You are on page 1of 4

Your professional power assistant

Model: P450E5

Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model P450E5
Power (kVA) 400 450
Engine brand Perkins
Power (kW) 320 360
Engine model 2206A-E13TAG3
Rated speed ( r.p.m) 1500
Speed control type ECM
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage 24V
AU VE
RI
BURE

ISO 9001
TA S

BUREAU VERITAS
Certification
182 8
Frequency 50HZ
Engine speed (RPM) 1500
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 89
·2006/42/EC Machinery safety. Fuel
100% prime power 81
·2006/95/EC Low voltage Consumption
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 75% prime power 62
12601 : 2010 (L/H)
50% prime power 42
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
Standard reference Conditions
power sequence, which may be run for an unlimited number of hours per year, between
Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30%
stated maintenance intervals. The permissible average power output during at 24 hours
relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
period shall not exceed 80% of the prime power. 10% overload available for governing
conforming to BS 2869: 1998 Class A2
purposes only.

(2) ESP (Standby Power):


L L
According to ISO 8528-1, It is defined as the maximum power available, under the
agreed operating conditions, for which the generating set is capable of delivering for up
to 500 hours of operation per year (of which no more than 300 hours for continuative H
H
use) with the maintenance intervals and procedures being carried out as prescribed by W
W
the manufacturers. No overload capability is available.

Dimension and Weight


Dimension Open Silent
Powers ESP PRP Standby
Length (L) 3180mm 4470mm
Voltage (V) KVA KW KVA KW Amps
Width (W) 1180mm 1420mm
415/240 450 360 400 320 626.1
Height (H) 1925mm 2385mm
400/230 450 360 400 320 649.5 Net Weight 3500KG 4450KG
380/220 450 360 400 320 683.7 Fuel Tank (L) 320 750
Note: This parameters allows for some acceptable deviations.
Your professional power assistant

Engine Specification: 2206A-E13TAG3

Basic technical data Induction system

No. of cylinders 6 Clean filter 2.5kpa

Cylinder arrangement Ver tical in-line Dir ty filter 6.4kpa

Cycle 4 stroke Air filter type Paper element - 15 inch diameter

Induction system Turbocharged, air-to-air charge cooling

Compression ratio 16.3:1

Bore 130mm

Stroke 157mm Lubrication system


Displacement 12.5L 40L
Total lub capacity
All ratings cer tified to within TBD TBD
Sump minimum
Speed variation at constant load TBD Sump maximum TBD

Maximum engine operating angles

-front up, front down, right side TBD

Cooling system or left side

Total coolant capacity Lubricating oil pressure

-with radiator TBD -Relief valve opens TBD


-without radiator TBD - at maximum no-load speed TBD
Maximum top tank temp TBD Oil consumption at full load

Thermostat operation range TBD as a % of fuel consumption


TBD
Radiator face area TBD
Rows and material TBD
Pressure cap setting Electrical system
TBD
Fan diameter Type Negative ground
TBD
Drive ratio Alternator voltage 24 volts
16.3: 1
Number of blades Alternator output 70 amps
TBD
Star ter motor voltage 24 volts

Star ter motor power TBD

Fuel system

Injection system Direct

Fuel injection pump TBD General installation Prime power

Combustion air flow TBD


Fuel atomiser TBD
TBD Exhaust gas temp TBD
Nozzel opening pressure
ECM Exhaust gas flow, wet TBD
Fuel lift pump type
TBD Engine coolant flow TBD
- flow/hour
TBD Cooling fan air flow TBD
- pressure

Maximum suction head:

-1500 rev/min TBD


Your professional power assistant

Alternator Specification
Emergency voltage curve

Sudden increase warp


Alternator Sudden voltage warp Sudden decrease warp

Number of phase 3 520

Power factor (Cos Phi) 0.8 464

+1%
Poles 4 408 +1%
380
380
-1%
Winding Connections (standard) Star-serie 352

Terminals 12 296

Insulation type H class 240


0 1 2 3 4 5 6 7 8 9 10 11 12

Winding Pitch 2/3 δu % : - 1 8 . 1 8


δu % : 8.89
Benchmark phase: A
Benchmark phase: A
Min. voltage: 310.9V Recovery time:
Recovery time:
1 . 95 s
.12s
0. s
Max. voltage: 413.8V

IP rating IP23

Excitation system Self-excited

Bearing Single bearing Emergency frequency curve


Coating Vacuum impregnation Sudden voltage warp
Sudden increase warp
Sudden decrease warp
70
Voltage regulator A.V.R

Couping Flexible disc 62

54 +1%
50
-1%
+1%
50
-1%
46

38

30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s

Options

Engine Alternator Generator Sets Fuel System

· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD

Canopy Lub oil system Cooling System Control Panel

· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay
Your professional power assistant

Control Panel

Configuration Benefits

· Emergency stop button · Less wiring and components


· Integrated solution
· Protection MCB
· Less engineering and programming
· Battery charger · User friendly set-up and button layout
· Integrated aviation plug · Module can be configured to suit individual applications
· ATS connection · PC software for simplified configuration
· Digital control module · Wide range of communication capabilities

Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· 3 phase generator set monitoring
· Storage temp: -30 ˚C to + 80 ˚C
· S uppor t of engines equipped with electronic control
· Operating humidity: 95% w/o condensation
unit
· Vibration 5-25Hz, ±1.6 mm
· Comprehensive diagnostic message
5-1 00 Hz , a=4g
· A utomatic or manual star t / stop of the gensets
· Shocks: a= 500m/s²
· Push buttons for simple control , lamp test
· G raphic back - lit LCD display
Options
· Parameters adjustable via keyboard or PC
· Mains measurements ( 50HZ / 60HZ ) · Ethernet interface (Remote monitoring and control)
· Generator measurements ( 50HZ / 60HZ ) · GSM modem/wireless internet (Remote monitoring and control)
· Comprehensive shutdown or warning on fault condition · RS232-RS485 Dual por t interface
· 3 phase Generator protections · Synchronizing control panel
· Distribution board with sockets kit and power busbar
- Over -/ under voltage
· Battery trickle charge ammeter
- Over -/ under frequency
· Ear th leakage protection
- Current / voltage asymmetry · Ear th fault protection
- Over current / overload · Low fuel level alarm
· 3 phase AMF function · Low fuel level shutdown
- Over-/under frequency · High fuel level alarm
- Over-/under voltage · Fuel transfer system control
- Voltage asymmetry · Low coolant level shutdown
· Configurable analog inputs · High lube oil temp shutdown
· Battery voltage, engine speed (pick-up) measurement · Overload via alarm switch on breaker
· Configurable programmable binary inputs and outputs · Engine coolant heater controls
· Warm-up and cooling functions · Control panel heater
· Generator C.B. and Mains C.B. control with feedback · S peed adjust switch
and return timer
· Oil temp displayed on LCD screen
· RS232 interface
· Additional 8 inputs and outputs
· Modem communication suppor t
· Hours counter
· Sealed to Ip65
· Event log
Publication No. GYH0517N, ISSUE 1 @ AGG

Distributed by

AGG UK | AGG China | AGG USA | AGG UAE


info@aggpower.com | www.aggpower.com

All information in the document is substantially correct a the time of printing


but may be subsequently altered by the company.

You might also like