PB: Bank

Location:

Circuit No. Load Description Lighting Outlet Receptacle Outlet Power Voltage, Volts Current, ampere/s Ampere Trip No. of Poles Size of Conductor and Ground Wire Size of Conduit
Watts

1 ACU 0.75hp 1 1587 230 6.9 20 2 2 #3.5-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
2 ACU 0.75hp 1 1587 230 6.9 20 2 2 #3.5-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
3 ACU 1 hp 1 1840 230 8 20 2 2 #3.5-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
4 Receptacle Outlet 13 2340 230 10.17 20 2 2 #3.5-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
5 Receptacle Outlet 11 1980 230 8.61 20 2 2 #3.5-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
6 Receptacle Outlet 5 900 230 3.91 20 2 2 #3.5-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
7 Light (8-18W, 4-12W, 2-7W) EL (4-6W) 14 4 290 230 1.26 15 2 2 #2.0-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
8 Light (14-12W,3-7W) EF (2-35W) EL (1-6W) 9 1 265 230 1.15 15 2 2 #2.0-mm2 THHN, E-8mm2 THHN 16mm ⌀PVC
Spare Spare
Total 23 37 10789 46.91

Design Analysis for Panel Board (Commercial)


@Bank
PB Load Current = Total Load Current
=(PB load current) (0.8) + (0.25) (Highest Rating Motor)
=(46.91) (0.8) + (0.25) (8)
=39.53 A
Main Circuit Breaker Rating = (TLC) (0.8) +(1.5) (HMR)
=(46.91) (0.8) +(1.5) (HMR)
=49.53 A
Therefore use:
Breaker: 60 AT
Wires: 14 mm2 THHN, E-8 mm2 THHN
Conduit: 21 mm dia. PVC

Schedule of Loads & Design Analysis


SCALE 1:100 MTS.