Model: P38D6

Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model P38D6
Power (kVA) 35 38
Engine brand Perkins
Power (kW) 28 30
Engine model 1103A-33G
Rated speed ( r.p.m) 1800
Speed control type Mechanical
Standard voltage (V) 400/230V
Phase 3
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage 12V
AU VE
RI
BURE

ISO 9001
TA S

BUREAU VERITAS
Certification
182 8
Frequency 60HZ
Engine speed (RPM) 1800
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 9.5
·2006/42/EC Machinery safety. Fuel 8.6
100% prime power
·2006/95/EC Low voltage Consumption
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 75% prime power 6.6
12601 : 2010 (L/H)
50% prime power 4.9
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
Standard reference Conditions
power sequence, which may be run for an unlimited number of hours per year, between
Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30%
stated maintenance intervals. The permissible average power output during at 24 hours
relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
period shall not exceed 80% of the prime power. 10% overload available for governing
conforming to BS 2869: 1998, Class A2
purposes only.

(2) ESP (Standby Power):


L L
According to ISO 8528-1, It is defined as the maximum power available, under the
agreed operating conditions, for which the generating set is capable of delivering for up
to 500 hours of operation per year (of which no more than 300 hours for continuative
H H
use) with the maintenance intervals and procedures being carried out as prescribed by
W W
the manufacturers. No overload capability is available.

Powers ESP PRP Standby Dimension and Weight


Voltage (V) KVA KW KVA KW Amps Dimension Open Silent

480/277 38 30 35 28 45.7 Length (L) 1920mm 2400mm

35 Width (W) 750mm 1100mm


440/254 38 30 28 49.9
Height (H) 1410mm 1632mm
400/230 38 30 35 28 54.8
Net Weight REQ 1450
380/220 38 30 35 28 57.7
Fuel Tank (L) Option 110
220/127 38 30 35 28 99.7 Note: This parameters allows for some acceptable deviations.

www.aggpower.com
Stay Focused , Always Reliable

Engine Specification: 1103A-33G

Basic technical data Induction system

No. of cylinders 3 Clean filter 3.0kpa

Cylinder arrangement Ver tical in-line Dir ty filter 6.5kpa

Cycle 4 stroke Air filter type Dry

Induction system Naturally aspirated

Compression ratio 19.25:1

Bore 105mm

Stroke 127mm Lubrication system


Displacement 3.3 L Total lub capacity 8.3L
All ratings cer tified to within TBD Sump minimum 6.2L
Speed variation at constant load ±0. 75% Sump maximum 7.8L
Maximum engine operating angles

-front up, front down, right side

Cooling system or left side


25℃
Total coolant capacity Lubricating oil pressure

-with radiator 10.2L -Relief valve opens 415-470 kPa


-without radiator 4.4L - at maximum no-load speed 276-414 kPa
Maximum top tank temp 110℃ Oil consumption at full load

Thermostat operation range 82-93℃ as a % of fuel consumption


0.15%
Radiator face area 0.276 m²
Rows and material Single rows aluminium
Pressure cap setting Electrical system
107 kPa
Fan diameter Type Negative ground
457 mm
Drive ratio Alternator voltage 12 volts
0.85 : 1
Number of blades Alternator output 65 amps
7
Star ter motor voltage 12 volts

Star ter motor power 3 KW

Fuel system

Injection system Direct

Fuel injection pump Rotary General installation Prime power

Multi-hole Combustion air flow 2.6 m³/min


Fuel atomiser
29.0 MPa Exhaust gas temp 520°C
Nozzel opening pressure
Mechanical Exhaust gas flow, wet 6.4 m³/min
Fuel lift pump type
120-150 l/h Engine coolant flow 151 I/min
- flow/hour
30-75 kPa Cooling fan air flow 70.0 m³/min
- pressure

Maximum suction head:

-1500 rev/min 17kPa

www.aggpower.com
Stay Focused , Always Reliable

Alternator Specification
Emergency voltage curve

Sudden increase warp


Alternator Sudden voltage warp Sudden decrease warp
520
Number of phase 3

Power factor (Cos Phi) 0.8 464

+1%
Poles 4 408 +1%
380
380
-1%
Winding Connections (standard) Star-serie 352

Terminals 12 296

Insulation type H class 240


0 1 2 3 4 5 6 7 8 9 10 11 12
δu%: -18.18 1.95s
Winding Pitch 2/3 δu%: 8.89
Benchmark phase: A
Benchmark phase: A
Min. voltage: 310.9V Recovery time:
Recovery time: 0..12ss
Max. voltage: 413.8V

IP rating IP23

Excitation system Self-excited

Bearing Single bearing Emergency frequency curve


Coating Vacuum impregnation Sudden increase warp
Sudden voltage warp Sudden decrease warp
70
Voltage regulator A.V.R

Couping Flexible disc 62

54 +1%
50
-1%
+1%
50
-1%
46

38

30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s

Options

Engine Alternator Generator Sets Fuel System

· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD

Canopy Lub oil system Cooling System Control Panel

· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay

www.aggpower.com
Stay Focused , Always Reliable

Control Panel

Configuration Benefits

· Emergency stop button · Less wiring and components


· Integrated solution
· Protection MCB
· Less engineering and programming
· Battery charger · User friendly set-up and button layout
· Integrated aviation plug · Module can be configured to suit individual applications
· ATS connection · PC software for simplified configuration
· Digital control module · Wide range of communication capabilities

Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· 3 phase generator set monitoring
· Storage temp: -30 ˚C to + 80 ˚C
· S uppor t of engines equipped with electronic control
· Operating humidity: 95% w/o condensation
unit
· Vibration: 5-25Hz, ±1.6 mm
· Comprehensive diagnostic message
5-1 00 Hz , a= 4g
· A utomatic or manual star t / stop of the gensets
· Shocks: a= 500m/s²
· Push buttons for simple control , lamp test
· G raphic back - lit LCD display
Options
· Parameters adjustable via keyboard or PC
· Mains measurements ( 50HZ / 60HZ ) · Ethernet interface (Remote monitoring and control)
· Generator measurements ( 50HZ / 60HZ ) · GSM modem/wireless internet (Remote monitoring and control)
· Comprehensive shutdown or warning on fault condition · RS232-RS485 Dual por t interface
· 3 phase Generator protections · Synchronizing control panel
· Distribution board with sockets kit and power busbar
- Over - / under voltage
· Battery trickle charge ammeter
- Over - / under frequency
· Ear th leakage protection
- Current / voltage asymmetry · Ear th fault protection
- Over current / overload · Low fuel level alarm
· 3 phase AMF function · Low fuel level shutdown
- Over-/under frequency · High fuel level alarm
- Over-/under voltage · Fuel transfer system control
- Voltage asymmetry · Low coolant level shutdown
· Configurable analog inputs · High lube oil temp shutdown
· Battery voltage, engine speed (pick-up) measurement · Overload via alarm switch on breaker
· Configurable programmable binary inputs and outputs · Engine coolant heater controls
· Warm-up and cooling functions · Control panel heater
· Generator C.B. and Mains C.B. control with feedback · S peed adjust switch
and return timer
· Oil temp displayed on LCD screen
· RS232 interface
· Additional 8 inputs and outputs
· Modem communication suppor t
· Hours counter
· Sealed to Ip65
· Event log
Publication No. GYH0517N, ISSUE 1 @ AGG

Distributed by

AGG UK | AGG China | AGG USA | AGG UAE


info@aggpower.com | www.aggpower.com

All information in the document is substantially correct a the time of printing


but may be subsequently altered by the company.

You might also like