Professional Documents
Culture Documents
(MPE) P14169 Formosa2 Protection V3
(MPE) P14169 Formosa2 Protection V3
settings
P14169
prepared for:
Released by:
Peter Lilje, Ph. D.
Tel.: +49 7071 13879-17
Email.: peter.lilje@moellerpoeller.de
2
P14169 – Wind farm Formosa 2 – Protection settings
Table of contents
1 Introduction .................................................................................................................................. 5
2 69kV Cable strings (CBs 610, 620, 630 and 640) ....................................................................... 7
2.1 Phase overcurrent protection (50/51) ...................................................................................... 7
2.2 Phase-to-ground overcurrent protection (50N/51N) .............................................................. 11
3 69kV Shunt reactors (CBs 910, 920, 930 and 940) .................................................................. 14
3.1 Phase overcurrent protection (50/51) .................................................................................... 14
3.2 Phase-to-ground overcurrent protection (50N/51N) .............................................................. 15
4 69kV Filters (CBs 810, 820) ....................................................................................................... 18
4.1 Phase overcurrent protection (50/51) .................................................................................... 18
4.2 Phase-to-ground overcurrent protection (50N/51N) .............................................................. 19
5 69/25kV Substation auxiliary transformer (CBs 590, 210)...................................................... 20
5.1 Phase overcurrent protection at 69kV (50/51) ....................................................................... 20
5.2 Phase-to-ground overcurrent protection at 69kV (50N/51N) ................................................. 21
5.3 Phase overcurrent protection at 23kV (50/51) ....................................................................... 22
5.4 Phase-to-ground overcurrent protection at 23kV (50N/51N) ................................................. 23
5.5 Transformer differential protection (87T) ............................................................................... 23
6 23/0.40kV Substation LV transformer (CB 220) ....................................................................... 25
6.1 Phase overcurrent protection at 23kV (50/51) ....................................................................... 25
6.2 Phase-to-ground overcurrent protection at 23kV (50N/51N) ................................................. 27
7 69kV Busbars .............................................................................................................................. 28
7.1 Busbar differential protection ................................................................................................. 28
7.2 69kV Bus coupler (CB 600) ................................................................................................... 31
7.2.1 Phase overcurrent protection at 69kV (50/51) ............................................................... 31
7.2.2 Phase-to-ground overcurrent protection at 69kV (50N/51N) ......................................... 31
8 161/69kV Wind farm transformers (CBs 710/20/30 and 1650/60/70) ...................................... 32
8.1 Transformer differential protection (87T) ............................................................................... 32
8.2 Phase overcurrent protection at 69kV (50/51) ....................................................................... 34
8.3 Phase-to-ground overcurrent protection at 69kV (50N/51N) ................................................. 36
8.4 Phase overcurrent protection at 161kV (50/51) ..................................................................... 38
8.5 Phase-to-ground overcurrent protection at 161kV (50N/51N) ............................................... 39
8.6 Transformer neutral overcurrent protection (51Z) ................................................................. 40
8.7 Voltage protection (27, 59, 59Vo) .......................................................................................... 42
9 161kV Busbars............................................................................................................................ 43
9.1 Busbar differential protection ................................................................................................. 43
10 161kV Export cables .................................................................................................................. 45
10.1 Phase directional overcurrent protection at F2-substation (67) ............................................ 45
3
P14169 – Wind farm Formosa 2 – Protection settings
4
P14169 – Wind farm Formosa 2 – Protection settings
1 Introduction
The company Fortune Electric Co., Ltd. (Fortune Electric) is planning the construction of the onshore
parts of the nearshore wind farm Formosa 2 in Taiwan, together with all required power system
studies. The wind farm will have 47 wind turbine generators of the type Siemens SG 8.0-167 DD;
60Hz. It will be connected to the 161kV transmission system. The wind farm voltage will be 69kV.
This document presents the proposed settings of the electrical protection relays. The protection
functions have been provided by Fortune Electric [1]. The settings are stated in terms of primary
voltages and currents. The values that must be entered into the relay may be secondary, % or per unit
values. These may depend on the specific version of the relay to be installed and must be derived by
the protection commissioning engineer from the primary values.
All current transformers have rated secondary currents of 5A [2]. It is recommended to ensure that the
burdens of all relay circuits do not lead to excessive saturation.
Figure 1 shows the topology of the onshore electrical system, including the circuit breakers (CBs) that
were considered in this study (numbers in red).
The symbol Apri is used throughout this document to mean Amperes on the primary side of the current
transformer.
5
P14169 – Wind farm Formosa 2 – Protection settings
Figure 1: Topology of onshore wind farm power system incl. circuit breaker numbers
6
P14169 – Wind farm Formosa 2 – Protection settings
The pickup current is set to approximately 120% of the maximum load current, which is achieved
when all WTGs are operating at 8.4MW and 1.08p.u. voltage. The current contribution from the WTGs
will be within the 110% for their rated currents during fault conditions (944A for 12 WTGs).
The protection acts as a backup the WTG transformer protection. It is noted that this backup function
has a limitation, because 2-ph faults on the secondary side of the last WTG in a string could lead to
faults currents in the order of the load currents i.e., they would not cause the overcurrent protection in
the CBs 610, 620, 630 or 640 to operate.
At currents above 150% of the instantaneous phase overcurrent protection of the WTGs, the tripping
time is reduced to 150ms.
Faults that lead to such fault currents that can only occur for faults in the 69kV cables and not in any
WTG transformer, are cleared instantaneously.
A negative-sequence definite-time overcurrent function is set to back up the protection on the HV side
of the WTG transformers in the event of unbalanced faults in the WTG transformers, leading to fault
currents that are not detected by the normal phase overcurrent protection. It is noted that the WTGs
control their negative sequence currents to zero during fault conditions. Table 4 shows that the
negative phase sequence overcurrent protection is slower than the phase overcurrent protection,
which ensures that the string is not disconnected prior to the WTG protection having had time to clear
WTG faults. The negative phase sequence protection also provides a back-up to earth faults on the
690V side of the WTG transformers.
Description Setting
Definite time overcurrent, I> (7SR45) 102Apri
Time delay, I> (7SR45) 190ms
Instantaneous overcurrent, I>> (7SR45) 1443Apri
Definite time overcurrent, I> (7SJ82) 98Apri
Time delay, I> (7SJ82) 190ms
Instantaneous overcurrent, I>> (7SJ82) 1393Apri
Harmonic blocking Enabled
7
P14169 – Wind farm Formosa 2 – Protection settings
Table 2: Rated, operating and sub-transient fault currents at CBs 610, 620, 630 and 640
8
P14169 – Wind farm Formosa 2 – Protection settings
Table 3: Phase overcurrent protection at CBs 610, 620, 630 and 640 (7SJ85)
Description Setting
610 620 630 640
IDMT characteristic (IEC) Standard Standard Standard Standard
inverse inverse inverse inverse
IDMT Current pick-up 1200 Apri 1200 Apri 1200 Apri 1200 Apri
IDMT time multiplier 0.50 0.50 0.50 0.50
Stage 1-definite time overcurrent, I> 1992 Apri 1992 Apri 1992 Apri 1992 Apri
Stage 1-time delay, I> 200ms 200ms 200ms 200ms
Instantaneous overcurrent, I>> 21004 Apri 21004 Apri 21004 Apri 21004 Apri
Negative sequence, Stage 1-definite time 180 Apri 180 Apri 180 Apri 180 Apri
overcurrent, I2>
Negative sequence, Stage 1-time delay, I2> 500ms 500ms 500ms 500ms
Harmonic blocking (both +ve and -ve Enabled Enabled Enabled Enabled
sequence)
Figure 2: Phase overcurrent protection at 69kV CBs 610, 620, 630 and 640 and cable capabilities
9
P14169 – Wind farm Formosa 2 – Protection settings
Table 4: Calculated operating times for phase overcurrent and negative sequence overcurrent
protection
Description
Phase Operating Negative Operating
current time sequence time
current
(Apri) (s) (s)
(Apri)
Minimum 2-ph short-circuit current at most 3801 0.20 2195 0.50
remote WTG (69kV), with fault impedance 0%
of WTG transformer impedance, string interlink
closed, one 161/69kV wind farm transformers
in service, one 161kV cable in service
Minimum 2-ph short-circuit current at most 1121 None 647 0.50
remote WTG (69kV), with fault impedance 80%
of WTG transformer impedance, string interlink
closed, one 161/69kV wind farm transformers
in service, one 161kV cable in service
Maximum 3-ph short-circuit current at first WTG 16255 0.20 0 None
(69kV), all 161/69kV wind farm transformers in
service, all 161kV cables in service
Minimum short-circuit current for phase-to- 595 None 297 0.50
phase fault at most remote WTG (690V
terminals), string interlink closed, two 161/69kV
wind farm transformers in service, two 161kV
cables in service
Maximum short-circuit current for three-phase 23793 0.00 0 None
fault at terminals of reactor (69kV), three
161/69kV wind farm transformers in service,
two 161kV cables in service
Maximum short-circuit current for phase-to- 19169 0.20 11288 0.50
phase fault at terminals of reactor (69kV), three
161/69kV wind farm transformers in service,
two 161kV cables in service
Maximum 2-ph short-circuit current at terminals 19110 0.20 11288 0.50
of reactor (69kV), three 161/69kV wind farm
transformers in service, two 161kV cables in
service
10
P14169 – Wind farm Formosa 2 – Protection settings
An earth fault current in the offshore network leads to a residual current at all four string CBs in the
substation (610, 620, 630 and 640). Selective protection is achieved using time-grading of time-
dependent overcurrent protection.
The starting current is set to measure RMS residual currents and in accordance with the
recommendation in [4], that for RMS current measurements the setting should not be less than 10% of
the secondary rated current. In this case, a pick-up setting of 15% of the CT rating has been selected.
Table 5 summarises the earth-fault protection settings of the WTG transformers [3] and Figure 3
shows them diagrammatically.
Description Setting
Instantaneous overcurrent, IG>> (7SR45) 24 Apri
Instantaneous overcurrent, IG>> (7SJ82) 12 Apri
Table 6 shows the fault currents through the bays 610-640 for various fault locations and operating
conditions. Both the residual currents (3Io) and the negative-sequence currents (I2) are shown.
Table 6: Sub-transient currents at CBs 610, 620, 630 and 640 for different operating and fault
conditions
11
P14169 – Wind farm Formosa 2 – Protection settings
3Io / I2
Maximum current for earth fault at end of string 386 / 449 / 0 336 / 2604 / 784
D (HV terminal of WTG), string D interlink 0 0 923
closed, three 161/69kV wind farm transformers
in service, strings A-D connected, reactors SR-
1 to 4 disconnected
3Io / I2
Maximum current for earth fault at terminals of 520 / 662 / 0 495 / 3839 / 1156
shunt reactor SR-4, three 161/69kV wind farm 0 0 1396
transformer in service, strings A-D connected,
reactors SR-1 to 4 disconnected
3Io / I2
Minimum current for earth fault at end of string 0/ 0/ 0/ 0/ 0
(LV terminal of WTG), string interlink closed, 200 198 200 198
one 161/69kV wind farm transformer in
service, strings A-D connected
3Io / I2
Table 7: Phase-to-ground overcurrent protection at CBs 610, 620, 630 and 640 (7SJ85)
Description Setting
610 620 630 640
IDMT characteristic (IEC) Standard Standard Standard Standard
inverse inverse inverse inverse
IDMT Current pick-up, 3Io 180 Apri 180 Apri 180 Apri 180 Apri
IDMT time multiplier 0.05 0.05 0.05 0.05
12
P14169 – Wind farm Formosa 2 – Protection settings
Figure 3: Phase-to-ground overcurrent protection, 69kV CBs 610, 620, 630, 640
13
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
910 920 930 940
IDMT characteristic (IEC) Standard Standard Standard Standard
inverse inverse inverse inverse
IDMT Current pick-up 120 Apri 120 Apri 120 Apri 120 Apri
IDMT time multiplier 0.09 0.09 0.09 0.09
Instantaneous overcurrent, I>> 500 Apri 500 Apri 500 Apri 500 Apri
Harmonic blocking Enabled Enabled Enabled Enabled
14
P14169 – Wind farm Formosa 2 – Protection settings
It is recommended to consider installing current transformers in the reactor neutral connections and to
make use of restricted earth fault protection to increase the percentage of the winding that is covered
by the protection. A full differential protection scheme, which would require current transformers in
each phase of the reactor neutrals, is not essential.
The starting current is set to measure RMS currents and respond to the lowest possible current,
subject to the recommendation in [4] that for RMS current measurements the setting should not be
less than 10% of the secondary rated current. This covers approximately 70% of the shunt winding.
Very high currents, which can only occur for faults in the respective shunt reactor, can be cleared
instantaneously.
15
P14169 – Wind farm Formosa 2 – Protection settings
Table 9: Sub-transient currents at selected CBs for different operating and 1ph-ground short-circuit
conditions
Description Current at CB
640 910, 920,
930, 940
Maximum residual current 3Io for fault at terminals of shunt reactor 3453 Apri 282 - 3662
SR-1 Apri
Minimum residual current 3Io for earth fault at end of string D, one 1169 Apri 237 Apri
161/69kV wind farm transformer in service, strings A-D connected
Maximum residual current 3Io for earth fault at end of string D, string 2293 Apri 187 Apri
D interlink closed, three 161/69kV wind farm transformers in service,
strings A-D connected
Table 10 summarises the proposed settings and Figure 5 shows them diagrammatically.
Table 10: Phase-to-ground overcurrent protection at CBs 910, 920, 930 and 940 (7SJ82)
Description Setting
16
P14169 – Wind farm Formosa 2 – Protection settings
Figure 5: Phase-to-ground overcurrent protection, 69kV CBs 910, 920, 930 and 940
17
P14169 – Wind farm Formosa 2 – Protection settings
It is recommended to study the proposed settings of the filter-internal protection, once this is available,
and to ensure appropriate selectivity between the internal protection and the protection described in
this report.
Table 11: Phase overcurrent protection at CBs 810 and 820 (7UT85)
Description Setting
810, 820
IDMT characteristic (IEC) Standard inverse
IDMT Current pick-up 150 Apri
IDMT time multiplier 0.10
18
P14169 – Wind farm Formosa 2 – Protection settings
The pickup current of the relay is set to measure RMS currents and respond to the lowest possible
current, subject to the recommendation in [4] that for RMS current measurements the setting should
not be less than 10% of the secondary rated current. It is assumed that the multi-ratio current
transformer will be set at 300/5A.
Table 12 summarises the proposed settings and Figure 13 shows them diagrammatically.
Table 12: Phase-to-ground overcurrent protection at CBs 810 and 820 (7UT85)
Description Setting
810, 820
Stage 1-definite time overcurrent, 3Io> 30 Apri
Stage 1-time delay, 3Io> 200ms
19
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 14 lists the proposed settings and Figure 7 shows the relay characteristics diagrammatically.
Description Setting
CT ratio 300 / 5
IDMT characteristic (IEC) Standard
inverse
IDMT Current pick-up 75 Apri
IDMT time multiplier 0.20
Instantaneous overcurrent, I>> 699 Apri
Harmonic blocking Enabled
20
P14169 – Wind farm Formosa 2 – Protection settings
Figure 7: Overcurrent protection at 69kV CBs 210, 220, 590 and 710, and capability of 6MVA
substation transformer TR-4
Table 12 summarises the proposed settings and Figure 13 shows them diagrammatically.
Description Setting
590
Stage 1-definite time overcurrent, 3Io> 45 Apri
Stage 1-time delay, 3Io> 150ms
21
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 17 lists the proposed settings and Figure 7 shows the relay characteristics diagrammatically.
Description Setting
CT ratio 200 / 5
IDMT characteristic (IEC) Standard
inverse
IDMT Current pick-up 190 Apri
IDMT time multiplier 0.08
Stage 1-definite time negative-sequence overcurrent, I2> 45 Apri
Stage 1-negative-sequence overcurrent time delay, I2> 500ms
Harmonic blocking Enabled
22
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
• The characteristic of the differential protection relay is shown in Figure 8, where the current
difference is given by Idiff = | I1 + I2 | and the restraint current by Irest. = Max (| I1|, | I2|), with I1
and I2 being the currents on either side of the transformer.
• The star-point of the 25kV-side is solidly grounded, but there is no CT available for measuring
the current in this connection. The relay needs to be set up correctly to eliminate the zero-
sequence current from the measured phase currents in case of external faults.
• The transformer tap position, which is not yet known, should be considered as it can cause a
non-zero current difference during normal operation.
• Current transformer errors can cause a non-zero current difference during normal operation.
Errors up to 10% have been considered below.
The maximum current on the 69kV-side of the transformer, for a fault on 23kV-side, is 723A. Currents
higher than this must, therefore, be due to faults inside the protected zone. Therefore, the setting for I-
diff-unstrained was set to a value greater than 723A / (6000/69/√3A) i.e., greater than 14 p.u. The final
setting takes CT errors into account.
The main parameters of the transformers are as follows:
Table 19: Parameters of wind farm step-up transformers
Parameter Value
Rated power (base for values below) 6MVA
Voltage HV side 69kV
Voltage LV side 22.8kV
Short circuit voltage uk range at nominal tap position 10%
23
P14169 – Wind farm Formosa 2 – Protection settings
The current transformer ratios are 300/5 on both sides of the transformer.
24
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
CT ratio 300 / 5
Neutral point (69kV-side) Grounded
Threshold 20% of rated current
Intersection 1 Irest 67% of rated current
Slope 1 30%
Add-on stabilisation Deactivated
Intersection 2 Irest 250% of rated current
Slope 2 70%
Threshold, I-diff unconstrained 20 x rated current
Harmonic blocking Enabled
Description Current
25
P14169 – Wind farm Formosa 2 – Protection settings
Table 14 lists the proposed settings and Figure 7 shows the relay characteristics diagrammatically.
Description Setting
CT ratio 50 / 5
IDMT characteristic (IEC) Standard
inverse
IDMT Current pick-up 19 Apri
IDMT time multiplier 0.08
Instantaneous overcurrent, I>> 400 Apri
Harmonic blocking Enabled
Figure 9: Overcurrent protection at CB 210, 220 and 590, and capability of 500kVA substation
transformer Trf_Station
26
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
27
P14169 – Wind farm Formosa 2 – Protection settings
7 69kV Busbars
7.1 Busbar differential protection
The busbar differential protection includes two zones, each of which includes one busbar and the bus
coupler.
The settings have been determined using the recommendations provided by Siemens in [6], the main
considerations of which are as follows:
• The characteristic of the differential protection relay is shown in Figure 8, where the current
difference is given by Idiff = | I1 + I2 + …| and the restraint current by Irest. = | I1| + | I2 | + …,
with I1 and I2 etc. being the currents through the individual CBs.
• The rated current must be selected to exceed a tenth of the largest nominal current. In this
case the largest nominal current would be that of the bus coupler, i.e. 2500A. The rated
current could be selected, for example, at 1000A (which exceeds 2500A/10 = 250A).
• The threshold Idiff determines the sensitivity of the protection in the case of low fault currents.
It should be set not higher than 80% of the lowest steady-state fault current and not lower than
130% of the highest operating current of all the feeders.
• The stabilisation factor k improves the stability in case of faults outside of the protected zone
but reduces the sensitivity of the detection of internal faults. Its setting considers measurement
errors of the current transformers. The manual includes a formula to calculate its setting,
based on the burden of the secondary circuit. These can be measured once the construction
has been completed.
• The single-Phase-to-ground short-circuit currents can be lower than the load currents.
Therefore, it is recommended to use the additional sensitive characteristic at low values of
load current. Stability should be ensured by using additional criteria, such as under-voltage.
Such criteria have already been foreseen by Fortune Electric [1].
• The threshold Id for the sensitive characteristic should be set to the lowest fault current with a
20% margin. The sensitive characteristic ends at the setting Is, which should be set to the sum
of the magnitudes of the maximum load currents plus the single-phase to earth fault current
(plus 20% margin).
28
P14169 – Wind farm Formosa 2 – Protection settings
The following table summarises the currents used to determine suitable settings for the busbar
differential protection.
Table 24: Sub-transient currents used to determine setting for 69kV busbar protection
Description Current
Minimum busbar fault current (2-phase fault); one 161kV cable, one 5981 Apri
161/69kV transformer and no 69kV strings in service
Minimum busbar fault current (1-phase fault); one 161kV cable, one 983 Apri
161/69kV transformer and no 69kV strings in service
Current through transformer, operating at 200MVA, 69kV 1673 Apri
The following table shows the proposed settings. The relay settings (in %) depend on the selection of
rated current.
The setting for the stabilisation factor should be reviewed on site using measurements of the CT
burden.
The “area of higher sensitivity” should be activated based on the zero-sequence voltage Uo.
29
P14169 – Wind farm Formosa 2 – Protection settings
The threshold Id of the sensitive characteristic was set to about 50% of the single-phase fault current
with only one transformer in service. The threshold Is was selected to ensure that the area of higher
sensitivity can be activated over the entire operating range. Is was set at 120% of the maximum total
current, being the sum of the maximum individual feeder currents and the earth-fault current.
Description Setting
30
P14169 – Wind farm Formosa 2 – Protection settings
Table 26 provides the proposed settings. These must be confirmed once the short-term capability of
the bus coupler is known.
Description Setting
IDMT characteristic (IEC) Standard inverse
IDMT Current pick-up 2500 Apri
IDMT time multiplier 0.40
Description Setting
IDMT characteristic (IEC) Standard inverse
IDMT Current pick-up, 3Io 250 Apri
IDMT time multiplier 0.05
31
P14169 – Wind farm Formosa 2 – Protection settings
• The characteristic of the differential protection relay is shown in Figure 8, where the current
difference is given by Idiff = | I1 + I2| and the restraint current by Irest. = Max (| I1|, | I2|), with I1
and I2 being the currents on either side of the transformer.
• The transformer tap changer can cause a non-zero current difference during normal operation.
• Current transformer errors can cause a non-zero current difference during normal operation.
Errors up to 10% have been considered.
The maximum current on the 161kV-side of the transformer, for a fault on 69kV-side, is 3600A.
Currents higher than this must, therefore, be due to faults inside the protected zone. Therefore, the
setting for I-diff-unconstrained was set to a value greater than 3500A, approximately 1.5 x 3500 =
5250A.
32
P14169 – Wind farm Formosa 2 – Protection settings
Parameter Value
Rated power (base for values below) (ODAN) 120 MVA
Rated power with forced cooling (ODAF) 200 MVA
Rated current at 200MVA, 0.9 x 161kV 797 A
Voltage HV side 161 kV
Voltage LV side 69 kV
Short circuit voltage uk range at nominal tap position 12 % @120MVA
Copper losses plus auxiliary losses 296 kW
Zero sequence impedance-Short circuit voltage uk0 12 % assumed
No load current 0.1% assumed
No load losses 105 kW
Vector group Dyn1
Additional voltage per tap 1.25 %
Minimum position -8
Maximum position 8
Table 29: Wind farm transformer differential protection at CBs 1650, 1660 and 1670 (7UT85)
Description Setting
It is recommended to activate and set the restricted earth fault protection on the 69kV side of the
transformers.
33
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
34
P14169 – Wind farm Formosa 2 – Protection settings
Table 31: Phase overcurrent protection at CBs 710, 720 and 730 (7SJ85)
Description Setting
Figure 11: Overcurrent protection, 69kV CBs 710, 720 and 730 (wind farm transformers)
35
P14169 – Wind farm Formosa 2 – Protection settings
Figure 12: Negative-sequence overcurrent protection, 69kV CBs 710, 720 and 730 (wind farm
transformers, 69kV)
Table 32 summarises the proposed settings and Figure 13 shows them diagrammatically.
Table 32: Phase-to-ground overcurrent protection at CBs 710, 720 and 730 (7SJ85)
Description Setting
710, 720, 730
IDMT characteristic (IEC) Standard inverse
IDMT Current pick-up 300 Apri
IDMT time multiplier 0.12
36
P14169 – Wind farm Formosa 2 – Protection settings
Figure 13: Phase-to-ground overcurrent protection, 69kV CBs 710, 720 and 730
37
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 34: Phase overcurrent protection at CBs 1650, 1660 and 1670 (7UT85)
Description Setting
38
P14169 – Wind farm Formosa 2 – Protection settings
Figure 14: Overcurrent protection, 161kV CBs 1650, 1660 and 1670 (transformers)
Table 35: Phase-to-ground overcurrent protection at CBs 1650, 1660, 1670 (7UT85)
Description Setting
1650, 1660, 1670
IDMT characteristic (IEC) Very inverse
IDMT Current pick-up, 3Io 300 Apri
IDMT time multiplier 0.05
39
P14169 – Wind farm Formosa 2 – Protection settings
Figure 15: Phase-to-ground overcurrent protection, 161kV CBs 1650 and 1660
Table 35 summarises the proposed settings and the characteristic is shown in Figure 16.
Description Setting
40
P14169 – Wind farm Formosa 2 – Protection settings
41
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
42
P14169 – Wind farm Formosa 2 – Protection settings
9 161kV Busbars
9.1 Busbar differential protection
The busbar differential protection includes two zones, each of which includes one busbar and the bus
coupler.
The settings have been determined using the recommendations provided by Siemens in [6], the main
considerations of which are as follows:
• The characteristic of the differential protection relay is shown in Figure 8, where the current
difference is given by Idiff = | I1 + I2 + …| and the restraint current by Irest. = | I1| + | I2 | + …,
with I1 and I2 etc. being the currents through the individual CBs.
• The rated current must be selected to exceed a tenth of the largest nominal current. In this
case the largest nominal current would be that of an export cable, which is around 1400A. The
rated current could be selected, for example, at 1000A (which exceeds 1400A/10 = 140A).
• The threshold Idiff determines the sensitivity of the protection in the case of low fault currents.
It should be set not higher than 80% of the lowest steady-state fault current and not lower than
130% of the highest operating current of all the feeders.
• The stabilisation factor k improves the stability in case of faults outside of the protected zone
but reduces the sensitivity of the detection of internal faults. Its setting considers measurement
errors of the current transformers. The manual includes a formula to calculate its setting,
based on the burden of the secondary circuit. These can be measured once the construction
has been completed.
• Since the minimum fault current is not in the range of the load current, no additional sensitive
characteristic is foreseen.
The following table summarises the currents used to determine suitable settings for the busbar
differential protection.
Table 38: Currents used to determine setting for 69kV busbar protection
Description Current
The setting for the stabilisation factor should be reviewed on site using measurements of the CT
burden.
43
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
44
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
1610, 1620
Table 41 summarises the settings and Figure 18 shows the characteristics diagrammatically.
Table 41: Phase overcurrent protection at CBs 1610 and 1620 (7SL86)
Description Setting
CT ratio 3000 / 5
Stage 1-definite time overcurrent, directional I> 2000 Apri
Stage 1-time delay, directional I> 0.15s
45
P14169 – Wind farm Formosa 2 – Protection settings
Table 42: Sub-transient currents at CBs 1610 and 1620 for different operating and fault conditions
(7SL86)
Description Current
Minimum current 3Io for single phase to ground short circuit at 161kV busbar 10685 Apri
of F2, both 161kV cables in service
Minimum current 3Io for single phase to ground short circuit at 161kV busbar 18798 Apri
of F2, one 161kV cables in service
46
P14169 – Wind farm Formosa 2 – Protection settings
Description Current
Table 44: Phase overcurrent protection at CBs 1550 and 1560 (7SL86)
Description Setting
CT ratio 3000 / 5
Stage 1-definite time overcurrent, I> 2000 Apri
Stage 1-time delay, I> 700 ms
Stage 2-definite time overcurrent, I> 6000 Apri
Stage 2-time delay, I> 300 ms
Harmonic blocking Enabled
47
P14169 – Wind farm Formosa 2 – Protection settings
Figure 18: Overcurrent protection, 161kV CBs at Yin-Pan substation (1550, 1560) and transformer
bays at F2 (1650, 1660 and 1670)
48
P14169 – Wind farm Formosa 2 – Protection settings
According to [12], the ratios of the multi-ratio current transformers have been selected at 3000A:5A.
The rated current of the cable could be set according to 1485 A (Table 43). The threshold I-DIFF is set
approximately 20% of the rated current (note that the use of the special charging compensation
function would allow a lower setting [11]). The fast stage I-DIFF fast 2 is set to approximately twice the
rated current of the cable.
A relay trip signal shall lead to the tripping of all three phases.
Description Setting
The first zone of the distance protection shall act as a backup to the cable differential protection (87L).
It is set to approximately 80% of the cable length so as not to risk tripping prior to the tripping of
downstream protection.
49
P14169 – Wind farm Formosa 2 – Protection settings
The distance relays shall be set up for direct inter-tripping i.e., if either of these relays see a fault in
zone 1, it shall send tripping signals to both the local-end and remote-end circuit breaker of the faulted
line.
A second zone is set to reach into the wind farm, thereby acting as a backup to the 200MVA wind farm
transformer protection. It shall be time-delayed and reach into, but not beyond the wind farm
transformers.
The relays at the Ying-Pan end should trip the breakers at Ying-Pan immediately if the fault is seen in
the overreaching zone (zone 2) and the remote circuit breaker is open. This is typically done using the
echo logic i.e., the relays at F2 shall be set up to send an echo signal.
Distance relays typically require a source-to-line impedance ratio (SIR) of at most 50 to estimate the
impedance with sufficient accuracy. The fault current from the wind farm depends on the number of
WTGs in operation. With all WTGs in operation, the fault current is limited to approximately 110% of
rated wind farm current (1.5kA). This relates to a source impedance of 63Ω. The cable impedance is
around 0.86Ω, so that the SIR is around 73. With half the number of WTGs in operation, this increases
to 126. Therefore, it cannot be assumed that a distance relay at F2 would always measure the
impedance to the fault correctly, especially if the fault is close to F2. It is, therefore, proposed to make
use of the weak infeed logic.
If the relays at Ying-Pan see the fault in zone 2, and no blocking signal is received from the relays at
F2, then they shall trip the circuit breakers at the Ying-Pan end. The blocking signal shall be generated
by the relays at F2 if they see the fault in their reverse zone i.e., behind them, such as in the wind farm
transformers.
The weak infeed logic should be set up to make use of a voltage measurement at F2. They shall trip
the breakers at F2 with minimal delay if they receive a permissive signal from the relays at Ying-Pan
and do not see the fault in their reverse zones e.g., in the wind farm transformers).
If the relays at F2 see the fault in their reverse zone, they send a blocking signal to the relays at Ying-
Pan.
It is recommended that the weak infeed logic is always operational i.e., not to make it dependent on
the operating state of the wind farm.
The reverse-looking zone 3 at F2 shall reach beyond the overreaching zone at Ying-Pan to prevent a
mal-operation of the weak infeed logic.
The proposed relay (Siemens SIPROTEC 7SL86) allows the setting of many possible impedance
shapes – see Figure 20. It is proposed to use quadrilaterals. The inclination characteristic defined by
the angle α is not used.
The resistive reach depends mainly on the resistance of the cable. Some allowance is made for the
resistance of an arc, which could occur at the cable termination.
50
P14169 – Wind farm Formosa 2 – Protection settings
Table 46: System data and currents at CBs 1550, 1560, 1610 and 1620 for different operating and
fault conditions
Description Value
VT ratio 161000V/√3:115V/√3
CT ratio 3000/5
Positive-sequence resistance of 161kV cables [13] 0.04852Ωpri
Positive-sequence reactance of 161kV cables [13] 0.8573 Ωpri
Positive-sequence impedance of 161kV cables 0.86 Ωpri, 86.8°
Zero-sequence impedance of of 161kV cables [13] 1.95 Ωpri, 58.8°
Rated current of cable, n-1 [10] 1485 Apri
Impedance of one 200MVA transformers at 161kV 25.9Ω
Half of impedance of three parallel 200MVA transformers at 161kV 4.3Ω
Minimum short circuit current at Ying-Pan for 2-phase fault at 69kV-side of 3060 Apri
transformer, one 161kV cable and one 200MVA transformer in service
51
P14169 – Wind farm Formosa 2 – Protection settings
Minimum short circuit current at Ying-Pan for 2-phase fault at 161kV- 5036 Apri
terminals of transformer with 8Ω fault reactance, both 161kV cables in
service
Maximum short-circuit current at Ying-Pan, three-phase fault at 161kV/F2 30 000 Apri
and one 161kV cable in service
Minimum short circuit current at Ying-Pan, 2-phase fault with 5 Ohm 11615 Apri
reactance at the terminals of a 200MVA transformer, other two transformers
out of service, one 161kV cable and one 200MVA transformer in service
Impedance seen at POC for worst-case loading (including some margin):
R+jX as seen at the POC at 161kV, 400MW, 0Mvar 64.8+j0 Ωpri
R+jX as seen at the POC at 161kV, 400MW, 0.9 power factor 52.5±j25.4 Ωpri
Table 47: 161kV cable distance protection at CBs 1550, 1560, 1610 and 1620 (7SL86)
Description Setting
General
Characteristic Quadrilateral, forward
Relay characteristic angle, 𝜑𝐷𝑖𝑠𝑡 86°
Pickup method Impedance
Minimum current to enable pickup 150Apri
Other • Direct intertripping from Yin-Pan
• Weak infeed logic at F2
52
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
53
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
54
P14169 – Wind farm Formosa 2 – Protection settings
55
P14169 – Wind farm Formosa 2 – Protection settings
Description Setting
56
P14169 – Wind farm Formosa 2 – Protection settings
The settings for the protection at the POC could act as a backup to the WTG protection. It must
consider the capability of the equipment, such as the harmonic filters and the transformers. Low
frequencies lead to high flux levels in transformers (for a given voltage). For transformers designed to
IEC standards, the maximum continuous flux level is typically 105% i.e., the ratio of per unit voltage
(based on the transformer’s rated voltage) to per unit frequency (60Hz) should not exceed 105%. At
161kV, the minimum continuous frequency would then be 1/1.05*60Hz i.e., 57.1Hz.
The proposed settings are shown in Table 51.
Description Setting
57
P14169 – Wind farm Formosa 2 – Protection settings
58
P14169 – Wind farm Formosa 2 – Protection settings
12 References
[1] Fortune Electric, “Formosa 2 On Shore Work Detailed design meeting No. 12th, Presentation,”
10. Dec. 2019.
[3] Siemens, “D8 60Hz 66kV Relay Settings; Fortune Electric Document F2-WTG-CON-SGR-SP-
EL-00002[00],” 06.08.2019.
[4] Siemens, “SIPROTEC 5, Version 8.01 and higher, Overcurrent Protection 7SJ82, 7SJ85, Manual
C53000-G5040-C017-B”.
[5] Siemens, “SIPROTEC 5, Version 8.01 and higher, Transformer Differential Protection 7UT82,
7UT85, 7UT86, 7UT87, Manual C53000-G5040-C016-C”.
[6] Siemens, “SIPROTEC 5, Version 8.30 and higher, Low-Impedance Busbar Protection, 7SS85,”
Manual C53000-G5040-C019-A.
[8] FORTUNE ELECTRIC CO., LTD., SPECIFICATION FOR TRANSFORMER TR19025; F2-ONS-
CON-FOR-LY-EL-00002-002, 2019/10/18.
[9] TPC, Taiwan Power Company's Technical Guidelines for the Parallel Connection of Renewable
Energy Power Generation Systems.
[11] Siemens, “SIPROTEC 5, Version 8.30 and higher, Distance Protection, Line Differential
Protection, and Overcurrent Protection for 3-Pole Tripping, 7SL86 etc.,” C53000-G5040-C010-D.
[12] Fortune Electric Co., “Formosa 2 Offshore Wind Farm Project, Protection Philosophy; F2-ONS-
CON-FOR-ST-EL-00021; Version 5,” 28 January 2021.
[13] MPE GmbH, “Wind farm Formosa 2; Load flow and short-circuit report, Version 4,” 30.09.2020.
[14] Siemens Wind Power, “D12 Wind Turbine Voltage and Frequency Limits, Type 3; F2 document
number F2-WTG-CON-F2-CD-EL-00013,” 07.03.2019.
59