DAILY REPORT

MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 14/06/2022


PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 COAL BURNER FRONT Control Panel NOTIFIER - NFS 640 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC LFAP-1 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector EL.22 FRONT 50SGC24CT013 PASS V


Heat Detector EL.22 FRONT 50SGC24CT014 PASS V
Heat Detector EL.22 FRONT 50SGC24CT015 PASS V
Heat Detector EL.22 FRONT 50SGC24CT016 PASS V
Heat Detector EL.22 FRONT 50SGC24CT017 PASS V
Heat Detector EL.22 FRONT 50SGC24CT018 PASS V
Heat Detector EL.27 FRONT 50SGC24CT019 PASS V
Heat Detector EL.27 FRONT 50SGC24CT020 PASS V
Heat Detector EL.27 FRONT 50SGC24CT021 PASS V
Heat Detector EL.27 FRONT 50SGC24CT022 PASS V
Heat Detector EL.27 FRONT 50SGC24CT023 PASS V
Heat Detector EL.27 FRONT 50SGC24CT024 PASS V
Heat Detector EL. 32 FRONT 50SGC24CT025 PASS V
Heat Detector EL. 32 FRONT 50SGC24CT026 PASS V
Heat Detector EL. 32 FRONT 50SGC24CT027 PASS V
Heat Detector EL. 32 FRONT 50SGC24CT028 PASS V
Heat Detector EL. 32 FRONT 50SGC24CT029 PASS V
Heat Detector EL. 32 FRONT 50SGC24CT030 PASS V

Deluge Water Valve EL.22 PAS V


Deluge Water Valve EL.27 PAS V
Deluge Water Valve EL.32

Selenoid Coal Burner El.22 50SGC23AA211 PAS V


Selenoid Coal Burner El.27 50SGC23AA221 PAS V
Selenoid Coal Burner El.32 50SGC23AA231

Pressure Switch El.22 50SGC23CP311 PAS V


Pressure Switch El.27 50SGC23CP321 PAS V
Pressure Switch El.32 50SGC23CP331

Supervisiory Limit switch El.22 50SGC23CG311 PAS V


Supervisiory Limit switch El.22 50SGC23CG312 PAS V
Supervisiory Limit switch El.27 50SGC23CG321 PAS V
Supervisiory Limit switch El.27 50SGC23CG322 PAS V
Supervisiory Limit switch El.32 50SGC23CG331 PAS V
Supervisiory Limit switch El.32 50SGC23CG332 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L2-OFF-U5-SGY-I-DGA-0001 FIRE DETECTION EQUIPMENT ARRANGEMENT DRAWING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 13/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 COAL BURNER REAR Control Panel NOTIFIER - NFS 640 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC LFAP-1 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector EL.22 REAR 50SGC24CT009 PASS V


Heat Detector EL.22 REAR 50SGC24CT010 PASS V
Heat Detector EL.22 REAR 50SGC24CT011 PASS V
Heat Detector EL.22 REAR 50SGC24CT012 PASS V
Heat Detector EL.22 REAR 50SGC24CT013 PASS V
Heat Detector EL.22 REAR 50SGC24CT014 PASS V
Heat Detector EL.27 REAR 50SGC24CT015 PASS V
Heat Detector EL.27 REAR 50SGC24CT016 PASS V
Heat Detector EL.27 REAR 50SGC24CT017 PASS V
Heat Detector EL.27 REAR 50SGC24CT018 PASS V
Heat Detector EL.27 REAR 50SGC24CT019 PASS V
Heat Detector EL.27 REAR 50SGC24CT020 PASS V
Heat Detector EL. 32 REAR 50SGC24CT021 PASS V
Heat Detector EL. 32 REAR 50SGC24CT022 PASS V
Heat Detector EL. 32 REAR 50SGC24CT023 PASS V
Heat Detector EL. 32 REAR 50SGC24CT024 PASS V
Heat Detector EL. 32 REAR 50SGC24CT025 PASS V
Heat Detector EL. 32 REAR 50SGC24CT026 PASS V

Deluge Water Valve EL.22 PAS V


Deluge Water Valve EL.27 PAS V
Deluge Water Valve EL.32

Selenoid Coal Burner El.22 50SGC24AA211 PAS V


Selenoid Coal Burner El.27 50SGC24AA221 PAS V
Selenoid Coal Burner El.32 50SGC24AA231

Pressure Switch El.22 50SGC24CP311 PAS V


Pressure Switch El.27 50SGC24CP321 PAS V
Pressure Switch El.32 50SGC24CP331

Supervisiory Limit switch El.22 50SGC24CG311 PAS V


Supervisiory Limit switch El.22 50SGC24CG312 PAS V
Supervisiory Limit switch El.27 50SGC24CG321 PAS V
Supervisiory Limit switch El.27 50SGC24CG322 PAS V
Supervisiory Limit switch El.32 50SGC24CG331 PAS V
Supervisiory Limit switch El.32 50SGC24CG332 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L2-OFF-U5-SGY-I-DGA-0001 FIRE DETECTION EQUIPMENT ARRANGEMENT DRAWING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 13/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 COAL BUNKER Control Panel NOTIFIER - NFS 640 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC LFAP-1 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC25CT031 PASS V


Heat Detector 50SGC25CT032 PASS V
Heat Detector 50SGC25CT033 PASS V
Heat Detector 50SGC25CT034 PASS V
Heat Detector 50SGC25CT035 PASS V
Heat Detector 50SGC25CT036 PASS V
Heat Detector 50SGC25CT037 PASS V
Heat Detector 50SGC25CT038 PASS V
Heat Detector 50SGC25CT039 PASS V
Heat Detector 50SGC25CT040 PASS V
Heat Detector 50SGC25CT041 PASS V
OPEN INDICATION, RESISTOR BROKEN, NEED
Heat Detector 50SGC25CT042 TROUBLE V RESISTOR, RESISTOR WILL BE INSTAL NEXT
DAY

Deluge Water Valve COAL BUNKER A PAS V GONG BELL LOOSE, ALREADY TIGHTENING
Deluge Water Valve COAL BUCKER B PAS V
Deluge Water Valve COAL BUCKER C PAS V
Deluge Water Valve COAL BUCKER D PAS V
Deluge Water Valve COAL BUCKER E PAS V
Deluge Water Valve COAL BUCKER F PAS V

Selenoid Coal Feader A 50SGC25AA211 PAS V


Selenoid Coal Feader B 50SGC25AA221 PAS V
Selenoid Coal Feader C 50SGC25AA231 PAS V
Selenoid Coal Feader D 50SGC25AA241 PAS V
Selenoid Coal Feader E 50SGC25AA251 PAS V
Selenoid Coal Feader F 50SGC25AA261 PAS V

Pressure Switch A 50SGC25CP311 PAS V


Pressure Switch B 50SGC25CP321 PAS V
Pressure Switch C 50SGC25CP331 PAS V
Pressure Switch D 50SGC25CP341 PAS V
Pressure Switch E 50SGC25CP351 PAS V
Pressure Switch F 50SGC25CP361 PAS V

Supervisiory Limit switch A 50SGC25CG311 PAS V


Supervisiory Limit switch A 50SGC25CG312 PAS V
Supervisiory Limit switch B 50SGC22CG321 PAS V
Supervisiory Limit switch B 50SGC22CG322 PAS V
Supervisiory Limit switch C 50SGC22CG331 PAS V
Supervisiory Limit switch C 50SGC22CG332 PAS V
Supervisiory Limit switch D 50SGC22CG341 PAS V
Supervisiory Limit switch D 50SGC22CG342 PAS V
Supervisiory Limit switch E 50SGC22CG351 PAS V
Supervisiory Limit switch E 50SGC22CG352 PAS V
Supervisiory Limit switch F 50SGC22CG361 PAS V
Supervisiory Limit switch F 50SGC22CG362 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L2-OFF-U5-SGY-I-DGA-0001 FIRE DETECTION EQUIPMENT ARRANGEMENT DRAWING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 10/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 AIR PREHEATER Control Panel NOTIFIER - NFS 640 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC LFAP-1 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

HEAT DETECTOR HAVE INTERMITEN


Heat Detector 50SGC22CT001 PASS
V NEED REPLACEMENT
Heat Detector 50SGC22CT002 PASS V
Heat Detector 50SGC22CT003 PASS V
Heat Detector 50SGC22CT004 PASS V
Heat Detector 50SGC22CT005 PASS V
Heat Detector 50SGC22CT006 PASS V
Heat Detector 50SGC22CT007 PASS V
Heat Detector 50SGC22CT008 PASS V

Deluge Water Valve AIR PREHEATER UNIT 1 PAS V


Deluge Water Valve AIR PREHEATER UNIT 2 PAS V

Selenoid Coal Feader 1 50SGC22AA221 PAS V


Selenoid Coal Feader 2 50SGC22AA211 PAS V

Pressure Switch 1 50SGC22CP321 PAS V


Pressure Switch 2 50SGC22CP311 PAS V

Supervisiory Limit switch 1 50SGC22CG321 PAS V


Supervisiory Limit switch 1 50SGC22CG322 PAS V
Supervisiory Limit switch 2 50SGC22CG311 PAS V
Supervisiory Limit switch 2 50SGC22CG312 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L2-OFF-U5-SGY-I-DGA-0001 FIRE DETECTION EQUIPMENT ARRANGEMENT DRAWING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 COAL FEADER Control Panel NOTIFIER - NFS 640 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC LFAP-1 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC26CT001 PASS V


Heat Detector 50SGC26CT002 PASS V
Heat Detector 50SGC26CT003 PASS V
Heat Detector 50SGC26CT004 PASS V
Heat Detector 50SGC26CT005 PASS V
Heat Detector 50SGC26CT006 PASS V
Heat Detector 50SGC26CT007 PASS V
Heat Detector 50SGC26CT008 PASS V
Heat Detector 50SGC26CT009 PASS V
Heat Detector 50SGC26CT010 PASS V
Heat Detector 50SGC26CT011 PASS V
Heat Detector 50SGC26CT012 PASS V

Deluge Water Valve COAL FEAFER A PAS V


Deluge Water Valve COAL FEAFER B PAS V
Deluge Water Valve COAL FEAFER C PAS V
Deluge Water Valve COAL FEAFER D PAS V
Deluge Water Valve COAL FEAFER E PAS V
Deluge Water Valve COAL FEAFER F PAS V

Selenoid Coal Feader A 50SGC26AA211 PAS V


Selenoid Coal Feader B 50SGC26AA221 PAS V
Selenoid Coal Feader C 50SGC26AA231 PAS V
Selenoid Coal Feader D 50SGC26AA241 PAS V
Selenoid Coal Feader E 50SGC26AA251 PAS V
Selenoid Coal Feader F 50SGC26AA361 PAS V

Pressure Switch A 50SGC26CP311 PAS V


Pressure Switch B 50SGC26CP321 PAS V
Pressure Switch C 50SGC26CP331 PAS V
Pressure Switch D 50SGC26CP341 PAS V
Pressure Switch E 50SGC26CP351 PAS V
Pressure Switch F 50SGC26CP361 PAS V

Supervisiory Limit switch A 50SGC26CG311 PAS V


Supervisiory Limit switch A 50SGC26CG312 PAS V
Supervisiory Limit switch B 50SGC26CG321 PAS V
Supervisiory Limit switch B 50SGC26CG322 PAS V
Supervisiory Limit switch C 50SGC26CG331 PAS V
Supervisiory Limit switch C 50SGC26CG332 PAS V
Supervisiory Limit switch D 50SGC26CG341 PAS V
Supervisiory Limit switch D 50SGC26CG342 PAS V
Supervisiory Limit switch E 50SGC26CG351 PAS V
Supervisiory Limit switch E 50SGC26CG352 PAS V
Supervisiory Limit switch F 50SGC26CG361 PAS V
Supervisiory Limit switch F 50SGC26CG362 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L2-OFF-U5-SGY-I-DGA-0001 FIRE DETECTION EQUIPMENT ARRANGEMENT DRAWING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( () )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 LUBRICATION AND COOLING OIL Control Panel NOTIFIER - NFS 320 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC 50SGC06GH001 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC06CT200 PASS V


Heat Detector 50SGC06CT201 PASS V
Heat Detector 50SGC06CT202 PASS V
Heat Detector 50SGC06CT203 PASS V
Heat Detector 50SGC06CT204 PASS V
Heat Detector 50SGC06CT205 PASS V
Heat Detector 50SGC06CT206 PASS V
Heat Detector 50SGC06CT207 PASS V

Local Operation Box 50SGE06CH001 PAS V

Horn Strobe 50SGE06EH001 PAS V

Deluge Water Valve 50SGC01AA202 PAS V

Selenoid 50SGC06AA401 PAS V

Pressure Switch 50SGC06CP301 PAS V

Supervisiory Limit switch 50SGE06CG301 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L1-OFF-C-SGY-I-DGA-3110 FIRE DETECTION AND ALARM SYSTEM ARRANGEMENT FOR TURBINE BUILDING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 SEAL OIL GENERATOR Control Panel NOTIFIER - NFS 320 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC 50SGC05GH001 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC05CT200 PASS V


Heat Detector 50SGC05CT201 PASS V
Heat Detector 50SGC05CT202 PASS V
Heat Detector 50SGC05CT203 PASS V

Local Operation Box 50SGC05CH001 PAS V

Horn Strobe 50SGC05EH001 PAS V

Deluge Water Valve 50SGC01AA202 PAS V

Selenoid 50SGC05AA401 PAS V

Pressure Switch 50SGC05CP001 PAS V

Supervisiory Limit switch 50SGC05CG301 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L1-OFF-C-SGY-I-DGA-3110 FIRE DETECTION AND ALARM SYSTEM ARRANGEMENT FOR TURBINE BUILDING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 EXCITATION TRANSFORMER Control Panel NOTIFIER - NFS 320 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC 50SGC00GH002 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC02CT200 PASS V


Heat Detector 50SGC02CT201 PASS V
Heat Detector 50SGC02CT202 PASS V
Heat Detector 50SGC02CT203 PASS V

Local Operation Box 50SGC04CH003 PAS V

Horn Strobe 50SGC05EH003 PAS V

Deluge Water Valve 50SGC01AA202 PAS V

Selenoid 50SGC02AA401 PAS V

Pressure Switch 50SGC02CP301 PAS V

Supervisiory Limit switch 50SGC02CG301 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L1-OFF-C-SGY-I-DGA-3110 FIRE DETECTION AND ALARM SYSTEM ARRANGEMENT FOR TURBINE BUILDING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 GENERATOR TRANSFORMER Control Panel NOTIFIER - NFS 320 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC 50SGC00GH002 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC01CT200 PASS V


Heat Detector 50SGC01CT201 PASS V
Heat Detector 50SGC01CT202 PASS V
Heat Detector 50SGC01CT203 PASS V
Heat Detector 50SGC01CT204 PASS V
Heat Detector 50SGC01CT205 PASS V
Heat Detector 50SGC01CT206 PASS V
Heat Detector 50SGC01CT207 PASS V
Heat Detector 50SGC01CT208 PASS V
Heat Detector 50SGC01CT209 PASS V
Heat Detector 50SGC01CT210 PASS V
Heat Detector 50SGC01CT211 PASS V

Local Operation Box 50SGC04CH005 PAS V

Horn Strobe 50SGC05EH004 PAS V

Deluge Water Valve 50SGC01AA201 PAS V

Selenoid 50SGC01AA401 PAS V

Pressure Switch 50SGC01CP301 PAS V

Supervisiory Limit switch 50SGC01CG301 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L1-OFF-C-SGY-I-DGA-3110 FIRE DETECTION AND ALARM SYSTEM ARRANGEMENT FOR TURBINE BUILDING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 TRANSFORMER A Control Panel NOTIFIER - NFS 320 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC 50SGC00GH002 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC03CT200 PASS V


Heat Detector 50SGC03CT201 PASS V
Heat Detector 50SGC03CT202 PASS V
Heat Detector 50SGC03CT203 PASS V
Heat Detector 50SGC03CT204 PASS V
Heat Detector 50SGC03CT205 PASS V
Heat Detector 50SGC03CT206 PASS V
Heat Detector 50SGC03CT207 PASS V

Local Operation Box 50SGC04CH002 PAS V

Horn Strobe 50SGC05EH002 PAS V

Deluge Water Valve 50SGC01AA203 PAS V

Selenoid 50SGC03AA401 PAS V

Pressure Switch 50SGC03CP301 PAS V

Supervisiory Limit switch 50SGC03CG301 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L1-OFF-C-SGY-I-DGA-3110 FIRE DETECTION AND ALARM SYSTEM ARRANGEMENT FOR TURBINE BUILDING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
DAILY REPORT
MAINTENANCE FIRE ALARM SYSTEM REPORT DATE: 09/06/2022
PT. BUMI JEPARA SERVICE. – TJ JATI UNIT 5&6 SPV: BP. HASANUDIN
Desa Tubanan, Kec. Kembang, Kab Jepara, Jawa Tengah OPERATOR: RAMADITYA
FIRE ALARM TESTING REPORT
Device
No. KKS STATE
No Area Equipment Condition Remark
OK NO
1 TRANSFORMER B Control Panel NOTIFIER - NFS 320 V
Power Input 220 VAC
Power Charger 24 VDC

Power SLC 14 VDC 50SGC00GH002 PASS

Baterry 1 13 VDC
Battery 2 13 VDC

Heat Detector 50SGC04CT200 PASS V


Heat Detector 50SGC04CT201 PASS V
Heat Detector 50SGC04CT202 PASS V
Heat Detector 50SGC04CT203 PASS V
Heat Detector 50SGC04CT204 PASS V
Heat Detector 50SGC04CT205 PASS V
Heat Detector 50SGC04CT206 PASS V
Heat Detector 50SGC04CT207 PASS V

Local Operation Box 50SGC05EH001 PAS V

Horn Strobe 50SGC05EH001 PAS V

Deluge Water Valve 50SGC01AA203 PAS V

Selenoid 50SGC04AA401 PAS V

Pressure Switch 50SGC04CP301 PAS V

Supervisiory Limit switch 50SGC04CG301 PAS V

ACTION :
- FIRE ALARM AND DELUGE SPRAY SYSTEM

ACCEPTEANCE CRITERIA
1 EQUIPMENT FUNCTIONALY
2 DEVICE NOTICED BY THE PANEL
3 DETECTOR WORKING NORMALY
4 MODUL WORKING NORMALY
5 LED PANEL BLINKING
DRAWING NUMBER -TJB56-L1-OFF-C-SGY-I-DGA-3110 FIRE DETECTION AND ALARM SYSTEM ARRANGEMENT FOR TURBINE BUILDING

PLAN & SOLUTION :

Approval Jakarta, 2022


PT. BJS Pelaksana Maintenance PT Indolok Bakti Utama

( ) ( ( ) )
LOCATION PHOTO

GENERATOR
TRANSFORMER
EXCITATION
TRANSFORMER
TRANSFORMER A
TRANSFORMER B
LUBRICATION AND
COOLING OIL
SEAL OIL GENERATOR
COAL FEADER
AIR PREHEATER
COAL BUNKER
COAL BURNER REAR
COAL BURNER FRONT