You are on page 1of 7

CHAPTER 2

RETAIL FACILITIES
General Criteria ....................................................................... 2.1 Department Stores ..................................................................... 2.5
Small Stores .............................................................................. 2.1 Convenience Centers ................................................................. 2.6
Discount and Big Box Stores .................................................... 2.2 Regional Shopping Centers ....................................................... 2.6
Supermarkets ............................................................................ 2.2 Multiple-Use Complexes ........................................................... 2.7

T HIS chapter covers the design and application of air-con-


ditioning and heating systems for various retail merchandising
facilities. Load calculations, systems, and equipment are covered
to offset the greater cooling and heating requirements. Entrance ves-
tibules and heaters may be needed in cold climates.
Many new small stores are part of a shopping center. While exte-
elsewhere in the Handbook series. rior loads will differ between stores, the internal loads will be sim-
ilar; the need for proper design is important.
GENERAL CRITERIA
Design Considerations
To apply equipment properly, it is necessary to know the con-
struction of the space to be conditioned, its use and occupancy, the System Design. Single-zone unitary rooftop equipment is com-
time of day in which greatest occupancy occurs, the physical build- mon in store air conditioning. The use of multiple units to condition
ing characteristics, and the lighting layout. the store involves less ductwork and can maintain comfort in the
The following must also be considered: event of partial equipment failure. Prefabricated and matching curbs
simplify installation and ensure compatibility with roof materials.
• Electric power—size of service The heat pump, offered as packaged equipment, readily adapts to
• Heating—availability of steam, hot water, gas, oil, or electricity small-store applications and has a low first cost. Winter design con-
• Cooling—availability of chilled water, well water, city water, and ditions, utility rates, and operating cost should be compared to those
water conservation equipment for conventional heating systems before this type of equipment is
• Internal heat gains chosen.
• Rigging and delivery of equipment Water-cooled unitary equipment is available for small-store air
• Structural considerations conditioning, but many communities in the United States have
• Obstructions restrictions on the use of city and ground water for condensing pur-
• Ventilation—opening through roof or wall for outdoor air duct, poses and require the installation of a cooling tower. Water-cooled
number of doors to sales area, and exposures equipment generally operates efficiently and economically.
• Orientation of store Retail facilities often have a high sensible heat gain relative to
• Code requirements the total heat gain. Unitary HVAC equipment should be designed
• Utility rates and regulations and selected to provide the necessary sensible heat removal.
• Building standards Air Distribution. The external static pressures available in
Specific design requirements, such as the increase in outdoor air small-store air-conditioning units are limited, and ducts should be
required for exhaust where lunch counters exist, must be consid- designed to keep duct resistances low. Duct velocities should not
ered. The requirements of ASHRAE ventilation standards must be exceed 6 m/s and pressure drop should not exceed 0.8 Pa/m. Aver-
followed. Heavy smoking and objectionable odors may necessitate age air quantities range from 47 to 60 L/s per kilowatt of cooling in
special filtering in conjunction with outdoor air intake and exhaust. accordance with the calculated internal sensible heat load.
Load calculations should be made using the procedure outlined in Attention should be paid to suspended obstacles, such as lights
Chapter 28 of the 1997 ASHRAE Handbook—Fundamentals. and displays, that interfere with proper air distribution.
In almost all localities there is some form of energy code in effect The duct system should contain enough dampers for air balanc-
that establishes strict requirements for insulation, equipment effi- ing. Dampers should be installed in the return and outdoor air duct
ciencies, system designs, and so forth, and places strict limits on for proper outdoor air/return air balance. Volume dampers should be
fenestration and lighting. The requirements of ASHRAE Standard installed in takeoffs from the main supply duct to balance air to the
90 should be met as a minimum guideline for retail facilities. branch ducts.
The selection and design of the HVAC for retail facilities are nor- Control. Controls for small stores should be kept as simple as
mally determined by economics. First cost is usually the determin- possible while still able to perform the required functions. Unitary
ing factor for small stores; for large retail facilities, operating and equipment is typically available with manufacturer-supplied con-
maintenance costs are also considered. Generally, decisions about trols for ease of installation and operation.
mechanical systems for retail facilities are based on a cash flow Automatic dampers should be placed in the outdoor air intake to
analysis rather than on a full life-cycle analysis. prevent outdoor air from entering when the fan is turned off.
Heating controls vary with the nature of the heating medium.
SMALL STORES Duct heaters are generally furnished with manufacturer-installed
safety controls. Steam or hot water heating coils require a motorized
The large glass areas found at the front of many small stores may valve for heating control.
cause high peak solar heat gain unless they have northern expo- Time clock control can limit unnecessary HVAC operation.
sures. High heat loss may be experienced on cold, cloudy days. The Unoccupied reset controls should be provided in conjunction with
HVAC system for this portion of the small store should be designed timed control.
Maintenance. To protect the initial investment and ensure max-
The preparation of this chapter is assigned to TC 9.8, Large Building Air- imum efficiency, the maintenance of air-conditioning units in small
Conditioning Applications. stores should be contracted out to a reliable service company on a
2.2 1999 ASHRAE Applications Handbook (SI)

yearly basis. The contract should clearly specify responsibility for Ventilation and outdoor air must be provided as required in ASH-
filter replacements, lubrication, belts, coil cleaning, adjustment of RAE standards and local codes.
controls, compressor maintenance, replacement of refrigerant,
pump repairs, electrical maintenance, winterizing, system startup, Design Considerations
and extra labor required for repairs. Heat released by the installed lighting is usually sufficient to
Improving Operating Cost. Outdoor air economizers can offset the design roof heat loss. Therefore, the interior areas of
reduce the operating cost of cooling in most climates. They are gen- these stores need cooling during business hours throughout the
erally available as factory options or accessories with roof-mounted year. The perimeter areas, especially the storefront and entrance
units. Increased exterior insulation generally reduces operating areas, may have highly variable heating and cooling require-
energy requirements and may in some cases allow the size of ments. Proper zone control and HVAC design are essential. The
installed equipment to be reduced. Many codes now include mini- location of checkout lanes in this area makes proper environmen-
mum requirements for insulation and fenestration materials. tal control even more important.
System Design. The important factors in selecting discount and
DISCOUNT AND BIG BOX STORES outlet store air-conditioning systems are (1) installation costs, (2)
floor space required for equipment, (3) maintenance requirements
Large warehouse or big box stores attract customers with dis-
and equipment reliability, and (4) simplicity of control. Roof-
count prices when large quantities are purchased. These stores typ-
mounted units are the most commonly used.
ically have high bay fixture displays and usually store merchandise
in the sales area. They feature a wide range of merchandise and may Air Distribution. The air supply for large sales areas should
include such diverse areas as a lunch counter, an auto service area, generally be designed to satisfy the primary cooling requirement. In
a supermarket area, a pharmacy, and a garden shop. Some stores sell designing air distribution for the perimeter areas, the variable heat-
pets, including fish and birds. This variety of merchandise must be ing and cooling requirements must be considered.
considered in designing air conditioning. The design and applica- Because of the store requirement to maintain high, clear areas for
tion suggestions for small stores also apply to discount stores. display and restocking, air is generally distributed from heights of
Another type of big box facility provides both dry good and 4.3 m and greater. Air distribution at these heights requires high
velocities in the heating season to overcome the buoyancy of the hot
grocery areas. The grocery area is typically treated as a traditional
stand-alone grocery. Conditioning of outside air into the dry goods air. The velocity of this discharge air creates turbulence in the space,
areas must be considered to limit the introduction of excess mois- and induces air from the ceiling area complete mixing of the air.
ture that will migrate to the freezer aisles. The designer should take advantage of stratification to reduce the
equipment load. By introducing air near the customers at low veloc-
Hardware, lumber and furniture, etc. is also retailed from big box
ity, the air will stratify during the cooling season. With this method
facilities. An particular concern in this type of facility is ventilation
of air distribution, the set-point temperature can be maintained in
for material handling equipment, such as forklift trucks.
the occupant zone and the temperature in the upper space can be
In addition to the sales area in any of these facilities such areas as allowed to rise. However, this strategy requires equipment to
stockrooms, rest rooms, offices, and special storage rooms for per- destratify the air during the heating season. Space-mounted fans,
ishable merchandise may require air conditioning or refrigeration. and radiant heating at the perimeter, entrance, and sales areas may
be required.
Load Determination Control. Because the controls are usually operated by person-
Operating economics and the spaces served often dictate the nel who have little knowledge of air-conditioning, it should be
indoor design conditions. Some stores may base summer load cal- simple, dependable, and fully automatic systems—it should be as
culations on a higher inside temperature (e.g., 27ºC db) but then set simple to operate as a residential system. Most unitary equipment
the thermostats to control at 22 to 24ºC db. This reduces the has automatic electronic controls for ease of operation.
installed equipment size while providing the desired inside temper- Maintenance. Most stores do not employ trained maintenance
ature most of the time. personnel; they rely instead on service contracts with either the
Special rooms for storage of perishable goods are usually installer or a local service company. For suggestions on lowering
designed with separate unitary air conditioners. operating costs, see the previous section on Small Stores.
The heat gain from lighting will not be uniform throughout the
entire area. For example, jewelry and other specialty displays have SUPERMARKETS
lighting heat gains as high as 65 to 85 W per square meter of floor
area, while the typical sales area has an average value of 20 to Load Determination
40 W/m2. For stockrooms and receiving, marking, toilet, and rest Heating and cooling loads should be calculated using the meth-
room areas, a value of 20 W/m2 may be used. When available, ods outlined in Chapter 28 of the 1997 ASHRAE Handbook—Fun-
actual lighting layouts rather than average values should be used for damentals. Data for calculating the loads due to people, lights,
load computation. motors, and heat-producing equipment should be obtained from the
The store owner usually determines the population density for a store owner or manager or from the equipment manufacturer. In
store based on its location, size, and past experience. supermarkets, space conditioning is required both for human com-
Food preparation and service areas in discount and outlet stores fort and for proper operation of refrigerated display cases. The air-
range from small lunch counters having heat-producing equipment conditioning unit should introduce a minimum quantity of outdoor
(ranges, griddles, ovens, coffee urns, toasters) in the conditioned air. This quantity is either the volume required for ventilation based
space to large deluxe installations with kitchens separate from the on ASHRAE Standard 62 or the volume required to maintain
conditioned space. Chapter 30 has specific information on HVAC slightly positive pressure in the space, whichever is larger.
systems for kitchen and eating spaces. Many supermarkets are units of a large chain owned or operated
Data on the heat released by special merchandising equipment, by a single company. The standardized construction, layout, and
such as amusement rides for children or equipment used for prepar- equipment used in designing many similar stores simplify load cal-
ing speciality food items (e.g., popcorn, pizza, frankfurters, ham- culations.
burgers, doughnuts, roasted chickens, cooked nuts, etc.), should be It is important that the final air-conditioning load be correctly
obtained from the equipment manufacturers. determined. Refer to manufacturers’ data for information on the
Retail Facilities 2.3

total heat extraction, sensible heat, latent heat, and percentage of Each of these problems is present to some degree in every super-
latent to total load for display cases. Engineers report considerable market, although situations vary with climate and store layout.
fixture heat removal (case load) variation as the relative humidity Methods of overcoming these problems are discussed in the follow-
and temperature vary in comparatively small increments. Relative ing sections. Extremely high energy cost may ensue if the year-
humidity above 55% substantially increases the load, while reduced round air-conditioning system has not been designed to compensate
relative humidity substantially decreases the load, as shown in Fig- for the effects of refrigerated display equipment.
ure 1. Trends in store design, which include more food refrigeration Heat Removed by Refrigerated Displays. The display refrig-
and more efficient lighting, reduce the sensible component of the erator not only cools a displayed product but envelops it in a blanket
load even further. of cold air that absorbs heat from the room air in contact with it.
To calculate the total load and percentage of latent and sensible Approximately 80 to 90% of the heat removed from the room by
heat that the air conditioning must handle, the refrigerating effect vertical refrigerators is absorbed through the display opening. Thus,
imposed by the display fixtures must be subtracted from the build- the open refrigerator acts as a large air cooler, absorbing heat from
ing’s gross air-conditioning requirements. the room and rejecting it via the condensers outside the building.
Modern supermarket designs have a high percentage of closed Occasionally, this conditioning effect can be greater than the design
refrigerated display fixtures. These vertical cases have large glass air-conditioning capacity of the store. The heat removed by the
display doors and greatly reduce the problem of latent and sensible refrigeration equipment must be considered in the design of the air-
heat removal from the occupied space. The doors do, however, conditioning and heating systems because this heat is being
require heaters to prevent condensation and fogging. These heaters removed constantly, day and night, summer and winter, regardless
should be cycled based on some kind of automatic control. of the store temperature.
The display cases increase the heating requirement of the
Design Considerations building such that heat is often required at unexpected times. The
Store owners and operators frequently complain about cold following example is an indication of the extent of this cooling
aisles, heaters that operate even when the outdoor temperature is effect. The desired store temperature is 24ºC. Store heat loss or
above 21ºC, and air-conditioners that operate infrequently. These gain is assumed to be 8 kW/ºC of temperature difference between
problems are usually attributed to spillover of cold air from open outdoor and store temperature. (This value varies with store size,
refrigerated display equipment. location, and exposure.) The heat removed by refrigeration
Although refrigerated display equipment may be the cause of equipment is 56 kW. (This value varies with the number of
cold stores, the problem is not due to excessive spillover or improp- refrigerators.) The latent heat removed is assumed to be 19% of
erly operating equipment. Heating and air-conditioning systems the total, leaving 81% or 45.4 kW sensible heat removed, which
must compensate for the effects of open refrigerated display equip- will cool the store 45.4/8 = 5.7ºC. By constantly removing sensi-
ment. Design considerations include the following: ble heat from its environment, the refrigeration equipment in this
store will cool the store 5.7ºC below outdoor temperature in win-
1. Increased heating requirement due to removal of large quantities ter and in summer. Thus, in mild climates, heat must be added to
of heat, even in summer. the store to maintain comfort conditions.
2. Net air-conditioning load after deducting the latent and sensible The designer has the choice of discarding or reclaiming the
refrigeration effect (Item 1). The load reduction and change in heat removed by refrigeration. If economics and store heat data
sensible-latent load ratio have a major effect on equipment indicate that the heat should be discarded, heat extraction from the
selection. space must be included in the heating load calculation. If this
3. Need for special air circulation and distribution to offset the heat internal heat loss is not included, the heating system may not have
removed by open refrigerating equipment. sufficient capacity to maintain the design temperature under peak
4. Need for independent temperature and humidity control. conditions.
The additional sensible heat removed by the cases may change
the air-conditioning latent load ratio from 32% to as much as 50%
110
of the net heat load. Removal of a 50% latent load by means of
refrigeration alone is very difficult. Normally, it requires specially
designed equipment with reheat or chemical adsorption.
100
Multishelf refrigerated display equipment requires 55% rh or
less. In the dry-bulb temperature ranges of average stores, humidity
in excess of 55% can cause heavy coil frosting, product zone frost-
ing in low-temperature cases, fixture sweating, and substantially
PERCENT LOAD

90 increased refrigeration power consumption.


LOW TEMP.
A humidistat can be used during summer cooling to control
humidity by transferring heat from the condenser to a heating coil in
the airstream. The store thermostat maintains proper summer tem-
80 MEDIUM TEMP. perature conditions. Override controls prevent conflict between the
humidistat and the thermostat.
The equivalent result can be accomplished with a conventional
air-conditioning system by using three- or four-way valves and
70
reheat condensers in the ducts. This system borrows heat from the
standard condenser and is controlled by a humidistat. For higher
energy efficiency, specially designed equipment should be consid-
60 ered. Desiccant dehumidifiers and heat pipes have also been used.
4 5 6 7 8 9 10 11 Humidity. Cooling from the refrigeration equipment does not
ABSOLUTE HUMIDITY, g/kg preclude the need for air conditioning. On the contrary, it increases
the need for humidity control.
Fig. 1 Refrigerated Case Load Variation with Store With increases in store humidity, heavier loads are imposed on
Air Humidity the refrigeration equipment, operating costs rise, more defrost
2.4 1999 ASHRAE Applications Handbook (SI)

periods are required, and the display life of products is shortened. 1. Return Ducts in Floor. This is the preferred method and can be
The dew point rises with the relative humidity, and sweating can accomplished in two ways. The floor area in front of the refrig-
become profuse to the extent that even nonrefrigerated items such erated display cases is the coolest area. Refrigerant lines are run
as shelving superstructures, canned products, mirrors, and walls to all of these cases, usually in tubes or trenches. If the trenches
may sweat. or tubes are enlarged and made to open under the cases for air
There are two commonly used devices for achieving humidity return, air can be drawn in from the cold area (see Figure 2). The
control. One is an electric vapor compression air conditioner, air is returned to the air-handling unit through a tee connection to
which overcools the air to condense the moisture and then the trench before it enters the back room area. The opening
reheats it to a comfortable temperature. Condenser waste heat is through which the refrigerant lines enter the back room should
often used. Vapor compression holds humidity levels at 50 to be sealed.
55% rh. If refrigerant line conduits are not used, the air can be
The second dehumidification device is a desiccant dehumidi- returned through inexpensive underfloor ducts. If refrigerators
fier. A desiccant absorbs or adsorbs moisture directly from the air have insufficient undercase air passage, the manufacturer
to its surface. The desiccant material is reactivated by passing hot should be consulted. Often they can be raised off the floor
air at 80 to 110ºC through the desiccant base. Condenser waste approximately 40 mm. Floor trenches can also be used as ducts
heat can provide as much as 40% of the heat required. Desiccant for tubing, electrical supply, and so forth.
systems in supermarkets can maintain humidity in the lower Floor-level return relieves the problem of localized cold areas
ranges of the comfort index. Lower humidity results in lower and cold aisles and uses the cooling effect for store cooling, or
operating costs for the refrigerated cases. increases the heating efficiency by distributing the air to the areas
System Design. The same air-handling equipment and distri- that need it most.
bution system are generally used for both cooling and heating. 2. Fans Behind Cases. If ducts cannot be placed in the floor,
The entrance area is the most difficult section to heat. Many circulating fans can draw air from the floor and discharge it
supermarkets in the northern United States are built with vesti- above the cases (see Figure 3). While this approach prevents
bules provided with separate heating equipment to temper the objectionable cold aisles in front of the refrigerated display
cold air entering from the outdoors. Auxiliary heat may also be cases, it does not prevent the area with a concentration of refrig-
provided at the checkout area, which is usually close to the front erated fixtures from remaining colder than the rest of the store.
entrance. Methods of heating entrance areas include the use of
(1) air curtains, (2) gas-fired or electric infrared radiant heaters, Control. Store personnel should only be required to change the
and (3) waste heat from the refrigeration condensers. position of a selector switch to start or stop the system or to change
Air-cooled condensing units are the most commonly used in
supermarkets. Typically, a central air handler conditions the
entire sales area. Specialty areas like bakeries, computer rooms,
or warehouses are better served with a separate air handler
because the loads in these areas vary and require different control
than the sales area.
Most installations are made on the roof of the supermarket.
If air-cooled condensers are located on the ground outside the
store, they must be protected against vandalism as well as truck
and customer traffic. If water-cooled condensers are used on the
air-conditioning equipment and a cooling tower is required,
provisions should be made to prevent freezing during winter
operation.
Air Distribution. Designers overcome the concentrated load
at the front of a supermarket by discharging a large portion of the
total air supply into the front third of the sales area.
Fig. 2 Floor Return Ducts
The air supply to the space with the vapor compression system
has typically been 5 L/s per square metre of sales area. This value
should be calculated based on the sensible and latent internal
loads. The desiccant system typically requires less air supply due
to its high moisture removal rate. In most cases, only about 40%
of the circulation rate passes through the dehumidifier.
Being more dense, the air cooled by the refrigerators settles to
the floor and becomes increasingly colder, especially in the first
900 mm above the floor. If this cold air remains still, it causes
discomfort and serves no purpose, even when other areas of the
store need more cooling. Cold floors or areas in the store cannot
be eliminated by the simple addition of heat. Any reduction of
air-conditioning capacity without circulation of the localized
cold air would be analogous to installing an air conditioner with-
out a fan. To take advantage of the cooling effect of the refrigera-
tors and provide an even temperature in the store, the cold air
must be mixed with the general store air.
To accomplish the necessary mixing, air returns should be
located at floor level; they should also be strategically placed to
remove the cold air near concentrations of refrigerated fixtures.
The returns should be designed and located to avoid the creation
of drafts. There are two general solutions to this problem: Fig. 3 Air Mixing Using Fans Behind Cases
Retail Facilities 2.5

(3) use of outdoor air for cooling during intermediate seasons and
peak sales periods. It is also desirable to adjust indoor temperature for
variations in the outdoor temperature. While the close control of
humidity is not necessary, a properly designed system should operate
to maintain relative humidity at 50% or below with a corresponding
dry-bulb temperature of 26ºC. This humidity limit eliminates musty
odors and retards perspiration, particularly in fitting rooms.

Load Determination
Because the occupancy (except store personnel) is transient,
indoor conditions are commonly set not to exceed 26ºC db and 50%
rh at outdoor summer design conditions, and 21ºC db at outdoor
winter design conditions. Winter humidification is seldom used in
store air conditioning.
The number of customers and store personnel normally found
on each conditioned floor must be ascertained, particularly in spe-
cialty departments or other areas having a greater-than-average
concentration of occupants. Lights should be checked for wattage
and type. Table 1 gives approximate values for lighting in various
Fig. 4 Heat Reclaiming Systems areas; Table 2 gives approximate occupancies.
Other loads, such as those from motors, beauty parlor and restau-
rant equipment, and any special display or merchandising equip-
ment, should be determined.
The minimum outdoor air requirement should be as defined in
the ASHRAE Standard 62, which are generally acceptable and ade-
quate for removing odors and keeping the building atmosphere
fresh. However, local ventilation ordinances may require greater
quantities of outdoor air.
Paint shops, alteration rooms, rest rooms, eating places, and
locker rooms should be provided with positive exhaust ventilation,
and their requirements must be checked against local codes.

Design Considerations
Before performing load calculations, the designer should exam-
ine the store arrangement to determine what will affect the load and
the system design. For existing buildings, a survey can be made of
Fig. 5 Machine Room with Automatic Temperature actual construction, floor arrangement, and load sources. For new
Control Interlocked with Store Temperature Control buildings, an examination of the drawings and a discussion with the
architect or owner will be required.
from heating to cooling or from cooling to heating. Control systems Larger stores may contain beauty parlors, restaurants, lunch
for heat recovery applications are more complex and should be counters, or auditoriums. These special areas may operate during all
coordinated with the equipment manufacturer. store hours. If one of these areas has a load that is small in propor-
Maintenance and Heat Reclamation. Most supermarkets, tion to the total load, the load may be met by the portion of the air
except large chains, do not employ trained maintenance personnel, conditioning serving that floor. If present or future operation could
but rather rely on service contracts with either the installer or a local for any reason be compromised by such a strategy, this space should
service company. This relieves the store management of the respon- be served by separate air conditioning. Because of the concentrated
sibility of keeping the air conditioning operating properly. load in the beauty parlor, separate air distribution should be pro-
The heat extracted from the store and the heat of compression vided for this area.
may be reclaimed for heating cost saving. One method of reclaim-
ing the rejected heat is to use a separate condenser coil located in the Table 1 Approximate Lighting Load for Department Stores
air conditioner’s air handler, either alternately or in conjunction
Area W/m2
with the main refrigeration condensers, to provide heat as required
(see Figure 4). Another system uses water-cooled condensers and Basement 30 to 50
delivers its rejected heat to a water coil in the air handler. First floor 40 to 70
The heat rejected by conventional machines using air-cooled Upper floors, women’s wear 30 to 50
condensers may be reclaimed by proper duct and damper design Upper floors, house furnishings 20 to 30
(see Figure 5). Automatic controls can either reject this heat to the
outdoors or recirculate it through the store. Table 2 Approximate Occupancy for Department Stores

DEPARTMENT STORES Area m2 per person


Basement, metropolitan area 2 to 9
Department stores vary in size, type, and location, so air-condition-
Basement, other with occasional peak 2 to 9
ing design should be specific to each store. An ample minimum quan-
tity of outdoor air reduces or eliminates odor problems. Essential First floor, metropolitan area 2 to 7
features of a quality system include (1) an automatic control system First floor, suburban 2 to 7
properly designed to compensate for load fluctuations, (2) zoned air Upper floors, women’s wear 5 to 9
distribution to maintain uniform conditions under shifting loads, and Upper floors, house furnishings 9 or more
2.6 1999 ASHRAE Applications Handbook (SI)

The restaurant, because of its required service facilities, is gen- HVAC units in the small stores with the shell construction, often
erally centrally located. It is often used only during the noon hours. before the space is leased or the occupancy is known. The larger
For control of odors, a separate air-handling system should be con- stores typically provide their own HVAC design and installation.
sidered. Future plans for the store must be ascertained because they
can have a great effect on the type of air conditioning and refriger- Design Considerations
ation to be used. The developer or owner may establish standards for typical heat-
System Design. Air conditioning for department stores may be ing and cooling that may or may not be sufficient for the tenant’s
of the unitary or central-station type. Selection should be based on specific requirements. The tenant may therefore have to install sys-
owning and operating costs as well as any other special consider- tems of different sizes and types than originally allowed for by the
ations for the particular store, such as store hours, load variations, developer. The tenant must ascertain that power and other services
and size of load. will be available for the total intended requirements.
Large department stores often use central-station systems con- The use of party walls in convenience centers tends to reduce
sisting of air-handling units having chilled water cooling coils, hot heating and cooling loads. However, the effect an unoccupied adja-
water heating coils, fans, and filters. Air systems must have ade- cent space has on the partition load must be considered.
quate zoning for varying loads, occupancy, and usage. Wide varia-
tions in people loads may justify consideration of variable volume
air distribution systems. The water chilling and heating plants dis-
REGIONAL SHOPPING CENTERS
tribute water to the various air handlers and zones and may take Regional shopping centers generally incorporate an enclosed
advantage of some load diversity throughout the building. heated and air-conditioned mall. These centers are normally owned
Air-conditioning equipment should not be placed in the sales by a developer, who may be an independent party, a financial insti-
area; instead, it should be located in ceiling, roof, and mechanical tution, or one of the major tenants in the center.
equipment room areas whenever practicable. Maintenance and The major department stores are typically considered to be sep-
operation after installation should be considered in the location of arate buildings, although they are attached to the mall. The space
equipment. for individual small stores is usually leased. Arrangements for
Air Distribution. All buildings must be studied for orienta- installing air conditioning in the individually leased spaces vary,
tion, wind exposure, construction, and floor arrangement. These but are similar to those for small stores in convenience centers.
factors affect not only load calculations, but also zone arrange- Table 3 presents typical data that can be used as check figures
ments and duct locations. In addition to entrances, wall areas with and field estimates. However, this table should not be used for final
significant glass, roof areas, and population densities, the determination of load, since the values are only averages.
expected locations of various departments (e.g., the lamp depart-
ment) should be considered. Flexibility must be left in the duct Design Considerations
design to allow for future movement of departments. The prelimi-
The owner provides the air-conditioning system for the enclosed
nary duct layout should also be checked in regard to winter heat-
mall. The mall may use a central plant or unitary equipment. The
ing to determine any special situations. It is usually necessary to
owner generally requires that the individual tenant stores connect to
design separate air systems for entrances, particularly in northern
a central plant and includes charges for heating and cooling in the
areas. This is also true for storage areas where cooling is not con-
rent. Where unitary systems are used, the owner generally requires
templated.
that the individual tenant install a unitary system of similar design.
Air curtains may be installed at entrance doorways to limit or
The owner may establish standards for typical heating and cool-
prevent infiltration of unconditioned air, at the same time providing
ing systems that may or may not be sufficient for the tenant’s spe-
greater ease of entry.
cific requirements. Therefore, the tenant may have to install systems
Control. The necessary extent of automatic control depends on of different sizes than originally allowed for by the developer.
the type of installation and the extent to which it is zoned. Control
Leasing arrangements may include provisions that have a detri-
must be such that correctly conditioned air is delivered to each zone.
mental effect on conservation (such as allowing excessive lighting
Outdoor air intake should be automatically controlled to operate at
and outdoor air or deleting requirements for economizer systems).
minimum cost. Partial or full automatic control should be provided
The designer of HVAC for tenants in a shopping center must be
for cooling to compensate for load fluctuations. Completely auto-
well aware of the lease requirements and work closely with leasing
matic refrigeration plants should be considered.
agents to guide these systems toward better energy efficiency.
Maintenance. Most department stores employ personnel for
Many regional shopping centers now contain specialty food
routine operation and maintenance, but rely on service and preven-
court areas that require special considerations for odor control, out-
tive maintenance contracts for refrigeration cycles, chemical treat-
door air requirements, kitchen exhaust, heat removal, and refriger-
ment, central plant systems, and major repairs.
ation equipment.
Improving Operating Cost. An outdoor air economizer can
reduce the operating cost of cooling in most climates. These are System Design. Regional shopping centers vary widely in phys-
generally available as factory options or accessories with the air- ical arrangement and architectural design. Single-level and smaller
handling units or control systems. Heat recovery and thermal stor- centers usually use unitary systems for mall and tenant air condi-
age should also be analyzed. tioning; multilevel and larger centers usually use a central plant. The
owner sets the design of the mall and generally requires that similar
systems be installed for tenant stores.
CONVENIENCE CENTERS
A typical central plant may distribute chilled air to the individual
Many small stores, discount stores, supermarkets, drugstores, tenant stores and to the mall air-conditioning system and employ
theaters, and even department stores are located in convenience variable volume control and electric heating at the local use point.
centers. The space for an individual store is usually leased. Some plants distribute both hot and chilled water. All-air systems
Arrangements for installing air conditioning in leased space vary. have also been used that distribute chilled or heated air to the indi-
In a typical arrangement, the developer builds a shell structure and vidual tenant stores and to the mall air conditioning and use variable
provides the tenant with an allowance for typical heating and cool- volume control at the local use point. The central plant provides
ing and other minimum interior finish work. The tenant must then improved efficiency and better overall economics of operation.
install an HVAC system. In another arrangement, developers install They also provide the basic components required for smoke control.
Retail Facilities 2.7

Table 3 Typical Installed Capacity and Energy Use in Enclosed Mall Centersa
Based on 1979 Data—Midwestern United States
Annual Consumption, MJ/m2
Installed Cooling
Type of Space W/m2 Lightingb Cooling c Heatingd Miscellaneous
Candy store 141 to 246 926 to 1147 302 to 911 372 to 221 93 to 2716
Clothing store 118 to 144 546 to 965 310 to 372 345 to 198 47 to 260
Fast food 152 to 246 647 to 1256 380 to 911 372 to 147 1476 to 2713
Game room 107 to 140 264 to 484 279 to 283 535 to 182 8 to 535
Gen. merchandise 104 to 138 512 to 903 244 to 376 244 to 217 54 to 360
Gen. service 124 to 159 608 to 674 302 to 357 465 to 229 295 to 318
Gift store 115 to 161 496 to 887 244 to 388 275 to 190 16 to 85
Grocery 219 to 272 422 to 748 205 to 345 233 to 271 721 to 814
Jewelry 169 to 209 1442 to 1740 411 to 477 217 to 140 295 to 360
Mall 95 to 151 209 to 465 322 to 531 446 to 217 8 to 58
Restaurant 126 to 167 194 to 853 302 to 477 736 to 647 667 to 814
Shoe store 116 to 160 791 to 1244 287 to 442 279 to 178 39 to 89
Center average 95 to 151 698 to 1085 310 to 581 233 to 116 39 to 116
aOperation of center assumed to be 12 h/day and 6.5 days/week. cCooling includes blower motor and is for unitary-type system.
bLighting includes miscellaneous and receptacle loads. dHeating includes blower and is for electric resistance heating.

Air Distribution. Air distribution for individual stores should be HVAC loads of the various occupancies should be determined inde-
designed for a particular space occupancy. Some tenant stores main- pendently. Where a combined central plant is under consideration, a
tain a negative pressure relative to the mall for odor control. block load should also be determined.
The air distribution should maintain a slight positive pressure
relative to atmospheric pressure and a neutral pressure relative to Design Considerations
most of the individual tenant stores. Exterior entrances should have Retail facilities are generally located on the lower levels of
vestibules with independent heating systems. multiple-use complexes, and other commercial facilities are on
Smoke management is required by many building codes, so the upper levels. Generally, the perimeter loads of the retail portion
air distribution should be designed to easily accommodate smoke differ from those of the other commercial spaces. Greater light-
control requirements. ing and population densities also make the HVAC demands for
Maintenance. Methods for ensuring the operation and mainte- the retail space different from those for the other commercial
nance of HVAC systems in regional shopping centers are similar to space.
those used in department stores. Individual tenant stores may have
The differences in HVAC characteristics for the various occu-
to provide their own maintenance.
pancies within a multiple-use complex indicate that separate air
Improving Operating Cost. Methods for lowering operating handling and distribution should be used for the separate spaces.
costs in shopping centers are similar to those used in department
However, combining the heating and cooling requirements of the
stores. Some shopping centers have successfully employed cooling
various facilities into a central plant can achieve a substantial sav-
tower heat exchanger economizers. ing. A combined central heating and cooling plant for a multiple-use
Central plant systems for regional shopping centers typically
complex also provides good opportunities for heat recovery, ther-
have much lower operating costs than unitary systems. However,
mal storage, and other similar functions that may not be economical
the initial cost of the central plant system is typically higher. in a single-use facility.
Many multiple-use complexes have atriums. The stack effect
MULTIPLE-USE COMPLEXES created by atriums requires special design considerations for tenants
Multiple-use complexes are being developed in most metropoli- and space on the main floor. Areas near entrances require special
tan areas. These complexes generally combine retail facilities with considerations to prevent drafts and accommodate extra heating
other facilities such as offices, hotels, residences, or other commer- requirements.
cial space into a single site. This consolidation of facilities into a System Design. Individual air-handling and distribution systems
single site or structure provides benefits such as improved land use; should be designed for the various occupancies. The central heating
structural savings; more efficient parking; utility savings; and and cooling plant may be sized for the block load requirements,
opportunities for more efficient electrical, fire protection, and which may be less than the sum of each occupancy’s demand.
mechanical systems. Control. Multiple-use complexes typically require centralized
control. It may be dictated by requirements for fire and smoke
Load Determination control, security, remote monitoring, billing for central facilities
The various occupancies may have peak HVAC demands that use, maintenance control, building operations control, and energy
occur at different times of the day or even of the year. Therefore, the management.

You might also like