Modbus extension module

Instruction manual
WP9038ADAM
Modbus extension module p 2/5

Table of Contents
1 Installation.................................................................................................................................................3

2 Communication protocol...........................................................................................................................3

3 Burner configuration..................................................................................................................................4

4 Module connections..................................................................................................................................4

WP9038ADAM www.pelltech.eu
Modbus extension module p 3/5

1 Installation
Modbus extension module connects to burners connector X22 as shown below

WP9038ADAM

485B
485A
AVcc
AGnd

Figure 1 Modbus extension module connection with connector X22

2 Communication protocol

Baud rate - 19200


Parity – None
Data bits - 8
Stop bits - 1
Handshake – None

WP9038ADAM www.pelltech.eu
Modbus extension module p 4/5

3 Burner configuration

To make burner compatible with Modbus extension module, it's modbus interface must be switched
from slave to master. It can be done by changing PAR 87 MODBUS TYPE from 1 to 2.

PAR 86 MODBUS ID also has to match with the modules id (Default is 1).

In master mode, the burner periodically communicates with modbus extension module, asking
sensor/input data and controlling outputs. All of inputs, both analog and digital can be displayed on
burner's graph in Web.

Modbus extension module is supported from version 2.9.18 and upwards.

4 Module connections

Figure 2 Analog input connection to modbus extension module

WP9038ADAM www.pelltech.eu
Modbus extension module p 5/5

Figure 3 Digital input connection to modbus extension module

Figure 4 Digital output connection to modbus extension module

WP9038ADAM www.pelltech.eu