You are on page 1of 2

Madagascar Chemicals & Printing Industry s.a.r.l.

THE MONTHLY CONSUMPTION OF


BOILER CHEMICAL
Capacity of Boiler 1000 kg/h and 2000 kg/h
Hour of Operation 12 h
Hardness of Raw water 20 to 25 ppm
Softened Water >1 ppm
Level of oxygen in feed water @70 to 800 C 2 to 3 ppm
Level of polymer in boiler 600 to 800 ppm
Cycle of concentration 15 taken as
Permissible hardness in boiler Less than 5 ppm
Iron content in feed water Less than 1 ppm for Jirama Water
Boiler Fired Oil Fired

The level of Oxygen is highly enough to enhance process of intensive problems of pitting
and corrosion in the absence of good oxygen scavenger.

Cell. +261 3420 60009 ; E-mail : mcpi.tana@gmail.com ; BP 1682 ; Lot 2 DF AntanetibeIlafyTana 101
Madagascar Chemicals & Printing Industry s.a.r.l.

Our Product consists of catalysed sulphite to inhibit corrosion through the following
process:

Sodium Sulphite combined with oxygen to form dissolved Sodium Sulphate

Na2SO3 + ½ O2--------- Na2 SO4

Monthly consumption of boiler product is as follows:

Consumption = Capacity of boiler x Polymer level x Oxygen level


----------------------------------------------
1000000 X 15 Cycles

= 1000x 700 ppm x 3 ppm


----------------------
1000000x 15

= 0.14 kg per hour

Based on 26 days at an operation of 12/24.

Capacity of Boiler Product/h Product/ day Product/month


1000 kg/h 0.14 kg 1.68 kg 43.68 kg

Packaging is 25 kg / pail
Therefore, to cope with one month it is advisable to order 50 kg of Product AmertrolTM ST
8046.

Cell. +261 3420 60009 ; E-mail : mcpi.tana@gmail.com ; BP 1682 ; Lot 2 DF AntanetibeIlafyTana 101