NATIONAL GRID SA

Title: Test Form for SAS Measurement Commissioning Index Number: DS-NG-6460-002-004 Rev01
Main Contractor:AL OJAIMI T&C Contactor: ALFANAR Contract No.: MOD 8369 Substation: 8369
Panel/ Bay No:H320C Equip. No.: 87 7SD Dwg. Ref.: 1013301 Serial No: 2103503303 Page Number: 1 of 6

1. Measurement at BCUs, HMI & Gateway


Measurement tests will be performed on all bays by current and voltage injection at the test
switch of the BCU. The respective registration of measurement values will be checked in the
BCU.

Checked Not Checked N.A Remarks


CT Ratio: -    
VT Ratio: 13.8kV/120V    

2. SAS Measurements
APPROVED
2.1. Current Measurement (I):
16 AUG 2021
DEAD BAND ( ) Checked: 
RATE OF CHANGE ( ) Checked: 
PHASE SEGREGATION Checked: 

Measured Reading
Injected Expected
R-Ph Y-Ph B-Ph
Current Current
BCU Error% BCU Error% BCU Error%
0.25 In - - - - - - -
0.50 In - - - - - - -
0.75 In - - - - - - -
1.00 In - - - - - - -
1.20 In - - - - - - -

Measured Reading
Injected Expected
R-Ph Y-Ph B-Ph
Current Current
HMI Error% HMI Error% HMI Error%
0.25 In - - - - - - -
0.50 In - - - - - - -
0.75 In - - - - - - -
1.00 In - - - - - - -
1.2 In - - - - - - -

Measured Reading
Injected Expected
R-Ph Y-Ph B-Ph
Current Current
Gateway Error% Gateway Error% Gateway Error%
0.25 In - - - - - - -
0.50 In - - - - - - -
0.75 In - - - - - - -
1.00 In - - - - - - -
1.2 In - - - - - - -
Error % = [(Expected Value – Measured Reading) ÷ (Expected Value)] X 100 %

CSD Contractor SAS T&C Contractor


Name Hesham Akl EmranulHaq Ahmed Abdel Sattar (SAS_FAN-015)
Sign.
Date: 11/04/2022 11/04/2022 11/04/2022
CLASSIFICATION: INTERNAL
NATIONAL GRID SA
Title: Test Form for SAS Measurement Commissioning Index Number: DS-NG-6460-002-004 Rev01
Main Contractor:AL OJAIMI T&C Contactor: ALFANAR Contract No.: MOD 8369 Substation: 8369
Panel/ Bay No:H320C Equip. No.: 87 7SD Dwg. Ref.: 1013301 Serial No: 2103503303 Page Number: 2 of 6

2.2. Voltage Measurement (V):

2.2.1. Phase to Neutral


DEAD BAND ( ) Checked: 
RATE OF CHANGE ( ) Checked: 
PHASE SEGREGATION Checked: 

Measured Reading
Injected Expected
Voltage Voltage R-N Y-N B-N
BCU Error% BCU Error% BCU Error%
0.25 Vn 1,994 2.0 -0.41 2.0 -0.41 2.0 -0.41
0.50 Vn 3,988 4.0 -0.41 4.0 -0.41 4.0 -0.41
0.8 Vn 6,381 6.4 -0.41 6.4 -0.41 6.4 -0.41
1.00 Vn 7,976 8.0 -0.41 8.0 -0.41 8.0 -0.41
1.20 Vn 9,571 9.6 -0.41 9.6 -0.41 9.6 -0.41

Measured Reading
Injected Expected
Voltage Voltage R-N Y-N B-N
HMI Error% HMI Error% HMI Error%
0.25 Vn 1,994 - - - - - -
0.50 Vn 3,988 - - - - - -
0.8 Vn 6,381 - - - - - -
1.20 Vn 7,976 - - - - - -
1.00 Vn 9,571 - - - - - -

Measured Reading
Injected Expected
Voltage Voltage R-N Y-N B-N
Gateway Error% Gateway Error% Gateway Error%
0.25 Vn 6826 - - - - - -
0.50 Vn 13652 - - - - - -
0.8 Vn 21845 - - - - - -
1.00 Vn 27305 - - - - - -
1.20 Vn 32767 - - - - - -
Error % = [(Expected Value – Measured Reading) ÷ (Expected Value)] X 100 %

CSD Contractor SAS T&C Contractor


Name Hesham Akl EmranulHaq Ahmed Abdel Sattar (SAS_FAN-015)
Sign.
Date: 11/04/2022 11/04/2022 11/04/2022
CLASSIFICATION: INTERNAL
NATIONAL GRID SA
Title: Test Form for SAS Measurement Commissioning Index Number: DS-NG-6460-002-004 Rev01
Main Contractor:AL OJAIMI T&C Contactor: ALFANAR Contract No.: MOD 8369 Substation: 8369
Panel/ Bay No:H320C Equip. No.: 87 7SD Dwg. Ref.: 1013301 Serial No: 2103503303 Page Number: 3 of 6

2.2.2. Phase to Phase


DEAD BAND ( 0.07kV ) Checked: 
RATE OF CHANGE (0.04 ) Checked: 

Measured Reading
Injected Expected
Voltage Voltage R-Y Y-B B-R
BCU Error% BCU Error% BCU Error%
0.25 Vn 3,45 3.4 1.0 3.4 1.0 3.4 1.0
0.50 Vn 6,9 6.9 0 6.9 0 6.9 0
0.8 Vn 11,04 11.0 0.36 11.0 0.36 11.0 0.36
1.00 Vn 13,8 13.8 0 13.8 0 13.8 0
1.2 Vn 16,56 16.6 -1.0 16.6 -1.0 16.6 -1.0

Measured Reading
Injected Expected
R-Y Y-B B-R
Voltage Voltage
HMI Error% HMI Error% HMI Error%
0.25 Vn 3,45 3.45 0 3.45 0 3.45 0
0.50 Vn 6,9 6.90 0 6.90 0 6.90 0
0.8 Vn 11,04 11.04 0 11.04 0 11.04 0
1.00 Vn 13,8 13.8 0 13.8 0 13.8 0
1.2 Vn 16,56 16.56 0 16.56 0 16.56 0
Address : 10154
Injected Expected Measured Reading

Voltage Voltage R-Y Y-B B-R


Gateway Error% Gateway Error% Gateway Error%
0.25 Vn 6826 - - 6826 -0.03 - -
0.50 Vn 13652 - - 13624 0.21 - -
0.8 Vn 21845 - - 21845 0 - -
1.00 Vn 27305 - - 27306 0 - -
1.20 Vn 32767 - - 32767 0 - -
Error % = [(Expected Value – Measured Reading) ÷ (Expected Value)] X 100 %

CSD Contractor SAS T&C Contractor


Name Hesham Akl EmranulHaq Ahmed Abdel Sattar (SAS_FAN-015)
Sign.
Date: 11/04/2022 11/04/2022 11/04/2022
CLASSIFICATION: INTERNAL
NATIONAL GRID SA
Title: Test Form for SAS Measurement Commissioning Index Number: DS-NG-6460-002-004 Rev01
Main Contractor:AL OJAIMI T&C Contactor: ALFANAR Contract No.: MOD 8369 Substation: 8369
Panel/ Bay No:H320C Equip. No.: 87 7SD Dwg. Ref.: 1013301 Serial No: 2103503303 Page Number: 4 of 6

2.3. Frequency Measurement (f):


DEAD BAND ( N.A ) Checked: 
RATE OF CHANGE ( 0.07Hz) Checked: 

59.00 Hz 59.50 Hz 60.00 Hz 60.50 Hz


Error %

Error %

Error %

Error %
Injected Frequency
BCU

BCU
BCU

BCU
Measured Frequency 59.0 0 59.5 0 60.0 0 60.5 0

59.00 Hz 59.50 Hz 60.00 Hz 60.50 Hz


Error %

Error %

Error %

Error %
Injected Frequency HMI
HMI

HMI

HMI
Measured Frequency 59.0 0 59.5 0 60.0 0 60.5 0
Address : 10155
59.00 Hz 59.50 Hz 60.00 Hz 60.50 Hz
Gateway

Gateway

Gateway
Gateway
Error %

Error %

Error %

Error %
Injected Frequency

1310 1474 1638 1802


Measured Frequency 0 0 0 0
7 5 4 2
Actual 13107 - 14745 - 16384 - 18022
Error % = [(Expected Value – Measured Reading) ÷ (Expected Value)] X 100 %

CSD Contractor SAS T&C Contractor


Name Hesham Akl EmranulHaq Ahmed Abdel Sattar (SAS_FAN-015)
Sign.
Date: 11/04/2022 11/04/2022 11/04/2022
CLASSIFICATION: INTERNAL
NATIONAL GRID SA
Title: Test Form for SAS Measurement Commissioning Index Number: DS-NG-6460-002-004 Rev01
Main Contractor:AL OJAIMI T&C Contactor: ALFANAR Contract No.: MOD 8369 Substation: 8369
Panel/ Bay No:H320C Equip. No.: 87 7SD Dwg. Ref.: 1013301 Serial No: 2103503303 Page Number: 5 of 6

2.4. Power Measurement:


DEAD BAND ( ) Checked: 
RATE OF CHANGE ( ) Checked: 

Measured Reading at In and Vn


Phase Active Power P [MW] Reactive Power Q [Mvar] Power Factor Cos PHI
Angle
Expected BCU Error Expected BCU Error Expected BCU Error
0° - - - - - - - - -
45° - - - - - - - - -
90° - - - - - - - - -
135° - - - - - - - - -
180° - - - - - - - - -
225° - - - - - - - - -
270° - - - - - - - - -
330° - - - - - - - - -

Measured Reading at In and Vn


Active Power P [MW] Reactive Power Q [Mvar] Power Factor Cos PHI
Phase
Angle Expecte Erro
HMI Error Expected HMI Expected HMI Error
d r
0° - - - - - - - - -
45° - - - - - - - - -
90° - - - - - - - - -
135° - - - - - - - - -
180° - - - - - - - - -
225° - - - - - - - - -
270° - - - - - - - - -
330° - - - - - - - - -

Measured Reading at In and Vn


Phase Active Power P [MW] Reactive Power Q [Mvar] Power Factor Cos PHI
Angle Expecte Gatewa Erro Expecte Gatewa Erro Expecte Gatewa
Error
d y r d y r d y
0° - - - - - - - - -
45° - - - - - - - - -
90° - - - - - - - - -
135° - - - - - - - - -
180° - - - - - - - - -
225° - - - - - - - - -
270° - - - - - - - - -
330° - - - - - - - - -
CSD Contractor SAS T&C Contractor
Name Hesham Akl EmranulHaq Ahmed Abdel Sattar (SAS_FAN-015)
Sign.
Date: 11/04/2022 11/04/2022 11/04/2022
CLASSIFICATION: INTERNAL
NATIONAL GRID SA
Title: Test Form for SAS Measurement Commissioning Index Number: DS-NG-6460-002-004 Rev01
Main Contractor:AL OJAIMI T&C Contactor: ALFANAR Contract No.: MOD 8369 Substation: 8369
Panel/ Bay No:H320C Equip. No.: 87 7SD Dwg. Ref.: 1013301 Serial No: 2103503303 Page Number: 6 of 6

Error % = [(Expected Value – Measured Reading) ÷ (Expected Value)] X 100 %

CSD Contractor SAS T&C Contractor


Name Hesham Akl EmranulHaq Ahmed Abdel Sattar (SAS_FAN-015)
Sign.
Date: 11/04/2022 11/04/2022 11/04/2022
CLASSIFICATION: INTERNAL