You are on page 1of 2

Vision Revo TP100

LFP-512V50AH

Overview Rack Specification


Vision Technology provides safe LiFePO4 battery
Voltage Range(V) 448~584
solutions for UPS and Energy storage system. This
battery system serves for UPS and Energy storage Cell 3.2V50Ah
system with perfect compatibility and safe long cycle
life. Series & Parallels 160S1P

Rated Voltage(V) 512


Features
Rated Capacity(Ah) 50
 Can/RS485 Communication output for
monitoring Rated Energy(KWh) 25.6
 Achieve up 32 BMU in cascade communication
Maximum Charge Current(A) 50
 Interal cell balancing ,Passive equalization , the
maximum equalization current up to 300mA Discharge cut-off voltage(V) 448
 High-precision cell voltage and temperature
Charge voltage(V) 560 ~ 584
acquisition:±3mv,±1℃;
 Fan control circuit and interface, realize heat Cycle life(@25℃,1C/1C,100%DOD ) > 2500
dissipation inside the module
Short-circuit Current(A) (< 10ms)   Approx. 5000A

System Dimension(W* D* H) (600*1000*2000 ) mm


Module Preview
Total Weight(Kg) Approx.550

Internal Resistance Fully Charged@ 25℃ ≤100mOhms

Thermal Management Air cooling

Charge 0 ~50℃
Operating temperature
Discharge -20 ~ 65 ℃
Module 51.2V50Ah
Operating humidity 60 ± 25%R.H.

Performance Data Communication CAN/RS485

Time(min) 10 15 30 45 60 Dry Contact Y


Constant
114 93 49.2 32.8 25.1 System parallels ≤15
Power(kw)
Constant
245 200 100 66.7 50 Screen optional
Current(A)

VISION GROUP / www.vision-batt.com -V01


Vision Revo TP100
LFP-512V50AH

Module size Rack

Rack TP100(S)
TP100S-with LCD TP100-withou LCD

Characteristics Curve

Discharge Performance at 25 C harge and Discharge at 25


580 580
0.2C Charge

0.5C
540 540
1.0C
Voltage (V)

Voltage (V)

4.0C
500 500
5.0C

460 460
(448 ) (448 )
Discharge
420 420
0 20 40 60 80 100 120 0 20 40 60 80 100 120
Capacity (%) Capacity (%)
Cycle life with DOD at 25
Temperature effects on capacity at 0.5C 4C discharge and 1C charge
110 110

100 100

90
Capacity (%)

Capacity (%)

90
80 100%DOD 80%DOD 50%DOD 30%DOD
80
70

70 60

60 50
-30 -20 -10 0 10 20 (25) 30 40 50 60 70 0 500 1000 1500 2000 2500 3000 4000 4500
Temperature ( ) Number of cycle (cycles)

VISION GROUP / www.vision-batt.com -V01