You are on page 1of 4

Interaction of Surface Gradient, Precipitation Rate

and Conductor Surface Treatment on


Corona Induced Audible Noise of
AC Overhead Transmission Lines
Oliver Pischler Uwe Schichler Bo Zhang
Institute of High Voltage Engineering Institute of High Voltage Engineering State Key Lab of Power Systems,
and System Performance and System Performance Department of Electrical Engineering
Graz University of Technology Graz University of Technology Tsinghua University
Graz, Austria Graz, Austria Beijing, People’s Republic of China
oliver.pischler@tugraz.at uwe.schichler@tugraz.at shizbcn@mail.tsinghua.edu.cn

Abstract—Overhead Transmission lines are prone to emit An overhead line’s geometry is naturally chosen in such a
audible noises under foul weather conditions (e. g. rain or fog), way that no corona discharges can occur under dry conditions.
which can be a significant source of annoyance for people living Under wet conditions, however, the water drops deposited on
close to the line. Apart from mere fulfilment of emission limits the conductors distort the electric field in such a way that
given by legislature, transmission system operators nowadays discharges may occur (Fig. 1).
often seek to reduce audible noise emissions as far as possible to
minimize public opposition towards overhead lines. A very A conductor’s surface condition strongly influences the
promising approach for the reduction of audible noise emissions way the water drops adhere to it. On a new standard
are hydrophilic conductor surface treatments, which influence aluminium conductor, which might be even tainted with
the way water drops form on the conductors. However, very drawing grease and therefore exhibit hydrophobic properties,
little is known about the operating behavior and limitations of small bead like drops form all around the conductor, which
hydrophilic conductors. This contribution therefore strives to cause a high number of corona discharges. On a hydrophilic
illustrate how the electric field intensity around the conductors conductor, water drops only accumulate at the bottom side of
(surface gradient) and the precipitation rate affect the the conductors and the drops are also fewer in number.
effectiveness and the emission behavior of hydrophilic
conductors compared to standard conductors. The presented
results are derived from a newly developed prediction model,
which is based on noise emission measurements performed on
25 different bundle conductor arrangements carried out in an
acoustically optimized high voltage laboratory. The compiled
results indicate that hydrophilic surfaces can provide significant
noise reductions, which tend to diminish with increasing surface
gradient. Above a certain point of intersection, hydrophilic
conductors exhibit higher emission levels than standard
conductors. Since this behavior has been observed to depend
strongly on the bundle conductor geometry, results for various
numbers of sub-conductors and sub-conductor diameters are Fig. 1. Electric discharges on water drops on an a standard OHL conductor.
presented. From a practical point of view, this contribution shall
raise awareness regarding the optimal utilization of hydrophilic It is a well known fact, that overhead line conductors gain
conductors by illustrating the principal correlations and by hydrophilic properties within their first few years of operation.
providing first guidelines. This is partly due to the removal of grease and partly due to
natural surface erosion, which roughens the surface and
Keywords—Audible Noise, Overhead Line, Corona, Surface thereby reduces the contact angle of adhering drops. An
Gradient, Hydrophilic, Conductors
overhead line therefore emits the highest noise levels right
I. INTRODUCTION after the first energization and noise levels can be expected to
decline as the line ages. To bridge the gap between first
The emission of audible noise by overhead lines (OHL) energization and sufficient aging, conductors with hydrophilic
during foul weather (rain, snow, fog, drizzle etc.) is a well- surface treatments can be employed.
known phenomenon, which has been studied extensively in
the past [1]. The noise emissions are generated by electric Such silent conductors can be considered to be “artificially
discharges (corona discharges) stemming from the surfaces of aged”. It is a noteworthy fact that the degree of hydrophilicity
the OHL conductors. Since electric discharges are a result of achieved by natural aging seems to lead to the highest noise
various ionisation processes, they can only occur if the electric reduction attainable with standard round wire conductors.
field in the vicinity of the conductors is sufficiently high. However, modern surface treatments have been shown to be
Apart from the radial decay of the electric field, it is mostly able to replicate this behaviour [2, 3]. Therefore, no distinction
the electric field right at the conductor surface (surface will be made and the term “hydrophilic” will be used
gradient), which governs the characteristics of the ionisation representatively for “naturally aged” as well as “artificially
and discharge phenomena in this regard. surface treated”.

XXX-X-XXXX-XXXX-X/XX/$XX.00 ©20XX IEEE


The fundamental research of audible noise, which was for the sound power level [4]. During the conversion of
carried out several decades ago, was focused on aged measured sound pressure levels L into power levels A’ room
conductors. Available and widely used prediction formulas acoustics and other influencing factors have to be taken into
therefore cover the case of “well aged” conductors [4], which account. The whole process, which is based on the procedure
– this ought to be stressed – does not necessarily imply outlined in ISO 3744, is described in [5].
“highest degree of attainable hydrophilicity”. Nowadays,
where legislature and emission control are more rigid, it is of III. EXAMPLARY RESULTS
utmost importance to have a good understanding of the noise A. Results
levels, which can be expected right after the stringing of the
conductors (new line or reconductered) as well as after many Typically, results or prediction values of audible noise
years of operation. Only if both are known, the optimal levels are presented as a function of the surface gradient.
conductor configuration for an OHL can be chosen and only However, seen from a practical point of view where the (line)
then reliable predictions can be made. For this purpose, the voltage is usually predetermined, this might be misleading
principal differences in the emission behaviour of standard when different bundle geometries are compared in one
and hydrophilic conductors and guidelines for the optimal diagram since the surface gradient is also influenced by bundle
utilization of hydrophilic conductors will be presented. geometry. However, as long as only different surfaces are
compared, the surface gradient is a convenient quantity. In
II. OHL NOISE EMISSION MEASUREMENTS accordance with the definition provided by EPRI, E refers to
IN THE HIGH VOLTAGE LABORATORY the RMS value of the average of the maximum surface
gradients occurring on each sub-conductor of a bundle
A. Measurement Setup conductor [4].
To gather meaningful results, which can be used for a
The diagram depicted in Fig. 3 shows the sound power
prediction model later on, it is necessary to perform noise
levels emitted by a standard conductor and a hydrophilic
emission measurements under conditions as close to reality as
conductor, which has proven in comparisons with various
possible. Therefore, all investigations were carried out on full
aged and treated conductors to possess optimal hydrophilic
scale conductor bundles of 10 m length and under realistic rain
properties. The conductors were arranged in horizontal twin
provided by a rainfall simulator. The details of the
bundle arrangements (spacing: 400 mm, d = 29 mm) and
measurement setup and the measurement equipment have
measured in the single phase setup described in section 2. Two
been described in detail in earlier publications (Fig. 2) [2, 3].
rain rates, 1 mm/h and 6 mm/h, were used for these
investigations. A similarly shaped diagram can be expected
for other bundle configurations.

Fig. 2. Laboratory setup for audible noise measurements.

B. Calculation of the Generated Sound Power Level


The acoustic quantity most readily accessible in such
laboratory measurements is the sound pressure level L evoked
by the coronating conductor bundle at a certain observation
point in the laboratory. However, the sound pressure level’s
significance is quite limited, as it strongly depends on the
Fig. 3. Sound power A’ emitted by a twin conductor bundle (d = 29 mm).
distance between the observation point(s) and the emitting
conductor bundle. As long as the measurement setup remains Unfortunately, no comprehensive description of the
unchanged, the sound pressure level can be used to compare audible noise generation process has been found yet. It is
the emission characteristics of different conductors and therefore not possible to fit the results to a physical model.
bundle configurations. To be able to make noise predictions, However, a hyperbolic fit according to (1) allows a
the measured sound pressure levels have to be converted to the satisfactory approximation over the whole surface gradient
underlying invariant source quantity, which is the sound range. In contrast to a simple polynomic fit, this description
power level A. In the present case, the sound power level A’ also takes the saturation behaviour for high surface gradients
describes the acoustic power emitted by the bundle conductor into account, which will be discussed further below.
per unit length. Although the sound pressure level as well as
the sound power level both use the unit “dB(A)”, the Since the test setup is a single phase setup, the test voltage
respective reference values are different. In case of the sound U and the corresponding surface gradients E scale linearly
pressure level a reference pressure of p0 = 20 µPa is used, according to (2). The gradient factor, which in this case is
while in accordance with the values provided by EPRI a g = 0.0726 kV/(cm∙kV), was obtained from the CSM
reference power of P0 = 1 µW will be used in this contribution calculation method previously described in [5].
In case of the hydrophilic conductor, fewer drops adhere
′= ′ −  

to the conductor. Therefore, the mutual shielding is less
pronounced and higher levels of corona activity and audible
= ∙  noise emissions can be attained for surface gradients
exceeding the intersection field strength. This behaviour is
The fitting coefficients for Eqn. 1 shown in Tab. 1 were also reflected in A’∞ in Tab. 1. The differences occurring
computed with Levenberg-Marquardt optimization with a between the two investigated rain rates are caused by a similar
determination coefficient of R2 > 0.998. interaction between the density of adhering water drops and
resulting mutual shielding. XU et al. have investigated this
TABLE I. SOUND POWER LEVEL FITTING COEFFICIENTS relationship extensively [7].
Fitting coeff. for Fig. 3 according to (1) C. Practical Implications
Rain
Surface A’∞ k E0
Rate Two major conclusions regarding OHL design are to be
dB(A) dB(A)∙kV/cm kV/cm drawn from the intersecting noise emission behaviours of
standard 26 166 5.3 standard and hydrophilic conductors. First, it ought to be
6 mm/h avoided to operate an overhead line close or even above the
hydrophil. 32 266 4.4
intersection surface gradient EI, since paradoxical emission
standard 51 632 1.8 behaviour regarding the influence of the rain rate as well as
1 mm/h the conductor hydrophilicity can be expected. For excessive
hydrophil. 86 1658 -3.5
surface gradients, a line might even get louder when it ages.
Secondly, if conductors with artificial hydrophilic properties
B. Noise Emission Behaviour are to be used for an OHL, their noise reducing properties can
only be harnessed fully when the surface gradient is
The noise emission curves depicted in Fig. 3 show that sufficiently low. For high surface gradients, hydrophilic
hydrophilic conductors indeed exhibit significantly lower conductors will yield only little effect.
emission values than standard conductors. However, the
difference between the two conductors decreases steadily until Unfortunately, existing prediction models cannot be used
the emission lines of the standard conductors and the treated to determine the intersection surface gradient EI, as they do
conductors intersect around EI ≈ 19 kV/cm. This can be not distinguish between standard and hydrophilic conductors
explained by the corona discharge behaviours of the different and only take the influence of different rain rates into
conductor types under wet conditions. consideration in a rudimentary fashion.

As stated in section 1, a high number of water drops, IV. NOVEL NOISE EMISSION MODEL
which are the source points of the noise generating discharges,
A. General
can be found around the whole circumference of standard
conductors. On hydrophilic conductors, water drops only While existing audible noise prediction models, such as
accumulate on the conductor’s bottom side. Due to this published by EPRI or BPA [4], allow to estimate noise
behaviour, the corona onset gradient EC of a wet hydrophilic emission levels of a planned OHLs with reasonable accuracy,
conductor is higher than that of a wet standard conductor. This their shortcomings, which were described in the previous
can be described by PEEK’s equation section, makes them less suited to be the basis for precise line
design. This realisation in combination with increasingly
= ∙ ∙ ∙ 1+   stringent environmental protection laws triggered the
√ ∙ development of a new audible noise model, which in
particular strives to incorporate the different emission
which can be used to predict the (critical) corona onset electric characteristics of standard and hydrophilic conductors.
field EC as a function of the conductor radius r (in cm) [6].
Since the onset electric field can be easily obtained from The model is based on a large number of noise emission
audible noise tests or accompanying partial discharge measurements carried out on standard and hydrophilic
measurements, Eqn. 3 can be used to estimate the surface overhead line conductors (diameters d = 20…50 mm) in
roughness coefficient m for the two types of conductors. For various bundle configurations with the methodologies
this, the air density factor is estimated to be δ = 1. The two presented in section 2. The emission model itself is not yet
empirical constants E0 and K are 21.1 kV/cm (RMS) and fully completed, but will be published soon. However, the
0.301 respectively [6]. gathered data can already be used to provide further insight
into the optimal utilization of hydrophilic OHL conductors,
Using results from various bundle configurations and which is the aim of this contribution.
conductor diameters it was possible to derive a surface
roughness coefficient of m = 0.38 for standard conductors and B. Intersection Surface Gradient
m = 0.44 for hydrophilic conductors (both for a rain rate of The large number of gathered results allows, for example,
6 mm/h). to predict the intersection surface gradients of various bundle
The discharge activity continuously increases for surface configurations (Fig. 4), which are universally valid and can
gradients E exceeding the onset gradient EC. However, with serve as first guideline for OHL design. For twin and triple
the increasing accumulation of space charges around the conductor bundles, the intersection gradient was observed to
conductors and the accompanying mutual shielding of be in the range of EI = 17… 19 kV/cm for d > 30mm. Towards
adjacent corona points, the emission curve gradually starts to thinner conductors the intersection surface gradient EI
flatten out. This behaviour is often referred to as the self- increases quite steeply. This behaviour is particularly
limiting mechanism of corona. pronounced for single conductors.
reduction then amounts to ΔA = 6 dB(A). Unsurprisingly, the
triple conductor bundle exhibits the most advantageous
audible noise behaviour.

Fig. 4. Intersection surface gradient EI for various bundle conductors with


n sub-conductors and sub-conductor diameter d.

C. Influence of the Bundle Geometry


Fig. 6. Noise reductions achievable from using hydrophilic conductors.
Regarding the design of an overhead line and based on the
exemplary curves shown in Fig. 3, the question arises how the V. OUTLOOK
surface gradient can be kept sufficiently low so that surface
treatments can still take effect. Naturally, for a fixed operating While single conductors and twin as well as triple
voltage U, increasing the number of sub-conductors n will conductors bundles are already fully incorporated in the newly
yield the most significant reduction of surface gradient and developed prediction model, quad bundles are not yet
thereby audible noise. However, the number of sub- sufficiently covered. Additionally, investigations with a
conductors is often chosen with other considerations in mind, suitable high-speed camera are planned to analyse the
which leaves the conductor diameter d as available parameter. discharge behaviour on water drops at surface gradients close
to the intersection gradient.
While the following results are universally valid, the
example of a standard European 400 kV line shall be used to VI. CONCLUSION
put the findings into perspective and to bridge the gap to real Hydrophilic conductor surfaces can provide a significant
life applications. For that purpose, Fig. 5 shows the average reduction of audible noise. However, the attainable reduction
maximum surface gradients E occurring on the point of diminishes with increasing surface gradient. Above the
minimum ground clearance on the line when n = 1…3 intersection surface gradient EI hydrophilic conductors exhibit
conductors per phase and conductors with diameters between higher noise levels than a standard conductor. A similar
d = 30…45 mm are used. The values for the intersection behaviour is apparent for the rain rate dependant emission
gradient summarized in Fig. 4 already suggest that a single behaviour of both conductor types, where low rain rates lead
conductor might give an unfavourable noise performance for to stronger noise emissions when the intersection surface
all available diameters, since it is constantly overstressed, gradient is exceeded. The noise reducing properties of
which cannot be remedied by using a hydrophilic conductor. hydrophilic conductors can therefore only be harnessed when
Employing a surface treated conductor will also be to little the surface gradient is sufficiently low. While increasing the
avail in the case of twin conductor bundles for d < 33 mm. number of sub-conductors per bundle yields the best results in
this respect, increasing the sub-conductor diameter can also
help to boost the efficacy of hydrophilic surfaces.

REFERENCES
[1] E. R. Taylor, V. L. Chartier, and D. N. Rice, “Audible Noise and Visual
Corona from HV and EHV Transmission Lines and Substation
Conductors – Laboratory Tests”, IEEE Transactions on Power
Apparatus and Systems, Vol. PAS-88(5), pp. 666 - 679, 1969.
[2] O. Pischler, U. Schichler, N. Hadinger, K. Reich, M. Leonhardsberger,
and O. Oberzaucher, “Corona Noise Reduction in the Austrian
Transmission Grid”, CIGRE SEERC, Report 3-113, Ukraine, 2019.
[3] O. Pischler, U. Schichler, S. Hedtke, P. Bleuler, and C. M. Franck,
“Corona Effects of Overhead Lines under Mixed AC/DC Stresses”,
CIGRE Symposium, Report PS1-95, Chengdu, People’s Republic of
Fig. 5. Surface gradient E occuring on the model OHL for various n and d. China, 2019.
[4] Electric Power Research Institute, “EPRI AC Transmission Line
Fig. 6 illustrates the noise reductions ΔA’ = A’hydro-A’std Reference Book – 200 kV and Above”, Third Edition, United States of
America, 2005.
which can be expected for the bundle configurations whose
surface gradients are shown in Fig. 5 when a hydrophilic [5] I. Kurniawan, Suwarno, O. Pischler, and U. Schichler, “Audible Noise
Calculation for Different Overhead Transmission Lines”, 53rd
conductor is used instead of a standard conductor. As International Universities Power Engineering Conference, Glasgow,
previously mentioned, in the present case, a hydrophilic Scotland, 2018.
surface will only aggravate the noise levels emitted by a single [6] F. Rizk, and G. Trinh, “High Voltage Enginnering”, CRC Press, 2014.
conductor. In case of a twin conductor bundle, a hydrophilic [7] P. Xu, S. Hedtke, B. Zhang, M. Pfeiffer, C. M. Franck, and J. He,
surface can be expected to yield a noticeable sound power “HVAC Corona Current Characteristics and Audible Noise during
reduction for d > 33 mm. For d = 45 mm the attainable noise Rain”, IEEE Transactions on Power Delivery, early access, 2020.

You might also like