Professional Documents
Culture Documents
Instruction manual
WP9038ADAM
Modbus extension module p 2/5
Table of Contents
1 Installation.................................................................................................................................................3
2 Communication protocol...........................................................................................................................3
3 Burner configuration..................................................................................................................................4
4 Module connections..................................................................................................................................4
WP9038ADAM www.pelltech.eu
Modbus extension module p 3/5
1 Installation
Modbus extension module connects to burners connector X22 as shown below
WP9038ADAM
485B
485A
AVcc
AGnd
2 Communication protocol
WP9038ADAM www.pelltech.eu
Modbus extension module p 4/5
3 Burner configuration
To make burner compatible with Modbus extension module, it's modbus interface must be switched
from slave to master. It can be done by changing PAR 87 MODBUS TYPE from 1 to 2.
PAR 86 MODBUS ID also has to match with the modules id (Default is 1).
In master mode, the burner periodically communicates with modbus extension module, asking
sensor/input data and controlling outputs. All of inputs, both analog and digital can be displayed on
burner's graph in Web.
4 Module connections
WP9038ADAM www.pelltech.eu
Modbus extension module p 5/5
WP9038ADAM www.pelltech.eu