1350x1400
RA DUCT

RA DUCT
900x1100

900x1100
SA DUCT
DA

SECTION X-X
(SCALE 1:50)
INSULATION THICKNESS FOR
BILL OF QUANTITIES FOR CHILLED WATER & DRAIN PIPES
CAL EXIT ECR 2ND. FL. (GRID 20A - 25) 34836 CFM AHU (2 NOS) SL. PIPE SIZE THICKNESS
NO. DN (mm.) (mm.)

ITEM
DESCRIPTION SIZE QTY

BUTTERFLY VALVE 80 10

BALANCING VALVE 80 2

Y-STRANER 80 2

3-WAY MIXING VALVE 65 2

PRESSURE GAUGE 04

DB TEMPERATURE GAUGE 04
SUPPORTING SPAN OF PIPES
X

BILL OF QUANTITIES FOR SUPPORT SL. PIPE SIZE SUPPORTING


NO. DN (mm.) SPAN (m)
SL. SIZE SUPPORT LENGTH WEIGHT WEIGHT QTY
NO. (mm.) TYPE RMT KG/MT KG/PL (NOS.)

BILL OF QUANTITIES FOR SL.NO. AHU TAG AHU TR/CFM


PURGE VALVE
SL. PIPE SIZE QUANTITY

24 24A 24B 25 NO. DN (mm.) (NOS.)

BILL OF QUANTITIES FOR BILL OF QUANTITIES FOR


CHILLED WATER PIPES REDUCERS
SL. PIPE SIZE LENGTH SL. SIZE QUANTITY
NO. DN (mm.) (m) NO. DN (mm.) (NOS.) BILL OF QUANTITIES FOR
ELBOWS

PLAN VIEW OF CAL EXIT ECR SECOND FL. SL. PIPE SIZE
NO. DN (mm.)
QUANTITY
(NOS.)

(SCALE 1:40)
BILL OF QUANTITIES FOR PIPE INSULATION

SL. PIPE SIZE INSULATION LENGTH


NO. DN (mm.) THIK (mm.) (RMT)
BILL OF QUANTITIES FOR
INSULATED DRAIN PIPES
SL. PIPE SIZE LENGTH
NO. DN (mm.) (m)

CHWR HEADER THERMOSTAT

CABLE

CHWR
CHWS HEADER

FM AHU

CHWS
S-2
TYP AHU CONNECTION DETAIL DRAIN

S-1
NOTES
1. ALL DIMENSIONS ARE IN MM, UNLESS OTHERWISE SPECIFIED.
TATA STEEL LIMITED
2. ALL SUPPORTING ARRANGEMENT STRUCTURE ie. BRAKET, HILTI SUPPORT , CHANEL, PLATE, ANCHOR SHALL BE IN SCOPE OF VOLTAS.
3. PIPES SHALL BE INSULATED AS PER AGREED TS & BOQ WITH TSL
4. ALL HVAC EQUIPMENT CIVIL & STRUCTURAL FOUNDATION IS IN CLIENT SCOPE. SHOWN HERE FOR REFERENCE ONLY. ALL FOUNDATION OF
HVAC EQUIPMENT SHOULD BE DESIGNED & DONE BY OTHERS.
5. INSULATION OF PIPES SHALL BE AS PER SPECIFICATION NO. -- GSP-01-00-00-14-000-004
6. PIPING SHALL BE AS PER GENERAL SPECIFICATION NO. -- STD-21-00-15-11-000-001-R1
7. PAINTING TO BE AS PER GENERAL SPECIFICATION NO. -- GSP-01-00-00-14-000-001
8. EQUIPMENT SIZE ARE TENTATIVE AND SHALL BE FINALIZED AFTER RECEIVED / APPROVAL OF GA.
9. ERECTION OF CHILLED WATER PIPING FROM SHOP PIPING TOP (AS PER CONTRACT) TO AHU MANIFOLD AND DRAIN PIPING FROM AHU TO
NEAREST SURFACE DRAIN WILL BE IN UMPESL SCOPE.
10. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH DWG NO. -- PIP-12-01-07-10-000-002-R0,
LYT-12-01-07-11-000-004-R0 & CDW-12-01-04-05-009-254-R0

DRG.No.