17 PEECC
192.168.201.32 T60A17 GCP17 Transformer Protection Relay GT#17 PEECC
192.168.201.85 EPM17 GCP17 Electrical Power Monitor GT#17 PEECC
192.168.201.237 SW13 Network Switch 13 - GT PEECC 17 - Primary GT#17 PEECC

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.4 UGT17_SVR Local HMI for GT#17 GT#17 PEECC
192.168.101.131 G17-R Gas Unit 17 <R> Controller GT#17 PEECC
192.168.101.132 G17-S Gas Unit 17 <S> Controller GT#17 PEECC
192.168.101.133 G17-T Gas Unit 17 <T> Controller GT#17 PEECC
192.168.101.136 E17 Primary EX2100 Unit 17 GT#17 PEECC
192.168.101.137 E17R Secondary EX2100 Unit 17 GT#17 PEECC

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
21
SIZE DWG. NO. SH. REV.
A3 132B8266 22 A

IP ADDRESSES : GT#18 PEECC

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.5 GT18_SVR Local HMI for Gas Turbine #18 GT#18 PEECC
192.168.201.73 BNG18 Bently Nevada 3500 - GT18 GT#18 PEECC
192.168.201.35 G60A18 GCP18 Generator Protection Relay GT#18 PEECC
192.168.201.36 G60B18 GCP18 Generator Protection Relay GT#18 PEECC
192.168.201.37 T60A18 GCP18 Transformer Protection Relay GT#18 PEECC
192.168.201.86 EPM18 GCP18 Electrical Power Monitor GT#18 PEECC
192.168.201.231 SW19 Network Switch 19 - GT PEECC 18 - Primary GT#18 PEECC

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.5 UGT18_SVR Local HMI for GT#18 GT#18 PEECC
192.168.101.141 G18-R Gas Unit 18 <R> Controller GT#18 PEECC
192.168.101.142 G18-S Gas Unit 18 <S> Controller GT#18 PEECC
192.168.101.143 G18-T Gas Unit 18 <T> Controller GT#18 PEECC
192.168.101.146 E18 Primary EX2100 Unit 18 GT#18 PEECC
192.168.101.147 E18R Secondary EX2100 Unit 18 GT#18 PEECC
192.168.101.41 UOSM17 On Site Monitoring GT#17 PEECC

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
22
SIZE DWG. NO. SH. REV.
A3 132B8266 23 A

IP ADDRESSES : GT#19 PEECC

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.6 GT19_SVR Local HMI for Gas Turbine #19 GT#19 PEECC
192.168.201.74 BNG19 Bently Nevada 3500 - GT19 GT#19 PEECC
192.168.201.40 G60A19 GCP19 Generator Protection Relay GT#19 PEECC
192.168.201.41 G60B19 GCP19 Generator Protection Relay GT#19 PEECC
192.168.201.42 T60A19 GCP19 Transformer Protection Relay GT#19 PEECC
192.168.201.87 EPM19 GCP19 Electrical Power Monitor GT#19 PEECC
192.168.201.225 SW25 Network Switch - GT PEECC 19 - Primary GT#19 PEECC

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.6 UGT19_SVR Local HMI for GT#19 GT#19 PEECC
192.168.101.151 G19-R Gas Unit 19 <R> Controller GT#19 PEECC
192.168.101.152 G19-S Gas Unit 19 <S> Controller GT#19 PEECC
192.168.101.153 G19-T Gas Unit 19 <T> Controller GT#19 PEECC
192.168.101.156 E19 Primary EX2100 Unit 19 GT#19 PEECC
192.168.101.157 E19R Secondary EX2100 Unit 19 GT#19 PEECC

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
23
SIZE DWG. NO. SH. REV.
A3 132B8266 24 A

IP ADDRESSES : GT#20 PEECC

PDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.201.7 GT20_SVR Local HMI for Gas Turbine #20 GT#20 PEECC
192.168.201.75 BNG20 Bently Nevada 3500 - GT20 GT#20 PEECC
192.168.201.45 G60A20 GCP20 Generator Protection Relay GT#20 PEECC
192.168.201.46 G60B20 GCP20 Generator Protection Relay GT#20 PEECC
192.168.201.47 T60A20 GCP20 Transformer Protection Relay GT#20 PEECC
192.168.201.88 EPM20 GCP20 Electrical Power Monitor GT#20 PEECC
192.168.201.219 SW31 Network Switch - GT PEECC 20 - Primary GT#20 PEECC

UDH Addresses
IP ADDRESS NAME DESCRIPTION LOCATION
192.168.101.7 UGT20_SVR Local HMI for GT#20 GT#20 PEECC
192.168.101.161 G20-R Gas Unit 20 <R> Controller GT#20 PEECC
192.168.101.162 G20-S Gas Unit 20 <S> Controller GT#20 PEECC
192.168.101.163 G20-T Gas Unit 20 <T> Controller GT#20 PEECC
192.168.101.166 E20 Primary EX2100 Unit 20 GT#20 PEECC
192.168.101.167 E20R Secondary EX2100 Unit 20 GT#20 PEECC

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
24
SIZE DWG. NO. SH. REV.
A3 132B8266 25 A

Glossary of Terms :

ADH : Atlanta Data Highway


AVR : Automatic Voltage Controly
BN : Bently Nevada Panel
CCR : Customer Control Room
CRM : Control Remote
DACA : AC / DC Power Convertion Modul
DCS : Distributed Control System
EMAP : Performance Monitoring System
EPM : Energy Power Meter
GCP : Generator Control Panel
GPP : Generator Protection Panel
HMI : Human Machine Interface
HST : Historian
MOXA : RS-485 / TCP-IP Modbus Converter
NTP : Network Time Protocol
OSM : On Site Monitoring
PDH : Plant Data Highway Network
PEECC:Package Electronic and Electrical Control Cabinet
RIM : Rack Interface Module
SVR : Server
SW : Switch
TCP : Turbine Control Panel
UDH : Unit Data Highway Network
UPS : Uninterrupted Power Supply
UTP : Unshielded Twisted Pair

Hardware link (documented in Customer Interface list document )

UDH: Unit Data Highway. Unshielded Twisted Pair (UTP) cable, 4 pair, Category 6, RJ-45 connectors.

PDH: Plant Data Highway. (UTP) cable, 4 pair, Category 6, RJ-45 connectors. SIZE CAGE CODE DWG NO
4108
Trunk: cross-over UTP cable is used to connect a switch to a switch. g GE Energy Products - Europe A3
E0876
NINAWA
NETWORK TOPOLOGY
Fiber Optic: Multimode - Maximum 2KM - SC type connectors. 132B8269

DISTR
DRAWN 24-June-2009 M. FALAKI
Modulated IRIG-B time code signal, RG-58 Coaxial cable, BNC connector

TO
SCALE CONT ON SHEET
25