You are on page 1of 15

Chiller Main chilled water pump

% of Full Load Total Capacity Total Capacity % load per Total Input Cooling COP % load per Total Input
Chiller
Chiller pump
(%) (kW) (RT) (kW) (kW/kW) (kW/kW) (kW)
100.0 3400.00 966.62 2x 1700 kW 100.00 579.40 5.868 0.5994 100.00 50.240
90.0 3060.00 869.96 2x 1700 kW 90.00 457.80 6.684 0.5262 90.00 37.051
80.0 2720.00 773.30 2x 1700 kW 80.00 352.60 7.714 0.4560 80.00 26.771
70.0 2380.00 676.63 2x 1700 kW 70.00 271.40 8.769 0.4011 70.00 18.906
60.0 2040.00 579.97 2x 1700 kW 60.00 197.62 10.323 0.3407 65.00 16.351
50.0 1700.00 483.31 2x 1700 kW 50.00 138.90 12.239 0.2874 65.00 16.351
40.0 1360.00 386.65 2x 1700 kW 40.00 101.00 13.465 0.2612 65.00 16.351
30.0 1020.00 289.99 1x 1700 kW 60.00 98.81 10.323 0.3407 65.00 8.176
20.0 680.00 193.32 1x 850 kW 80.00 85.12 7.989 0.4403 80.00 13.385
10.0 340.00 96.66 1x 850 kW 40.00 24.87 13.671 0.2573 65.00 8.176
led water pump Second chilled water pump Condensated water pump Cooling tower
Heat reject
Cooling % load per Total Input kW Cooling % load per Total Input kW Cooling % load per Total Input kW Cooling
capacity per CT
pump pump CT
(kW/RT) (kW) (kW/RT) (kW) (kW/RT) (kW) (kW) (kW/RT)
0.0520 100.0 20.190 0.0209 100 40.380 0.0418 1989.70 100 27.176 0.0281
0.0426 90.0 16.466 0.0189 100 40.380 0.0464 1758.90 88.40 21.912 0.0252
0.0346 80.0 13.427 0.0174 100 40.380 0.0522 1536.30 77.21 17.186 0.0222
0.0279 70.0 10.989 0.0162 100 40.380 0.0597 1325.70 66.63 13.104 0.0194
0.0282 60.0 9.067 0.0156 100 40.380 0.0696 1118.81 56.23 9.528 0.0164
0.0338 50.0 7.577 0.0157 100 40.380 0.0835 919.45 46.21 6.551 0.0136
0.0423 40.0 6.435 0.0166 100 40.380 0.1044 730.50 36.71 4.204 0.0109
0.0282 30.0 5.557 0.0192 100 20.190 0.0696 1118.81 56.23 4.764 0.0164
0.0692 20.0 4.858 0.0251 100 15.000 0.0776 765.12 76.28 4.203 0.0217
0.0846 10.0 4.255 0.0440 100 15.000 0.1552 364.87 36.38 1.032 0.0107
Chiller HXE 1700kW
% of Full Load Capacity kW Input kW Cooling COP kW/kW Cooling kW/RT
100.0 1700.00 289.70 5.868 0.5993
90.0 1530.00 228.90 6.683 0.5263
80.0 1360.00 176.30 7.715 0.4559
70.0 1190.00 135.70 8.768 0.4011
60.0 1020.00 98.81 10.320 0.3407
50.0 850.00 69.45 12.240 0.2874
40.0 680.00 50.50 13.470 0.2612
30.0 510.00 39.48 12.920 0.2722
20.0 340.00 23.44 14.510 0.2424
10.0 262.90 19.23 13.670 0.2572

Chiller HXE 850kW


% of Full Load Capacity kW Input kW Cooling COP kW/kW Cooling kW/RT
100.0 850.00 140.30 6.060 0.5804
90.0 765.00 110.20 6.939 0.5068
80.0 680.00 85.12 7.988 0.4403
70.0 595.00 64.06 9.288 0.3786
60.0 510.00 46.37 11.000 0.3197
50.0 425.00 31.81 13.360 0.2633
40.0 340.00 24.87 13.670 0.2573
30.0 255.00 16.92 15.070 0.2333
20.0 170.00 11.54 14.730 0.2387
10.0 149.50 10.34 14.460 0.2432
Main Chilled Water Pump
Pump power ratio
C3 C2 C1 C0
1.636421527 -1.523252514 1.084897777 -0.197989715

Max power (kW) 25.12 Max flow (l/s) 57.93

Pump partload Power fraction Pump rated Power


100 1.0000 25.12 25.1200
90 0.7375 25.12 18.5255
80 0.5329 25.12 13.3853
70 0.3763 25.12 9.4529
65 0.3130 26.12 8.1755
60 0.2580 25.12 6.4816
50 0.1682 25.12 4.2248
40 0.0970 25.12 2.4359
30 0.0346 25.12 0.8683
20 - - -
10 - - -

Second Chilled Water Pump


Pump power ratio
C3 C2 C1 C0
0.695492445 -0.180691762 0.304395355 0.181607567

Max power (kW) 20.19 Max flow (l/s) 63

Pump partload Power fraction Pump rated Power


100 1.0000 20.19 20.1900
90 0.8156 20.19 16.4662
80 0.6650 20.19 13.4271
70 0.5443 20.19 10.9887
60 0.4491 20.19 9.0665
50 0.3753 20.19 7.5766
40 0.3187 20.19 6.4348
30 0.2752 20.19 5.5567
20 0.2406 20.19 4.8583
10 0.2108 20.19 4.2554
Cnorm
1.000077075 Power vs Pump partload
30

25

20

Power 15 Power

10

Minimun part load 0


100 90 80 70 65 60 50 40 30
Pump partload

Cnorm
1.00080336800396 Power vs Pump partload
25

20

15
Power

Power
10

0
100 90 80 70 60 50 40 30 20 10
Pump partload
Power

Power
Condensated Water Pump for Chiller 1700kW
Pump power ratio
C3 C2 C1 C0 Cnorm
-0.005453596 0.353486911 0.331224635 0.321108704 1.000366654

Max power (kW) 20.19 Max flow (l/s) 95.54

Pump partload Power fraction Pump rated Power


100 1.0000 20.19 20.1900
90 0.9012 20.19 18.1958
80 0.8092 20.19 16.3384
70 0.7240 20.19 14.6183
60 0.6457 20.19 13.0364
50 0.5742 20.19 11.5931
40 0.5096 20.19 10.2892
30 0.4520 20.19 9.1254
20 0.4013 20.19 8.1023
10 0.3576 20.19 7.2205

Condensate Water Pump for Chiller 850kW


Pump power ratio
C3 C2 C1 C0 Cnorm
0.313319075968326 -1.33960073215469 2.02925754240802 -0.00182599411387606 1.00114989210778

Max power (kW) 15 Max flow (l/s) 47.81

Pump partload Power fraction Pump rated Power


100 1.0000 15 15.0000
90 0.9667 15 14.5009
80 0.9236 15 13.8539
70 0.8687 15 13.0308
60 0.8002 15 12.0034
50 0.7162 15 10.7437
40 0.6149 15 9.2233
30 0.4943 15 7.4142
20 0.3525 15 5.2881
10 0.1878 15 2.8170
Power vs Pump partload
25

20

15
Power

Column E
10

0
100 90 80 70 60 50 40 30 20 10
Pump partload

Power vs Pump partload


25

20

15
Power

Column E
10

5
20

15

Power
Column E
10

0
100 90 80 70 60 50 40 30 20 10
Pump partload
Cooling tower
CT power ratio
C3 C2 C1 C0
-0.345874057214263 1.42573430496847 -0.093178789791455 0.01392103233046

Max Fan power (kW) 13.58

CT partload Power fraction Fan power rated Fan power


100 1.0006 13.58 13.5882
90 0.8328 13.58 11.3089
80 0.6748 13.58 9.1632
70 0.5287 13.58 7.1794
60 0.3966 13.58 5.3854
50 0.2805 13.58 3.8096
40 0.1826 13.58 2.4801
30 0.1049 13.58 1.4252
20 0.0495 13.58 0.6729
10 0.0185 13.58 0.2514

Max Fan power (kW) 6.79

CT partload Power fraction Fan power rated Fan power


100 1.0006 6.79 6.7941
90 0.8328 6.79 5.6545
80 0.6748 6.79 4.5816
70 0.5287 6.79 3.5897
60 0.3966 6.79 2.6927
50 0.2805 6.79 1.9048
40 0.1826 6.79 1.2401
30 0.1049 6.79 0.7126
20 0.0495 6.79 0.3364
10 0.0185 6.79 0.1257
Fan power vs CT partload
16

14

12

10
Fan power

8 Column E

0
100 90 80 70 60 50 40 30 20 10
CT partload

Fan power vs CT partload


8

5
Fan power

4 Column E

0
100 90 80 70 60 50 40 30 20 10
CT partload

You might also like