Professional Documents
Culture Documents
Oem Transformer Maintenance Recomendation
Oem Transformer Maintenance Recomendation
INSULATION OIL
a. Inspection of Characteristics onece/3 years
1 b. Dissolved Gas in Oil Analysis once/year (base on condition)
INTERNAL PART
ON-LOAD TAP-CHANGER
a. Internal Inspection On condition noted
3
b. Replacement On condition noted
c. Oil Purifier for diverter Switch room On condition noted
DE-ENERGIZED TAP CHANGER
4 every 15 years (recommended)
a. Replacement every 30 years (high recommended)
BUSHING
a. Inspection of Oil Characteristics every 10 years (recommended)
5
b. Replacement every 15 years (recommended)
every 30 years (high recommended)
OIL CONSERVATOR
6 every 15 years (recommended)
a. Replacement of Rubber-bag
every 30 years (high recommended)
VOLTAGE RANGE
150 kV dst….