Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model AF22D5
Power (kVA) 20 22
Engine brand AGG
Power (kW) 16 18
Engine model AF2540
Rated speed ( r.p.m) 1500
Speed control type Electronic
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage 12V
AU VE
RI
BURE

ISO 9001
TA S

BUREAU VERITAS
Certification
182 8
Frequency 50HZ
Engine speed (RPM) 1500
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 5.5
2006/42/EC Machinery safety. Fuel 5
100% prime power
2006/95/EC Low voltage Consumption
EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 75% prime power 3.7
12601 : 2010 (L/H)
50% prime power 2.6
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
Standard reference Conditions
power sequence, which may be run for an unlimited number of hours per year, between
Note: Standard reference condition 25 (77℉) air inlet temp, 100m(328ft) A.S.L 30%
stated maintenance intervals. The permissible average power output during at 24 hours
relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
period shall not exceed 80% of the prime power. 10% overload available for governing
conforming to BS 2869: 1998 Class A2
purposes only.

(2) ESP (Standby Power):


L L
According to ISO 8528-1, It is defined as the maximum power available, under the
agreed operating conditions, for which the generating set is capable of delivering for up
to 500 hours of operation per year (of which no more than 300 hours for continuative
H H
use) with the maintenance intervals and procedures being carried out as prescribed by
W W
the manufacturers. No overload capability is available.

Dimension and Weight


Dimension Silent
Powers ESP PRP Standby
Length (L) 2008mm
Voltage (V) KVA KW KVA KW Amps
Width (W) 950mm
415/240 22 18 20 16 30.6
Height (H) 1389mm
400/230 22 18 20 16 31.8 Net Weight 982 KG
380/220 22 18 20 16 33.4 Fuel Tank (L) 150L
Note: This parameters allows for some acceptable deviations.
Engine Specification :AF2540

Basic technical data Intake system

No. of cyl / Arrangement 4L Air consumption at 100% of load 1.9 m³/min

Injection system Direct Air intake restriction clean filter ≤ 2.5

Governor Method Electronic Air filter type Dry

Induction System Naturally Aspirated

Bore x stroke mm 90*100 mm

Displacement 2.545 L Exhaust system

Compression ratio 18 :1 Gas flow at stand by power 5.5 m³/min

Engine speed 1500rpm Max temperature 550 °C

Flywheel rotation Counter-clockwise Max allowable back pressure 6.7 kPa

viewed on flywheel

Housing flywheel SAE 4


Electric system
Flywheel 7.5"/10"
starter motor power 3.5 kW
Engine dry weight 220
rated voltage 12 V
Heat rejection of exhaust 20.2 kW
Starting batteries recommended capacity 100 Ah
Heat rejection from engine 1.6 kW
Alternator rated voltage 14 V
Heat rejection of coolant 16.1 kW
power 750 kW
Dimensions 750*555*680 mm

Performances Cooling package

Prime Power (gross) 21 kWm Type Liquid

Stand-By Power (gross) 23 kWm Recommanded coolant Water + Ethylene Glycol(50:50)

Fan consumption 1 kWm Coolant capacity 8

Performance conditions Shutdown switch setting 100 ± 3ºC

-temperature 25°C Fan

-pressure 100 mbar -diameter 400 mm

-humidity 30% -number of pale 7

-drive ratio 170/113

Lubrication system

Oil system capacity including filters 8L

Oil pressure at rated speed >=3.5 kPA

Oil temperature max 110 °C

Oil specification 15W40 CF4

Oil consumption 0.05%


Alternator Specification
Emergency voltage curve

Sudden increase warp


Alternator Sudden voltage warp Sudden decrease warp

Number of phase 3 520

Power factor (Cos Phi) 0.8 464

+1%
Poles 4 408 +1%
380
380
-1%
Winding Connections (standard) Star-serie 352

Terminals 12 296

Insulation type H class 240


0 1 2 3 4 5 6 7 8 9 10 11 12

Winding Pitch 2/3 δu%: -18.18


δu%: 8.89
Benchmark phase: A
Benchmark phase: A
Min. voltage: 310.9V Recovery time:
Recovery time:
1.95s
0..12ss
Max. voltage: 413.8V

IP rating IP23

Excitation system Self-excited

Bearing Single bearing Emergency frequency curve


Coating Vacuum impregnation Sudden voltage warp
Sudden increase warp
Sudden decrease warp
70
Voltage regulator A.V.R

Couping Flexible disc 62

54 +1%
50
-1%
+1%
50
-1%
46

38

30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s

Options

Engine Alternator Generator Sets Fuel System

· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD

Canopy Lub oil system Cooling System Control Panel

· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay
Control Panel

Configuration Benefits

· Emergency stop button · Less wiring and components


· Integrated solution
· Protection MCB
· Less engineering and programming
· Battery charger · User friendly set-up and button layout
· Integrated aviation plug · Module can be configured to suit individual applications
· ATS connection · PC software for simplified configuration
· Digital control module · Wide range of communication capabilities

Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· Storage temp: -30 ˚C to + 80 ˚C
· Operating humidity: 95% w/o condensation
· Vibration: 5-25Hz, ±1.6 mm
5-1 00 Hz, a=4g
· Shocks: a= 500m/s²

Options

· Ethernet interface (Remote monitoring and control)


· GSM modem/wireless internet (Remote monitoring and control)
· RS232-RS485 Dual por t interface
· Synchronizing control panel
· Distribution board with sockets kit and power busbar
· Battery trickle charge ammeter
· Ear th leakage protection
· Ear th fault protection
· Low fuel level alarm
· Low fuel level shutdown
· High fuel level alarm
· Fuel transfer system control
· Low coolant level shutdown
· High lube oil temp shutdown
· Overload via alarm switch on breaker
· Engine coolant heater controls
· Control panel heater
· S peed adjust switch
· Oil temp displayed on LCD screen
· Additional 8 inputs and outputs
Publication No. GYH0518N, ISSUE 1 @ AGG UK

AGG UK | AGG China | AGG USA | AGG UAE Distributed by www.activ.eco

info@aggpower.co.uk | www.aggpower.co.uk

Follow us @facebook.com/aggpowergroup

Follow us @linkedin.com/company/agg-power

Follow us @ AGGPOWER

All information in the document is substantially correct a the time of printing


but may be subsequently altered by the company.

You might also like