Professional Documents
Culture Documents
Abstract—High voltage cable-wound generator, the stator high voltage on the stability of power grid with dynamic
winding of which is made of high voltage cables, is a new type of simulation, reference [9] introduces the short-circuit tests of
generator. And its stator structure is different from that of high voltage generator, reference [10] analyzes the steady-state
classical generator, so the designment of the primary dimension and fault of double winding high voltage generator, reference
of high voltage cable-wound generator is not same as [11] establishes the model of the internal single phase to
conventional generator too. In this paper, the primary dimension ground fault of high voltage generator. Reference [12] presents
determining method for High voltage cable-wound generator is the process of the development of high voltage generator
investigated based on the primary dimension determining prototype though, and primary dimensions, results of
method of conventional generator, and the specific determining
electromagnetic calculation of prototype are also presented, the
process of primary dimensions of high voltage generator is
determining process of primary dimension is not analyzed at
explained with an example.
length, therefore it is necessary to study the method of
Keywords-high voltage cable-wound generator; electric determine the primary dimensions for high voltage
machine design; primary dimension cable-wound generator systematically.
In this paper, primary dimensions determining method for
I. INTRODUCTION
high voltage cable-wound generator is investigated according
In February 1998, ABB corporation declared that a high to the mechanical and electric characteristic of high voltage
voltage generator (Powerformer) has been developed cables, and the determining methods of stator inner diameter,
successfully, which could directly be connected to the power stator external diameter and stator core length are presented,
network, and it was installed in Foundation Porjus centre the specific determining process of primary dimensions is
hydro-power [1] in the north of Sweden. Subsequently, the explained with an example.
research institutions of China began to study of high voltage
cable-wound generator in 2001 year and it was called energy II. METHOD OF THE PRIMARY DIMENSIONS OF
converter, high voltage generator or power generator[2][3]. CONVENTIONAL GENERATOR
The stator windings of high voltage generator is made of The generator primary dimensions include the outer
high-voltage cross-linked polyethylene (XLPE) cable, the diameter of stator core D1 , the inner diameter of stator core
section of which is circular and the electrical field distribution Di1 and the core length lef . For multi-pole generator, the
around it is uniform. So the output voltage can achieve grid
voltage level, which makes the high voltage generator can be general method is to determine the polar distance firstly, and
linked with the transmission grid directly [4] [5]. Cables are then calculate the diameter of the stator core with equation (1).
used as stator winding of high voltage generator and the slots 2 pτ
are composed of circles interact linked. The stator structure of Di1 = (1)
high voltage generator is different from conventional generator π
greatly, and the determining method of primary dimensions for where, p is the number of pole pairs, and τ is the polar
conventional generator is not suitable for high voltage distance (cm).
generator. Now, there are many papers studying on high A. Choice of polar distance τ
voltage generator at home and abroad, for example, reference
[6] investigates the stability of high voltage from the heating of According to difference cases, the following methods are
stator winding, it is found that the time constant of high voltage used to select polar distance initially:
generator is longer than that of conventional and the over-load 1) According to the curve by manufacturing practice and
capacity of the winding heat load is larger than conventional
the empirical formula
generator, reference [7] calculates and analyzes the leak
reactance of high voltage, reference [8] studies the impact of S
τ = K1 N (2)
Project Supported by National Science Foundation of China (50577012) and 2p
Innovation Found Project for Graduate student of Heilongjiang Province
(YJSCX2009-030HLJ) where, D1 is coefficient, and D1 = 9.0 − 12.5 (medium
Ge Baojun was born in 1960.He received PH. D. degree from Harbin Institute of
Technology, Heilongjiang Province, China. Dr. GE is now a Professor of Harbin capacity) or 8.3-10.7(the maximum is taken for large capacity
University of Science and Technology. He mainly studies on basis theory and and high speed).
application technology of large electromechanical energy conversion device
DONG Chuanyou was born in 1981. He is a postgraduate student now and studies
on the electromagnetic calculation of large synchronous generator.
R2 = Rs 2 + 0.75 (14)
3.6/6 1*25 2.5
R1 = Rs1 + 0.75 (15)
6/10 1*25 3.4
where, R1 , R2 are diameters of two kinds of cables, as
shown in Fig. 1. 8.7/15 1*25 4.5
D n C
i N
Yoke flux density is generally between 1.0~1.1T, and the
height of yoke should be guaranteed a certain value in order to 1000
= 2
ensure adjustment of the stator core. Therefore, the outer 0.96 × 1000 × 3.3
diameter of high voltage generator stator core can be = 328(mm)
determined by the following formula: where C = 3.3
D1 = Di + 2( H s + H j ) (18) D. Determination of the High voltage cable-wound generator
stator outer diameter
IV. EXAMPLE
According to empirical data, the stator standard diameter of
A High voltage cable-wound generator with 6 poles, rated High voltage cable-wound generator with 6 poles, rated voltage
voltage of 10.5kV and rated capacity of 750kW is taken for an of 10.5kV and rated capacity of 750kW is D1 =118cm.
example, and the primary dimensions of High voltage
cable-wound generator is determined according to the above Because of its size is larger than the classical generator stator
method. size, the stator outer diameter cannot be chosen standard size
but next following frame size, which D1 =143cm.
A. Selection of cable dimensions
The cable insulation level is analyzed according to the cable V. CONCLUSIONS
voltage test and breakdown test. The cable dimensions • Cables are used in High voltage cable-wound generator
parameter is listed in the table. 1. as its stator windings. Stator inner diameter of high
The 3.6/6kV cable can be used in this High voltage voltage cable-wound generator can be designed bigger
cable-wound generator according to the Tab.1 and previous than that of conventional generator with the same
High voltage cable-wound generator prototype cable winding capacity because of restrictions of cable bend diameter,
design experience, of the High voltage cable-wound generator and the length of stator core is shorter of high voltage
a. The wire cross-sectional area of this specification winding is generator than that of conventional generator.
25mm 2,its insulation thickness is 2.5mm. • The maximum bend radius of cables must be remarked
in the determination of stator inner diameter according
to polar distance, it is because that cables are used in
high voltage cable-wound generator as its stator
windings.
• The bigger number stator frame is chosen in the
process of determination of stator external diameter for
high voltage cable-wound generator because of low of
the coil space factor and big of stator dimensions of the
high voltage generator.
REFERENCE
[1] Mats, Leijon, “PowerformerTM ——A radically new rotating machine”,
ABB Review, 1998, no. 2, pp. 21-26.
[2] Ge Baojun, Zhang Dakui, Liang Yanping, “Powerformer and Its Recent
Development”. Transactions of China Electrotechnical Society, 2005,
vol. 20, no.1, pp. 26–30 (In Chinese).
[3] Ge Baojun, Liang Yanping, Zhou Chuiyou, Song Fuchuan, Wang
Zhimin, Li Fahai. “Powerformer——a Nascent Electric Power
Generation Equipment for the 21st Century”. Automation of Electric
Power Systems, 2004, vol. 28, no. 7, pp. 1–4 (In Chinese).
[4] Dettmer R, “The heart of a new machine [Powerformer, cable-wound
stator machine]”, IEE Review, 1998, vol. 44, no. 6, pp. 255-258.
[5] Metwally, I A. Radwan, R M. Abou-Elyazied, A M, “Powerformers: a
breakthrough of high-voltage power generators”, IEEE Potentials, 2008,
vol. 27, no. 3, pp. 37-44
[6] Lindahl, S. “Improved control of field current heating for voltage
stability machine design-PowerformerTM”. Power Engineering Society
Winter Meeting, Columbus, USA, Jan, 2001, vol. 1, pp. 209-214.
[7] GE Baojun, ZHANG Dakui, LIANG Yanping, et al. “Analysis and
Calculation of Stator Leakage Reactance of Powerformer”. Power
System Technology, 2005, vol. 29, no. 3, pp. 15-22 (In Chinese).
[8] Aumuller, C.A. Saha, T.K. “Investigating the impact of Powerformer on
voltage stability by dynamic simulation”. IEEE Transactions on Power
System, 2003, vol. 18, no. 3, pp. 1142-1148.
[9] STEFAN G Johansson, BERTIL Larsson. “Short-Circuit Tests on a
High-Voltage, Cable-Wound Hydropower Generator”. IEEE
Transactions on Energy Conversion, 2004, vol. 19, no. 1, pp. 28-33.
[10] MARGUERITE Touma-Holmberg, KAILASH Srivastava. “Double
Winding, High-Voltage Cable Wound Generator: Steady-State and Fault
Analysis”. IEEE Transaction on Energy Conversion, 2004, vol. 19, no. 2,
pp. 245-250.
[11] SU Guoxia, GE Baojun, TAO Dajun, et al. “Modeling and Analysis of
Internal Single Phase to Ground Fault in Powerformer”. Electric
Machines and Control, 2007, vol. 11, no. 6, pp. 584-588 (In Chinese).
[12] Ge Baojun, Wang, Xiaowen, Tao Dajun, et. al, “Development of
Powerformer prototype”, Electric Machnies and Control, vol. 12. no. 4,
pp. 370-373. (In Chinese).
[13] Bai Yannian. Design and calculation of hydraulic generator. Beijing:
China Machine PRESS, 1982 (In Chinese).
[14] Chen Shikun. Electric machine design. Beijing:China Machine Press,
2002 (In Chinese).
[15] Yang Xilai. “The Electromagnetic Design and Parameter Calculation of
Powerformer by Fem”. Harbin University of Science and Technology,
2005, pp. 9–13 (In Chinese).
[16] MA Wenzhong, LI Yaohua, KONG Li. “Research on the Characteristic
of the Winding Cable in High Voltage Motor”. High Voltage
Engineering, 2006, vol. 32, no. 3. pp. 24 (In Chinese).