You are on page 1of 20

Cummins 3100 Series Generator Operation Service Manual

Full download: http://manualplace.com/download/cummins-3100-series-generator-operation-service-manual/

Operation/Service Manual
PowerCommand Control
3100 Series
Digital Paralleling
Generator Sets

Models
DFAA,DFAB,DFAC,DFBC,DFBD,DFBE,DFBF,DFCB,DFCC,
DFCE,DFEB,DFECDFED,DFFA,DFFB,DFGA,DFGB,
DFGC,DFJA,DFJB,DFJC,DFJD,DFLA,DFLB,DFLC,
DFLD,DFLE,DFMB,DQAA,DQAB,DQBA,DQBB

Printed in U.S.A. 9000519C 1-2002

This is the cut pages sample. Download all 219 page(s) at: ManualPlace.com
Table of Contents

SECTION TITLE PAGE


SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
1 INTRODUCTION
About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
How To Obtain Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Generator Set Control Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
2 CONTROL OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
PCC Power On/Standby Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Menu Display and Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Engine Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Gen Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
3 CIRCUIT BOARDS AND MODULES
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Digital Board (A32) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Engine Interface Board (A31) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Analog Board (A33) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Digital Display Board (A35) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Customer Interface Board (A34) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
PT/CT Board (A36) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Bus PT Board (A39) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Genset Communications Module (A41) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Voltage Regulator Output Module (A37) . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Governor Output Module (A38) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Master First Start Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
4 TROUBLESHOOTING
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Resetting the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Warning and Shutdown Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
PCC Oil Pressure Warning and Shutdown Limits . . . . . . . . . . . . . . . . . . . 4-12
Troubleshooting Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
PCC Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-56
Load Sharing Controls Troubleshooting Procedure . . . . . . . . . . . . . . . . . . 4-57

i
SECTION TITLE PAGE
5 CONTROL SERVICE AND CALIBRATION
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Circuit Board Removal/Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Initial Start Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Adjust Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
Setup and Calibration Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Calibration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-26
Accessory Box Control Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Engine Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
Magnetic Speed Pickup Unit (MPU) Installation . . . . . . . . . . . . . . . . . . . . . 5-46
Current Transformer (CT) Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-47
6 SERVICING THE GENERATOR
Testing the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Insulation Resistance (Megger) & Polarization Index (PI) Testing . . . . . . . 6-2
Drying the Windings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Generator/PCC Control Isolation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Exciter Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Exciter Rectifier Bridge (Rotating Rectifier Assembly) . . . . . . . . . . . . . . . . 6-6
Exciter Rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Main Rotor (Generator Field) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Main Stator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Test the PMG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Generator Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Generator Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
7 DAY TANK FUEL TRANSFER PUMP AND CONTROL
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Fuel Transfer Pump Motor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Testing the Float Switch Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
8 INITIAL SYSTEM STARTUP
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
The Startup Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Equipment Application Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Individual Generator Set Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Manual System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Automatic System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
Black Start Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
Test Reports and Acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
On Site Power System Application Review
(Diesel/600VAC and Lower) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
9 WIRING DIAGRAMS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1

ii
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS – This manual contains EXHAUST GASES ARE DEADLY
important instructions that should be followed during
installation and maintenance of the generator and batter- • Provide an adequate exhaust system to properly
ies. expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
Before operating the generator set (genset), read the likely to congregate. Visually and audibly inspect
Operator’s Manual and become familiar with it and the the exhaust daily for leaks per the maintenance
equipment. Safe and efficient operation can be schedule. Make sure that exhaust manifolds are se-
achieved only if the equipment is properly operated cured and not warped. Do not use exhaust gases to
and maintained. Many accidents are caused by failure heat a compartment.
to follow fundamental rules and precautions.
• Be sure the unit is well ventilated.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the op-
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
erator, service personnel, or the equipment.
birth defects, and other reproductive harm.
This symbol warns of immediate
MOVING PARTS CAN CAUSE SEVERE
hazards which will result in severe personal in-
jury or death. PERSONAL INJURY OR DEATH
• Keep your hands, clothing, and jewelry away from
WARNING This symbol refers to a hazard or un- moving parts.
safe practice which can result in severe per-
sonal injury or death. • Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-
CAUTION This symbol refers to a hazard or un- connect starting batteries, negative (–) cable first.
safe practice which can result in personal injury This will prevent accidental starting.
or product or property damage. • Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
FUEL AND FUMES ARE FLAMMABLE in position over fans, drive belts, etc.
Fire, explosion, and personal injury or death can result • Do not wear loose clothing or jewelry in the vicinity of
from improper practices. moving parts, or while working on electrical equip-
ment. Loose clothing and jewelry can become
• DO NOT fill fuel tanks while engine is running, un- caught in moving parts.
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential • If adjustment must be made while the unit is run-
fire hazard. ning, use extreme caution around hot manifolds,
moving parts, etc.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source DO NOT OPERATE IN FLAMMABLE AND
near the generator set or fuel tank.
EXPLOSIVE ENVIRONMENTS
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be Flammable vapor can cause an engine to overspeed and
made with an approved flexible line. Do not use zinc become difficult to stop, resulting in possible fire, explo-
coated or copper fuel lines with diesel fuel. sion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
• Be sure all fuel supplies have a positive shutoff created by fuel spill, leak, etc., unless the genset is
valve. equipped with an automatic safety device to block the air
• Be sure battery area has been well-ventilated prior intake and stop the engine. The owners and operators of
to servicing near it. Lead-acid batteries emit a highly the genset are solely responsible for operating the gen-
explosive hydrogen gas that can be ignited by arc- set safely. Contact your authorized Cummins Power
ing, sparking, smoking, etc. Generation distributor for more information.

LS-14M
iii
ELECTRICAL SHOCK CAN CAUSE GENERAL SAFETY PRECAUTIONS
SEVERE PERSONAL INJURY OR DEATH • Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex-
• Remove electric power before removing protective changer pressure cap while the engine is running.
shields or touching electrical equipment. Use rub- Allow the generator set to cool and bleed the system
ber insulative mats placed on dry wood platforms pressure first.
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing • Used engine oils have been identified by some state
(particularly wet shoes) or allow skin surface to be or federal agencies as causing cancer or reproduc-
damp when handling electrical equipment. Do not tive toxicity. When checking or changing engine oil,
wear jewelry. Jewelry can short out electrical con- take care not to ingest, breathe the fumes, or con-
tacts and cause shock or burning. tact used oil.

• Use extreme caution when working on electrical • Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
components. High voltages can cause injury or
such as wood and cloth; Class B fires, combustible
death. DO NOT tamper with interlocks.
and flammable liquid fuels and gaseous fuels; Class
• Follow all applicable state and local electrical C fires, live electrical equipment. (ref. NFPA No. 10).
codes. Have all electrical installations performed by • Make sure that rags are not left on or near the en-
a qualified licensed electrician. Tag and lock open gine.
switches to avoid accidental closure.
• Make sure generator set is mounted in a manner to
• DO NOT CONNECT GENERATOR SET DI- prevent combustible materials from accumulating
RECTLY TO ANY BUILDING ELECTRICAL SYS- under the unit.
TEM. Hazardous voltages can flow from the gen- • Remove all unnecessary grease and oil from the
erator set into the utility line. This creates a potential unit. Accumulated grease and oil can cause over-
for electrocution or property damage. Connect only heating and engine damage which present a poten-
through an approved isolation switch or an ap- tial fire hazard.
proved paralleling device.
• Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-
MEDIUM VOLTAGE GENERATOR SETS
bris from the set and keep the floor clean and dry.
(601V to 15kV) • Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol
• Medium voltage acts differently than low voltage. or drug that makes the operation of equipment un-
Special equipment and training is required to work safe.
on or around medium voltage equipment. Operation • Substances in exhaust gases have been identified
and maintenance must be done only by persons by some state or federal agencies as causing can-
trained and qualified to work on such devices. Im- cer or reproductive toxicity. Take care not to breath
proper use or procedures will result in severe per- or ingest or come into contact with exhaust gases.
sonal injury or death.
• Do not store any flammable liquids, such as fuel,
• Do not work on energized equipment. Unauthorized cleaners, oil, etc., near the generator set. A fire or
personnel must not be permitted near energized explosion could result.
equipment. Due to the nature of medium voltage
electrical equipment, induced voltage remains even
• Wear hearing protection when going near an oper-
after the equipment is disconnected from the power ating generator set.
source. Plan the time for maintenance with author- • To prevent serious burns, avoid contact with hot
ized personnel so that the equipment can be de-en- metal parts such as radiator, turbo charger and ex-
ergized and safely grounded. haust system.

KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE

iv
1. Introduction
ABOUT THIS MANUAL TEST EQUIPMENT
To perform the test procedures in this manual, the
This manual covers models produced under the following test equipment must be available
Cummins/Onan and Cummins Power Genera- • True RMS meter for accurate measurement of
tion brand names. small AC and DC voltages. Fluke models 87 or
8060A are good choices.
This manual provides troubleshooting and repair • Grounding wrist strap to prevent circuit board
information regarding the PowerCommand damage due to electrostatic discharge (ESD).
Control 3100 (PCC) and generators for the • Battery Hydrometer
generator set (genset) models listed on the front • Jumper Leads
cover. Engine service instructions are in the • Tachometer or Frequency Meter
applicable engine service manual. Operating and • Wheatstone Bridge or Digital Ohmmeter
maintenance instructions are in the applicable • Variac
Operator’s Manual. • Load Test Panel
This manual does not have instructions for • Megger or Insulation Resistance Meter
servicing printed circuit board assemblies. After • PCC Service Tool Kit (Harness Tool and Sen-
determining that a printed circuit board assembly is sor Tool)
faulty, replace it. Do not repair it. Attempts to repair a HOW TO OBTAIN SERVICE
printed circuit board can lead to costly damage to
Always give the complete Model, Specification and
the equipment.
Serial number of the generator set as shown on the
This manual contains basic (generic) wiring nameplate when seeking additional service
diagrams and schematics that are included to help information or replacement parts. The nameplate is
in troubleshooting. Service personnel must use the located on the side of the generator output box.
actual wiring diagram and schematic shipped with WARNING Incorrect service or replacement of
each unit. The wiring diagrams and schematics that parts can result in severe personal injury or
are maintained with the unit should be updated death, and/or equipment damage. Service per-
when modifications are made to the unit. sonnel must be trained and experienced to per-
form electrical and mechanical service. Read
Read Safety Precautions and carefully observe all and follow Safety Precautions, on pages iii and
instructions and precautions in this manual. iv.

Copyright 2001 Cummins Power Generation. All rights reserved.


Cummins, Onan and PowerCommand are registered trademarks of Cummins Inc.

1-1
SYSTEM OVERVIEW The PCC monitors frequency from both the
magnetic pick-up (MPU) and the main stator inputs.
The PCC is a microprocessor-based control for The control sends a low power pulse-width
Onan generator sets. It provides fuel control and modulated (PWM) signal to the governor output
engine speed governing, main alternator voltage module, which then sends an amplified signal to the
output regulation, and complete generator set engine fuel control.
control and monitoring. It also provides controls for
automatic and semi-automatic synchronizing and The Bus PT module reduces the bus voltage to
automatic load sharing controls for both isolated approximately 18 VAC and provides a signal to the
bus or utility (mains) paralleling applications. control for reference in synchronizing the generator
set to the system bus.
The operating software provides control of the The external PT/CT module reduces generator
generator set and its performance characteristics, voltage to approximately 18 VAC, and produces a
and displays performance information on a digital representative AC voltage from CT output current.
display panel. It accepts menu-driven control and The voltage regulation function sends a low power
setup input from the push button switches on the PWM signal to the voltage regulator output module,
front panel. which then sends an amplified signal to the exciter
stator.
GENERATOR SET CONTROL FUNCTION
Oil, coolant, and exhaust temperatures are sensed
Figure1-1 shows some of the control functions. A by variable resistance element sensors. Oil
more complete block diagram is provided in Section pressure is sensed by a capacitive element active
3. A system schematic is provided in Section 9. sensor.

Fuel
Governor Control MPU
Output

Regulator
Output

PMG Sensors
S N


1
2
3
4

Battery
• •
BT1
Bus PT
1 2 3 4
Module


• To
• Load

FIGURE 1-1. GENERATOR SET CONTROL FUNCTIONS

1-2
2. Control Operation
GENERAL SAFETY CONSIDERATIONS
The following describes the function and operation AC power is present when the set is running. Do not
of the PowerCommand generator set control. All in- open the generator output box while the set is run-
dicators, displays, meters and control switches are ning.
located on the face of the control panel as illustrated WARNING Contacting high voltage compo-
in Figure 2-1. nents can cause electrocution, resulting in se-
The PCC control cabinet must be opened only by vere personal injury or death. Do not open the
technically qualified personnel. generator output box while the set is running.
Read and observe all WARNINGS and CAU-
Normally, generator set configuration options are TIONS in your generator set manuals.
set at the factory. When a new control is installed on CAUTION The PCC control cabinet must be
a generator set or when parts are replaced, the con-
opened only by technically qualified personnel.
trol must be configured for that generator set with
Lower level voltages (18 VAC to 24 VDC) are
the use of the “Initial Start Setup” portion of the inter-
present in PCC control cabinet. These voltages
nal software. Setup and calibration procedures are
can cause electrical shock, resulting in per-
described in Section 5.
sonal injury.
The automatic voltage regulator (AVR) and gover- Even with power removed, improper handling
nor operation characteristic adjustments are also of components can cause electrostatic dis-
described in Section 5. charge and damage to circuit components.

2-1
SEQUENCE OF OPERATION one of eight “wake up” inputs from remote sensing
switches.
When the PowerCommand control is in the AUTO
mode, it will cause the generator set to start on re- The wake up signals are:
ceiving a signal from a remote device. The Power-
Command control will initiate a starter cranking sig- • Emergency Stop
nal and verify that the engine is rotating. The Power- • Low Coolant Level
Command control will provide sufficient fuel to the
engine to accelerate to start disconnect speed. On • Low Coolant Temperature
reaching that speed, the control will ramp the gener- • Low Fuel
ator set to rated speed and voltage.
• Customer Fault Inputs 2 and 3
On reaching rated speed and voltage, the Power-
Command control checks the system bus voltage. If • Run Selected on Run/Off/Auto Switch
no bus voltage is present, it will wait for a pulse from • Remote Start Signal in Auto Mode
a remote Master First Start Sensor. On receiving
that pulse, the control will signal the paralleling • Self Test switch
breaker to close. To activate and view the menu displays, press and
If bus voltage is present, the PowerCommand con- release the Self Test switch. The PCC will initialize
trol will check for proper phase rotation, adjust the the operating software and permit operation of the
generator set to the bus voltage and frequency lev- menu display panel. If no menu selections are
el, and then synchronize the generator set to the made, the power to the control panel will shut down
system bus. When a synchronous condition is after 30 seconds.
achieved, the control will send a signal to close the
Power On Mode
paralleling breaker.
When the paralleling breaker is closed, the genera- In the Power On (awake) mode (selector switch S5
tor set will assume it’s proportional share of the total on the Digital Board is set to the left), the PCC will
load on the system bus. initialize the operating software and permit opera-
tion of the menu display panel. (See Figure 3-1 for
PCC POWER ON / STANDBY MODE S5 location.) Power will stay on until switch (S5) is
set to the Standby mode. It is recommended that
Standby Mode
switch S5 be left in the Power On mode in all ap-
In the Standby (sleep) mode (selector switch S5 on plications, except those where auxiliary battery
the Digital Board is set to the right and the generator charging is not available.
set is not running), the control’s operating software
CAUTION Electrostatic discharge will damage
is inactive and the LEDs and displays on front panel
are all off. circuit boards. Always wear a grounding wrist
strap when touching or handling circuit boards
The operating software is initialized and the front or socket-mounted ICs and when disconnect-
panel is turned on in response to a run signal or any ing or connecting harness connectors.

2-2
KILOWATT FREQUENCY AC AC AMMETER
METER METER VOLTMETER (PERCENT AMPS)
(PERCENT LOAD) (DUAL SCALE)

MENU UPPER AND LOWER


ACTIVE SWITCH ALPHANUMERIC
SELECTION SCALE INDICATOR
INDICATOR DISPLAY
SWITCH
(1 of 4) (1 of 6)

RESET MENU PANEL LAMP EMERGENCY


PCC 3100 SWITCH SWITCH SWITCH STOP PUSH
LABEL BUTTON
SELF TEST
PARALLELING RUN/OFF/AUTO SWITCH
BREAKER SWITCH
PHASE SELECTOR
SWITCHES AND SWITCH AND
INDICATORS NONAUTOMATIC
INDICATORS
WARNING
SHUTDOWN
STATUS INDICATORS

FIGURE 2-1. FRONT PANEL (PCC 3100)

2-3
FRONT PANEL Reset Switch: Press this switch to reset warning
and shutdown messages after the condition has
Figure 2-1 shows the features of the front panel. been corrected. To reset a shutdown message with
the Reset switch, the Run/Off/Auto switch must be
AC Voltmeter: Dual scale instrument indicates AC in the Off position.
voltage. Measurement scale in use is shown on
scale indicator lamp. With the Run/Off/Auto switch in the Auto mode,
shutdown faults can be reset by removing the re-
AC Ammeter: Indicates current output in percent of mote start input and then cycling the remote reset
maximum rated current. (Percent current is based input.
on .8 PF.)
Self Test Switch: Press and hold this switch to light
Kilowatt Meter: Indicates 3-phase AC power out- all front panel LEDs and cycle through all shutdown
put as percent of rated load. and warning messages.

Frequency Meter: Indicates generator output fre- In the Standby (sleep) mode, with the generator set
quency in hertz. not running, the control’s operating software is inac-
tive and the LEDs and displays on front panel are all
Upper and Lower Scale Indicator Lamps: Indi- off.
cate AC voltmeter scale.
To activate and view the menu displays without
Digital Display: This two-line, 16-character per line starting the generator set, press and hold the Self
alphanumeric display is used in the menu-driven Test switch until the front panel LEDs light. The
operating system, in conjunction with the display PCC will initialize the operating software and permit
menu selection switches and the Menu switch. Re- operation of the menu display panel. If no menu se-
fer to the menu trees later in this section. The dis- lections are made, a software timer will shut down
play is also used to show warning and shutdown the power after 30 seconds.
messages. Panel Lights Switch: Press this switch to turn con-
Display Menu Selection Switches: Four momen- trol panel illumination on and off. The illumination
tary switches—two on each side of the digital dis- will shut off after about eight minutes.
play window—are used to step through the various Phase Selector Switch and Indicators: Press this
menu options and to adjust generator set parame- momentary switch to select phases of generator
ters. The green arrow adjacent to the switch is lit output to be measured by the analog AC voltmeter
when the switch can be used (switch is “active”). and ammeter. LEDs indicate the selected phase.
Menu Switch: Press this switch to return the digital Run/Off/Auto Switch: This switch starts and stops
display to the MAIN MENU. Refer to the menu trees the set locally, or enables start/stop control of the
later in this section. engine from a remote location. (Ground to start.)

2-4
Emergency Stop Button: Push the button in for Shutdown Status Indicator: This red lamp is lit
emergency shutdown of the engine. whenever the control detects a shutdown condition.
After the condition is corrected, shutdown indica-
Remote Reset switch will not reset emergency stop. tors can be reset by turning the Run/Off/Auto switch
Can only be reset at the PCC front panel.
to the Off position, and pressing the Reset switch.
To reset: In Auto mode, shutdowns can be reset by removing
1. Pull the button out or turn the button clockwise the remote start input and then cycling the remote
(button with arrow) and allow it to pop out. reset input.
2. Move the Run/Off/Auto switch to Off.
3. Press the front panel Reset switch. Emergency Stop shutdown status (Code 102) can be
4. Select Run or Auto, as required. reset only at the PCC front panel.

Non-Automatic Status Indicator: This red lamp


flashes continuously when the Run/Off/Auto switch Paralleling Breaker Switches and Indicators:
is not in the Auto position. These two switches are used to manually open or
close the paralleling breaker of the generator set.
Warning Status Indicator: This yellow lamp is lit The lamps are used to indicate the opened or
whenever the control detects a warning condition. closed position of the paralleling breaker.
After the condition is corrected, warning indicators
can be reset by pressing the Reset switch. (It is not
necessary to stop the generator set.) The Breaker Operation switches are operational only
when the Run/Off/Auto switch is in the Run position.
With the Run/Off/Auto switch in the Auto mode, The breaker will close when the generator set is syn-
warnings can also be reset by cycling the remote re- chronized with the system bus, or if the system bus
set input after the condition is corrected. is de-energized.

2-5
FIGURE 2-2. DIGITAL DISPLAY AND MENU SELECTION SWITCHES

MENU DISPLAY AND SWITCHES MAIN MENU


The facing page shows the main menu and a block
Figure 2-2 shows the digital display and the menu representation of the available submenus.
selection switches. Refer to heading “Front Panel” As shown in the diagram, the main menu can
which describes the menu display and switches. branch into one of four directions.
To display engine parameters, such as oil pressure
In the Standby Mode, to activate and view the menu and temperature, water temperature, engine speed
displays without starting the generator set, press (RPM), and exhaust temperature, press the button
and release the Self Test switch. This will initialize next to the word “ENGINE” in the display. Refer to
the PCC operating software and permit operation of ENGINE MENU in this section.
the menu display panel. If no menu selections are To display generator parameters, such as volts,
made, a software timer will shut down the power af- amps, power (kW), and frequency, press the button
ter 30 seconds. In the Power On Mode, power is next to the word “GEN” in the display. Bus voltage,
continuously supplied to the control panel. Display frequency and a digital synchroscope can also be
viewed from this menu branch. Turn to the GEN
will always remain on.
MENU in this section.
To adjust output voltage and frequency, or start and
In the digital display, the “>>” symbol indicates that stop delays, press the button next to the word “AD-
selecting the adjacent button causes the operating JUST” in the display. Refer to ADJUST MENU in
program to branch to the next menu display—as Section 5.
shown in the menu diagrams.
To display the selected generator set model and the
resident version software, press the button next to
In the digital display, the “<<” symbol indicates that
the “>>” in the display. Refer to VERSION & DIS-
selecting the adjacent button causes the operating
PLAYS MENUS in Section 5.
program to go back to the previous menu display.

2-6
MAIN MENU

PAGES 28 & 29 PAGES 210 & 211


RPM << %GOV / REG <<
EXHAUST FREQUENCY

BATTERY << POWER <<


HOURS >> KW HRS >>

OIL << VOLTS <<


COOLANT >> AMPS >>

< ENGINE GEN >

< ADJUST >> >

RESET MENU >

CLEAR WARNING AND RETURN TO


SHUTDOWN MESSAGES MAIN MENU

⇑ VOLTAGE VERSION
⇓ _______ >> SECTION 5 SETUP / CAL
HISTORY
⇑ FREQUENCY
⇓ _______ >>
(ACCESS CODE)
⇑ START DELAY
⇓ _______ SEC >>

⇑ STOP DELAY
⇓ _______SEC >>
DISPLAY CAL <<
SECTION 5 METERS >>
⇑ IDLE SPEED
⇓ _______RPM >>

SECTION 5
GOV / REG <<
SECTION 5 PARALLEL SETUP

INACTIVE BUTTON

< ACTIVE BUTTON


< ACTIVE BUTTON SELECTED

2-7
ENGINE MENU

The facing page shows a block representation of BATTERY/HOURS submenu: From the OIL/
the ENGINE menu. If you press the button next to COOLANT submenu, press the button next to the
the word “ENGINE” in the display, the first ENGINE “>>” in the display to move to the BATTERY/
submenu will appear. HOURS submenu. Select BATTERY for a display
of battery voltage. Select HOURS for a display of
As shown in the diagram, the ENGINE menu has the number of starts and the running hours. When
three submenus. battery or hours parameters are displayed, press-
ing the button next to the “<<” will return the display
OIL/COOLANT submenu: This is the first sub- (“BACK”) to the BATTERY/HOURS submenu.
menu. Select OIL for a display of oil pressure and oil
temperature. Select COOLANT for a display of RPM/EXHAUST submenu: From the BATTERY/
coolant temperature. When oil or coolant parame- HOURS submenu, press the button next to the “>>”
ters are displayed, pressing the button next to the in the display to move to the RPM/EXHAUST sub-
“<<” will return the display (“BACK”) to the OIL/ menu. Select RPM for a display of engine RPM.
COOLANT submenu. Select EXHAUST for a display of the (optional) ex-
haust temperature. When RPM or exhaust pa-
rameters are displayed, pressing the button next to
the “<<” will return the display (“BACK”) to the RPM/
EXHAUST submenu.

2-8
ENGINE
BACK
< ENGINE GEN > < OIL << > ___PSI / KPA << >
< ADJUST >> > < COOLANT >> > ___°F / °C

BACK
< OIL << > L___°F / °C << >
< COOLANT >> > R___°F / °C (or N/A)

< OIL << > < ENGINE GEN >


< COOLANT >> > < ADJUST >> >

< OIL << >


< COOLANT >> >

BACK
< BATTERY << > BATTERY << >
< HOURS >> > ___VDC

BACK
< BATTERY << > STARTS ___ << >
< HOURS >> > HOURS ___

< BATTERY << > < OIL << >


< HOURS >> > < COOLANT >> >

< BATTERY << >


< HOURS >> >

BACK
< RPM << > RPM << >
< EXHAUST ___

BACK
< RPM << > L___°F/°C (or N/A) << >
< EXHAUST R___°F/°C (or N/A)

< RPM << > < BATTERY << >


< EXHAUST < HOURS >> >

Indicates OR" Condition

2-9
GEN MENU

The facing page shows a block representation of turn the display (“BACK”) to the POWER/KW
the GEN menu. If you press the button next to the HOURS submenu.
word “GEN” in the display, the first GEN submenu
will appear. The PF reading will contain an asterisk if the power
factor is leading (for example, *.3PF).
As shown in the diagram, the GEN menu has three Beginning Version 1.06, N/A is displayed in the PF
submenus. field when the generator set is not running.

%GOV/REG/FREQUENCY submenu: From the


VOLTS/AMPS submenu: This is the first sub- POWER/KW HOURS submenu, press the button
menu. Select VOLTS for a display of a line-to-line or next to the “>>” in the display to move to the %GOV/
line-to-neutral selection, or for viewing of the sys- REG/FREQUENCY submenu. Select %GOV/REG
tem bus line-to-line voltage. Select line-line or line- for a display of voltage regulator and governor duty
neutral for the desired voltage display. Select cycle (drive) levels in percentage of maximum. Se-
AMPS for a display of L1, L2, and L3 current in lect FREQUENCY for a display of the generator
amps. When voltage or current parameters are dis- output frequency the bus frequency, or the digital
played, pressing the button next to the “<<” will re- synchroscope. When voltage regulator and gover-
turn the display (“BACK”) to the L-L/L-N submenu. nor or frequency parameters are displayed, press-
ing the button next to the “<<” will return the display
If DELTA is selected in the Initial Start Setup subme- (“BACK”) to the %GOV/REG/FREQUENCY sub-
nu, when selecting VOLTS, the “line-line” or “line- menu.
neutral” submenus will not be displayed, only the
L12, L23, L31 submenu will be displayed. Bus Frequency (Digital Synchroscope) subme-
nu: When the bus frequency (digital synchroscope)
POWER / KW HOURS submenu: From the information is displayed, the operator can observe
VOLTS/AMPS submenu, press the button next to the generator set synchronizing with the system
the “>>” in the display to move to the POWER/KW bus. The display indicates bus frequency and num-
HOURS submenu. Select POWER for a display of ber of degrees from synchronous condition (+ indi-
power output in kilowatts and a power factor value. cates faster, – indicates slower). When the genera-
Select KW HOURS for a display of kilowatt hours. tor set is operating within the sync-check window,
When power or kW hours parameters are dis- an asterisk will indicate that the paralleling breaker
played, pressing the button next to the “<<” will re- can be closed.

2-10
< ENGINE GEN > GEN
< ADJUST >> >
BACK
< VOLTS << > < L-L << > L12 L23 L31 << >
< AMPS >> > < L-N BUS ___ ___ ___

BACK
< L-L << > L1N L2N L3N << >
< L-N BUS ___ ___ ___
BACK
< L-L << > L12 L23 L31 << >
< L-N BUS ___ ___ ___
BACK
< L-L << >
< L-N BUS

BACK
< VOLTS << > L1 L2 L3 << >
< AMPS >> > ___ ___ ___

< VOLTS << > < ENGINE GEN >


< AMPS >> > < ADJUST >> >
BACK
< VOLTS << > < POWER << > ___ KW << >
< AMPS >> > < KW HRS >> > ___ PF
BACK
< POWER << > KW HRS << >
< KW HRS >> > ____________
BACK
< POWER << >
< KW HRS >> >
BACK
< POWER << > < %GOV / REG << >
< KW HRS >> > < FREQUENCY

BACK
< %GOV / REG << > GOV__ % << >
< FREQUENCY REG__ %

BACK
< %GOV / REG << > FREQUENCY << >
< FREQUENCY ___ HZ BUS

FREQUENCY << >


___ HZ BUS

BACK
BUS FREQUENCY<< >
Indicates OR" Condition ___ HZ ___ DEG

2-11
THIS PAGE LEFT INTENTIONALLY BLANK

2-12
Cummins 3100 Series Generator Operation Service Manual
Full download: http://manualplace.com/download/cummins-3100-series-generator-operation-service-manual/

3. Circuit Boards and Modules


GENERAL The system schematics are provided in Section 9 of
this manual.
This section describes the function of the PCC cir-
cuit boards and modules that are contained in the CAUTION Electrostatic discharge will damage
control panel (Figure 3-1) and the accessory box. circuit boards. Always wear a grounding wrist
The block diagram in Figure 3-2, shows both inter- strap when touching or handling circuit boards
nal and external components of the PCC system. or socket-mounted ICs.

S5 POWER ON/ J1 (FOR INPOWER


STANDBY SWITCH SERVICE TOOL)

DIGITAL BOARD
A32
DISPLAY BOARD
A35 GENSET ANALOG
COMM. BOARD
BOARD A33
A41

ENGINE INTERFACE CUSTOMER INTERFACE


A31 A34

RUN/OFF/AUTO GOVERNOR
SWITCH S12 OUTPUT MODULE
A38

BUS PT MODULE
A39

PT/CT
BOARD
A36
VOLTAGE REGULATOR
OUTPUT MODULE
A37 ACCESSORY BOX
(HC 4/5)

FIGURE 3-1. CIRCUIT BOARD LOCATIONS

3-1
This is the cut pages sample. Download all 219 page(s) at: ManualPlace.com

You might also like