WRWTP water demand is Higher filtration rate could OHA required a Filtration
increasing. The goal of the save the City $5-10M by not Pilot Study to evaluate
project is to increase plant having to build additional filters. filtered water performance
capacity without constructing at higher flow rates, prior to
additional major process approving the higher plant
infrastructure. capacity.
3
Project Introduction
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
PNWS
Willamette River
Water Treatment Plant
4
WRWTP Process Flow Diagram
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Calcium Thiosulfate
Sodium Hypochlorite
Microsand
Sodium Hypochlorite
Polymer
Caustic Soda
Polymer
Caustic Soda
Alum
Alum
O3
O3
To Distribution
FM
Initial Ballasted
Ozone
Mix Flocculation Filters Filter
Control Clearwell/High Service
Raw Water Recycle Pumps Weir Pump Station
Pump Station
Filtration
Filter Control Weir
Ozonation
Ozone Generation
• Expansion from 15 mgd to 20 mgd via process uprating • Installing baffles in existing clearwell to increase
• Equipment replacement disinfection capacity
6 • Seismic Retrofits • Electrical upgrades to support up to 30 mgd capacity
Raw Water Flow
• Ranges from 3 to 14 MGD
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Initial Ballasted
Ozone
Mix Flocculation
Raw Water
Pump Station
Filtered Water Turbidity
• Turbidity is less than or equal to 0.05 NTU
• Average Filtered Water Turb 0.02 NTU
Filtration Rate & Run Time
• Filtration Rate ranges from 2 to 7 gpm/sf
• Average Filter Run time is 60 hours
7
• Typical UFRV is 14,000 gal/sf
8
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
A Pilot Study must be conducted to Testing occurred over one full year with four
demonstrate filter performance at the higher testing periods, each lasting 4 weeks. Most
loading rate and must simulate worst-case operated at 12 gpm/sf, even during the winter
raw water quality conditions. when demand is typically the lowest.
Filtered water turbidity optimization goals Influent and individual filter effluent turbidity
must be met. were monitored and evaluated.
Giardia and cryptosporidium surrogate Influent and individual filter effluent particle
removal rates must be monitored and counts were monitored and compared against
evaluated in the pilot study. the raw water particle counts
If running at a higher filter loading rate, the Ballasted Flocculation was operated with
pathogen reduction must not be compromised a single train to simulate the doubling of
for the other major unit processes, such as flow through the process.
the Actiflo clarifier, ozone contactor, and
disinfection with chlorine in the clearwell.
9
Testing Schedule
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Dates Aug – Sept 2020 Nov – Dec 2020 Feb – March 2021 Apr – May 2021
Actiflo® Trains Online Single Train Single Train Single Train Single Train
10
Testing Schedule
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Dates Aug – Sept 2020 Nov – Dec 2020 Feb – March 2021 Apr – May 2021
Intermediate
Plant Production
3-10 & up
Raw Water Turbidity to 50 NTU
Actiflo® Trains Online Single Train Single Train Single Train Single Train
11
Testing Schedule
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Dates Aug – Sept 2020 Nov – Dec 2020 Feb – March 2021 Apr – May 2021
Lowest
Plant Production
Actiflo® Trains Online Single Train Single Train Single Train Single Train
12
Total Number of Filter Runs: 150
Testing Schedule
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Dates Aug – Sept 2020 Nov – Dec 2020 Feb – March 2021 Apr – May 2021
Actiflo® Trains Online Single Train Single Train Single Train Single Train
13
Filtration Pilot Testing, Success Criteria
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Parameters
Unit Filter Run • UFRV can be used to determine how efficiently a granular media filter performs.
Volume
• UFRV was calculated for each filter run to confirm filter efficiency does not
decrease with increased filtration rates.
• Log removal of particle counts was calculated for each bin size, particularly
focused on particle bin sizes similar to Giardia and Crypto size.
15
16
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Most filter runs were operated at 12 gpm/sf to demonstrate performance at the hydraulic
capacity of the full-scale filters. However, filtration rate ranged from 8 – 16 gpm/sf due to
excellent performance.
17
Full-Scale and Pilot Filter Design
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
PILOT EFFLUENT
AND BW WATER PILOT WATER
TO WW/EQ BASIN SUPPLY
LOCATION OF
FILTRATION PILOT
19
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Differential Pressure
Feed Pump,
Flow Controlled
6-ft GAC
1-ft Sand
Chemical Injection
Assembly, Manual
20
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Backwashing Procedure:
1. Air only for 1 minute
2. Air plus water at a low-rate for 1 minute
3. Water at a high-rate only for 4 minutes
21
4. Water only at a low-rate for 2 minutes
Filtration Pilot Operational
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Conditions
1. Backwash Pilot Filters
2. Filter to Waste (15 minutes)
3. Return Filter to Service when filtered water turbidity is ≤0.1 NTU
4. Run filters at a pre-determined filtration rate
5. Terminate filter run when:
a) Filtered water turbidity ≥ 0.1 NTU (turbidity breakthrough)
b) Differential pressure > 144 inch (terminal headloss)
c) Operators can increase number of filter runs (time)
24
Example Filter Run: TP1 Summer 2020
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
26
Filtration Pilot Study Results,
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
27
Filtration Pilot Study Results,
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Results, Impact of
Seasonal RWQ
• Filtered water turbidity goals were met
during all testing periods at 12 gpm/sf
based on 83 filter runs.
Results, Headloss
• Filter runs were terminated if terminal
headloss was reached.
30
31
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Filtration Rate Filtered Water Filter Run Time UFRV, gal/sf Success
Turbidity Criteria Met?
WRWTP Full-Scale 0.02 NTU 60 hrs 18,000 gal/sf -
Filters, 4-6 gpm/sf
Confirms that the higher loading rates did not compromise filtered water turbidity or UFRV
32
Uprated Design Criteria
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Next Steps: OHA requests full-scale monitoring for ~1year to confirm the full-scale
plant is operating similar to the pilot results
33
Filtration Pilot Takeaways
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Pilot Study results showed Successfully testing filters at Higher filtration rate was
excellent filter performance > 10 gpm/sf built operational approved by OHA, saving the
up to 12 gpm/sf. Filtration rates confidence the filters can City $5-10M by not having to
up to 16 gpm/sf were tested. operate at higher rates across a build additional filters.
range of water quality
conditions.
34
35
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Acknowledgements
RESEARCH
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Questions?
Mike Nacrelli
mnacrelli@ci.wilsonville.or.us
Katerina Messologitis
Katerina.Messologitis@stantec.com
36
37
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
38
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Filtration Pilot Study
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
Results, UFRV
• UFRV was used to calculate filter efficiency.
Filter efficiency was 99% at 12 gpm/sf
with an average UFRV of 25,000 gal/sf.
Typical WRWTP UFRV
• UFRV typically met / exceeded the
(98%current
Filter Efficiency)
WRWTP UFRV for pilot runs operated at 12
gpm/sf. Minimum Target UFRV
(95% Filter Efficiency)
• Seasonal raw water quality slightly impacted
UFRV during TP3, however did not fall
below the 5,000 gal/sf minimum goal.
39
Filtration Pilot Study Results,
WRWTP 20MGD EXPANSION PROJECT, FILTER UPRATING STUDY
2) Raw water particle count for the 5 and 15 µm range was calculated
* WRWTP is rated as a conventional as the sum of particles in the 5 to 10 µm and 10 to 15 µm bin sizes.
treatment plant, therefore receiving
2.5-log removal credit for Giardia.
40