Transformer Vault

Circuit No Load description Lighting outlet Receptacle outlet Power Watts Voltage, Volts Current, ampere/s Ampere Trip No. of Poles Size of Conductor and Ground Wire Size of Conduit
1 ACU 2hp 1 2300 230 10 20 2 2 #5.5-mm2 THHN, E-14mm2 THHN 16mm ⌀PVC
2 Receptacle Outlet 7 1260 230 5.48 15 2 2 #5.5-mm2 THHN, E-14mm2 THHN 16mm ⌀PVC
3 Lighting Outlet( 12-15W T5) EL (2-6W) 12 2 192 230 0.83 15 2 2 #5.5-mm2 THHN, E-14mm2 THHN 16mm ⌀PVC
4 CCTV 50W (DVR & Camera) 1 50 230 0.22 15 2 2 #5.5-mm2 THHN, E-14mm2 THHN 16mm ⌀PVC
5 Spare
Total 12 11 3802 16.53

@Transformer Vault
PB Load Current = Total Load Current
= (PB load current) (0.8) + (0.25) (Highest Rating Motor)
= (16.53) (0.8) + (0.25) (10)
= 15.72 A
Main Circuit Breaker Rating = (TLC) (0.8) +(1.5) (HMR)
= (16.53) (0.8) +(1.5) (HMR)
= 28.22 A
Therefore use:
Breaker: 30 AT
Wires: 5.5 mm2 THHN, E-8 mm2 THHN
Conduit : 16 mm dia. PVC

Schedule of Loads & Design Analysis


SCALE 1:100 MTS.

EP 43