PROJECT : ONE QUBE PODIUM-3 , PLOT NO.

20, SECTOR-18 GURGOAN


COST ESTIMATE FOR HVAC WORKS

Dated 4/6/2023

S.NO. Description Unit Qty Rate Amount

[C] AIR DISTRIBUTION:

1.0 SHEET METAL DUCT:

1.1 Supply, Installation, testing, and balancing of Factory


fabricated (LFQ) duct complete with cleats/TDC
Flanges/corners/HD galvanized nut bolts & supporting
rods /sealant confirming to SMACNA standards 2005
(IIIrd edition). Any to suit pieces shall be hand fabricated
at site.The price shall include factory fabricated TDF
flanges, turning vanes, spliter dampers, supports
(factory fabricated, wire rope based supporting system
as per specifications), sealent (neoprene gasket),
hangers, access door etc. The joints shall be with least
leak and shall be tested with smoke testing.
a) 24 gauge galvanized sheet Sqm. 95

b) 22 gauge galvanized sheet Sqm. 35

c) 20 gauge galvanized sheet Sqm. 22

d) 18 gauge galvanized sheet Sqm. 50

2 SITE FABRICATED :

Supply, fabrication, installation and testing of sheet


metal ducts of following thicknesses including necessary
supports anti vibration, hangers, nut & bolts, gaskets,
splitter dampers, vanes etc complete as per
specifications in accordance with the approved shop
drawings and as required as per IS 655. (Site fabricated
ducts shall be used only in case of makeup pieces).The
price shall include flanges, turning valves, spliter
dampers, supports (factory fabricated, wire rope based
supporting system as per specifications), sealent
(neoprene gasket), hangers, access door etc. The joints
shall be with least leak and shall be tested with smoke
testing.

a) 24 gauge galvanized sheet Sqm. 5

b) 22 gauge galvanized sheet Sqm. 5

c) 20 gauge galvanized sheet Sqm. 5

d) 18 gauge galvanized sheet Sqm. 5

3.0 ROUND DUCT:

3.1 Supply,construction, erection, testing, and preformance


of Factory fabricated (LFQ) round duct complete with
cleats/TDC Flanges/HD galvanised nut bolts & Sqm. RO
supporting rods /sealant confirming to SMACNA
standards 2005 (IIIrd edition)

4.0 FLEXIBLE CONNECTION:

Supply, fabrication, installation and testing of double


canvas (fire proof) flexible connection constructed of fire Sqm. RO
resistant material as per drawings/specifications.

5.0 MOTORIZED FIRE DAMPERS:


Supply, installation, testing and commissioning of fire
dampers of at least 90 minutes fire rating as per
specification & approved shop drawings, complete with
actuator with spring return mechanism and control
panel, limit switch to on fans when the damper opens.
The fire damper shall be UL listed.

a) Fire Dampers Sqm. 1.8

b) Actuators with spring return mechanism Nos. 2

6.0 VOLUME CONTROL DAMPER:

Supply, installation and testing of GI volume control


dampers within ducts complete with suitable links, levers
and quadrants for manual air balancing.

SIZE : 700MMx500MM Nos. 2


SIZE : 7750MMx500MM Nos. 1
SIZE :600MMx400MM Nos. 1
SIZE : 700MMx450MM Nos. 1

7.0 SUPPLY/RETURN AIR GRILLES:

a) Supply, installation, testing and balancing standard


single louvered extrucded aluminimum supply air grills
Sqm. R.O
with dampers as per approval shop drawings &
specifications.

b) Supply, installation, testing and balancing standard


single louvered extrucded aluminimum return air grills
Sqm. R.O
without dampers as per approval shop drawings &
specifications.

8.0 LINEAR GRILLES:

a) Supply, installation, testing and balancing of extruded


powder coated aluminium linear grills as per approved
shop drawings & approved samples.

i) 100 mm high RM R.O


ii) 150 mm high RM R.O
iii) 200 mm high RM R.O

b) Volume control damper in supply air collers. Sqm R.O

9.0 DIFFUSER:

Supply, installation, testing and balancing of square, air


diffusers. All diffusers must be multislotted complete
with air pattern controller. Each diffuser shall be
equipped with fixed air distribution grid and antis-mudge
ring where required as per the shop drawings &
specifications.

a) Extruded Aluminium powder coated diffusers with


Sqm. R.O
damper

b) Extruded Aluminium powder coated diffusers without


Sqm. R.O
damper

10.0 SLOT DIFFUSERS :

Supply, installation, testing and commissioning of


extruded aluminium powder coated slot diffusers (20mm
gap).

a) 1 slot- with hit and miss damper RM R.O


b) 1 slot- without hit and miss damper RM R.O

c) 2 slot- with hit and miss damper RM R.O

d) 2 slot- without hit and miss damper RM R.O

e) 3 slot- with hit and miss damper RM R.O

f) 3 slot- without hit and miss damper RM R.O

g) 4 slot- with hit and miss damper RM R.O

h) 4 slot- without hit and miss damper RM R.O

11.0 FRESH AIR LOUVER:

a) Supply, installation and testing of fresh air inlet louvers,


bird screen in accordance with approved shop drawings Sqm R.O
and specifications.

12.0 EXHAUST AIR GRILLES:

Supply, installation & testing of exhaust air grilles. All


grilles shall be single louvered only.

a) Aluminium powder coated grilles. Sqm R.O

13.0 EXHAUST AIR LOUVERS:

Supply, installation and balancing of exhaust air louvers


with bird screen in accordance with approved shop Sqm R.O
drawings and specifications.

14.0 TRANSFER AIR GRILLES:

Supply, installation & testing of transfer air grilles of


Sqm R.O
extruded aluminium.

15.0 GRAVITY LOUVER:

Supply, Installation, Testing & Commissioning of gravity


louver having 18 gauge GI frame all around and suitable
partitions with 20 gauge GI louvers & SS pivoted rods
mounted in the frame through linkage to avoid rattling of Sqm R.O
blades within louvers for free movement.

16.0 NOZZLES DIFFUSER (SUPPLY)


Supply, installation, testing & commissioning of
aluminium construction, half breast, Supply Air Nozzle
diffuser as per specifications and of approved colour
and shade.
The diffuser shall be completed with suitable Butterfly
Damper of 16 G GSS with Brass bush and operating
handle. The damper shall have multiple controlling
option and should provision to lock at any position for
Supply Air Nozzles diffuser.
a. 400mm dia Nos R.O
b. 300mm dia Nos R.O

TOTAL OF AIR DISTRIBUTION SYSTEM CARRIED


OVER TO SUMMARY
[D] INSULATION:

1.0 THERMAL INSULATION:


a) Supply, installation & testing of external factory
laminated,fire retardent thermal insulation with
aluminium foil face on ducts. Density shall not be less
than 48 kg/cu.m. as per the specifications & approved
shop drawings.

i 25 mm thick prelaminated fibre glass insulation. Sqm 22


iii 50 mm thick prelaminated fibre glass insulation. Sqm 100

2.0 ACOUSTIC LINING :

XLPE
Supply and fixing of acoustic lining of supply air dict and
plenum with 25mm thick engineered cross linked
polyethene semi open cell insulation having a noise
reduction coefficient of 0.35( as per ISO 354) with
density 30kg/m3following std. ASTM D3575, passing
class 1 fire performance tests per BS 476 part7, VOC Sqm 70
level shall be as per ASTM D5116 with antifungal
properties as per ASTM G21 and bacterial resistance
test as per DIN ISO 22196, to be applied using
manufacturers recommended rubber based adhesive in
a blend of solvent.

TOTAL OF INSULATION CARRIED OVER TO


SUMMARY
TOTAL OF HVAC SYSTEM CARRIED OVER TO
SUMMARY
SOPHIC DESIGNS PVT. LTD.

PROJECT : ONE QUBE PODIUM-3 , PLOT NO. 20, SECTOR-18 GURGOAN

COST ESTIMATE FOR ELECTRICAL WORKS


Dated 4/6/2023

S.NO. Description Unit Qty Rate Amount

1 MV SWITCHGEAR PANELS :

Design, manufacture, supply, installation, testing and commissioning of following Utility panels
suitable for 415 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free
standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type
compartmentalised design fabricated out of 2mm thick CRCA sheet steel for Load bearing members
and 1.6 mm thick for non-load bearing members, complete with colour coded, heat shrinkable PVC
insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the
length of the panel. The incoming and outgoing feeders shall be accommodated in a fully
segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar
alley/chamber (form-3b Construction). The panel shall be complete with name plate, earthing,
numbering, danger plate etc. as required and as per specifications and drawings. The panel shall
withstand the fault level of as indicated elsewhere or shown in Single Line Diagram.

Important Notes: Common for all Switchgear Panel/ Switchboard:

1 The BOQ shall be read inconjunction with general notes, specification and Single Line Diagram
(attached for Ref.). Incase of any discrepancy between specification, BOQ and SLD, the same shall
be brought to the notice of Client/Consultant before quoting the rates, otherwise stringent condition
shall be deemed to have been considered.

2 Fault current wherever mentioned shall be Ics value. (Ics = 100% Icu).
3 All MCCB shall be provided with door interlocked rotary handle with ON/OFF/TRIP position indicator,
continious variable thermal magnetic O/C and S/C releases. MCCB above 400 Amp rating shall be
provided with microprocessor based release for over current, selectable short circuit , instantaneous
short circuit protection (suitable at site).

4 Incoming MCCBs shall be provided with O/C, S/C, and Earth fault protection releases.

5 Outgoing MCCBs shall be provided with O/C & short circuit protection.

6 All feeder doors shall have pad locking arrangement.

7 All TP feeders shall have solid isolable neutral link.

8 All MCCB used in starter feeder shall be suitable for motor duty application.
9 All power contactors including NIC shall be of AC3 duty.
10 All switchgear used in starter feeder shall be type-2 co-ordinated. Manufacturer is required to
submit manufacturers type-2 co-ordination chart for the make used.

11 All outgoing terminals (power and control) shall be brought upto cable alliy. 10% exxtra terminals
shall be provided.

12 10% extra indicating lamps in loose shall be supplied along with panel.

13 Removable lifting hooks shall be provided in all transportation section.


14 All CTs & PTs shall be Cast resin.
15 All meters are digital type.

16 Panel shall be powder coated of approved shade with minimum 60 micron thickness.
17 ACB's/MCCB's in one particular panel shall be of one similar make.

18 Size of Voltmeter / Ammeter for incomer also, 96mm x 96mm flush mounted with shrouded terminal
shall be used in the panel.

19 Bus bar chamber shall be kept at top of the all panels.


20 All bus bar shall be insulated with coloured PVC Sleeve i.e.RYB,BK as per colour code.
21 Internal wiring of panel shall be with size 2.5sqmm Flexible Copper Conductor for CT circuit and
control wiring with 1.5 sqmm.

22 All indicating light shall be LED type .


23 Each vertical section of floor mounted panel shall have independent base frame (75mm x 40mm)
size made out of 3 mm sheet steel (LT Panel & DG Panel).

24 All the makes shall be as per Client approved make list only.

25 Wherever only voltmeter & ammeter are required, the same may be provided in combined meter
suitable for both parameter.

26 All relays shall be neumeric relays


27 All panels shall be provided with TVSS at main bus as per main single line diagram. Panel vendor
shall take care of space provision for the same.

Project: One Cube Podium-3 Gurgaon Page 5


Electrical Bil of quantities
SOPHIC DESIGNS PVT. LTD.

28 Suitable arrangement/provisions of Hardware and control wiring shall be done by the panel. Vendor
to communicate the DG operation to Dual Source Energy Meters of panels.

29 All Panels shall be provided with door switch controled illumination lamp and termostst control fully
equiped with space heater and exhaust fan.

30 Where ever Mentioned in BOQ and specification all Electronic Energy Meter will be Prepaid Duel
source electronic energy meter having ISI Marked as well as accepted to State Electricity Board
(Make EM 6438 Conzerv/Neptune/secure/crystal/Capital),Electrical Vendor will provide the
acessories/Device for the integration of MFM data with Energy meter as per direction of service
consultant to meet the requirment of GRIHA Certified ,ECBC compliance building requirment without
any cost.

There should be fault descimination in incommer & out going breaker-ACB/MCCB/MCB of single
make.Casading effect need to be consider during selection of breaker.Panel Manufacturer will
31 arrange the Falut level claculation and Software generated report for each panel from the switchgear
provider Design department during GAD approval without any cost.

Proposed Electrical Panel should be integrable and functional with Fire alarm Panel and PA system
32 in addition to BMS system as per NBC-2016 /Fire department requirment.

1.1 MDB-P3 PODIUM-3 (NEW PANEL)TENANTS


Location : Podium-3

Incomer:

- one (1) No. 125A 4P MCCB . (35KA)

Combind digital electronic ammeter/ Volt meter with selector switch and 10 VA, CL-1 CTs & 2 amps
- TP MCB's.

- One (1) set of RYB phase indication lamps with control SP MCB.

- ON OFF Trip indication.

Busbar :

200A TPN Al. Busbar of short circuit withstand capacity 35kA. Busbar shall be insulated with heat
shrinkable sleeves and shall be color coded.

Outgoing :

Each MCCB outgoing feeders shall be provided with ON/OFF/Trip indication lamps with back up SP
MCBs.

3 No. 63A TPN MCCB with 3 phase, Digital,Pre-paid dual source Energy meter with the Class-1 CTs
- of suitable ratio and VA, as required, with suitable internal wiring for 230V control signal, for DG
supply.(Tenant-1 ,Tenant-2 & GYM.)
1 No. 40A TPN MCCB with 3 phase, Digital,Pre-paid dual source Energy meter with the Class-1 CTs
- of suitable ratio and VA, as required, with suitable internal wiring for 230V control signal, for DG
supply.(CRECHE)

- 2 Nos.63A TPN MCCB Spare

MDB-P3 PODIUM-3 (NEW PANEL)TENANTS) described as above as per SLD Set 1

1.2 SPD's AS PER IS/IEC 62305-3 Standard


Modular Surge Arrester with integrated backup fuses for TT and TN-S system (3 phase, 415V), Type 1
- 2 SPD No

TOTAL OF MV PANELS

2 CABLES, SUB MAINS & CABLE TRAYS,EARTHING STRIP


2.1 CABLES, SUB MAINS & CABLE TRAYS:

2.1.1 1.1KV Grade Cables on Racks / Pipes/ DuCTs / wireways


Supply installation, testing and commissioning of following sizes of PVC sheathed XLPE insulated
Aluminium conductor/copper con-ductor power/ multicore control armoured cable of 1.1 KV grade on
surface of wall or in existing cable tray /masonary duCTs/hume pipe with fixing hardware etc as
required.Including 1Meter Fire retardent paint on both side of cable to be painted at each Wall
crossing/ Fire Barrier..

2..2.1.1 Aluminium Conductor XLPE Armoured Cables:


a) 3 ½ core 70 sqmm RM R.O
b) 3 ½ core 50 sqmm RM 50 320
c) 3 1/2 core 35 sqmm RM R.O
d) 4 core 25 sqmm RM R.O
e) 4 core 16 sqmm RM R.O
f) 4 core 10 sqmm RM R.O
m) 4 core 6 sqmm RM R.O

2.2.1.2 Copper Conductor Armoured Control Cables


a) 14 C 2.5 Sqmm PVC cable RM R.O
b) 10 C 2.5 Sqmm PVC cable RM R.O

Project: One Cube Podium-3 Gurgaon Page 6


Electrical Bil of quantities
SOPHIC DESIGNS PVT. LTD.

c) 6 C 2.5 Sqmm PVC cable RM R.O


d) 3 C 2.5 Sqmm PVC cable RM 2000 173

2.2 1.1KV Grade Cable Terminations :


Supply and making end termination with brass double compression glands up to 120 Sqmm Cales &
below 120 Sqmm Cables single compression glands for the following XLPE insulated PVC sheathed
1100 V grade cable including cost of crimping lugs/ferrules, compression glands, solder, cable
sockets, insulation tap etc complete as required.

10.3.1 Aluminium conductor armoured cables Termination.


a) 3 ½ core 70 Sqmm Nos. R.O
b) 3 ½ core 50 Sqmm Nos. 2 1260
c) 3 ½ core 35 Sqmm Nos. R.O
d) 4 Core 25 Sqmm Nos. R.O
e) 4 Core 16 Sqmm Nos. R.O
f) 4 Core 10 Sqmm Nos. R.O
g) 4 Core 6 Sqmm Nos. R.O
10.3.2 Copper Conductor Armoured Control Cables :
(Glands suitable for following armoured cables)
a) 14 C x 2.5 Sqmm PVC Cable Nos. R.O
b) 10 C x 2.5 Sqmm PVC Cable Nos. R.O
c) 6 C x 2.5 Sqmm PVC Cable Nos. R.O
d) 3 C x 2.5 Sqmm PVC Cable Nos. 8 640

Note: The cable quantities given are approximate and to cover various sizes.
The contractor will verified the actual route length as per provised shop drawings ,validating
consulatnt cable schedule length to confirm the volatge drop for the feeder shall not exceed 2% at
design load.The volatge drop for the branch circuit shall not be exceed 3% at design laod. The toltal
distribuition losses in power cable should not exceed the ECBC-2017 Guidline i.e 3% of total power
usage.
The contractor shall measure the cables required and procurement order shall be placed
accordingly. The quantities shall be confirmed before start of work.

2.3 Cable Trays :


Supply and installation of ladder type/perforated type cable trays of the following sizes fabricated out
of perforated hot dip galvanised MS sheets of minimum 2 mm thick with 75 mm flange to be installed
horizontally or vertically. The cable tray shall be complete including cost of bends, elbows, cross,
tees, reducers etc as per drawings/site condition and as required.
Notes:

i) Structural steel such as ISMC, ISA, flats, rods etc to be used for cable tray/bus duct support shall
not be paid separatey.The support arrangement shall be as indicated in the drgs.If nothing is
mention for spacing and size then applicable latest CPWD speciifcation /IS code will be followed by
vendor after getting the duly approval from client and consultant during shop drawings approval.

The contractor may refer to the tray installation drawings/ specification for this purpose.
ii) The cable tray shall be factory built. Bidder shall include in his price, required numbers of Tees,
Crosses, Bends, Elbows etc as required as per actual site conditions. Bidder may refer to the
drawings for estimation purpose.

iii) Earthing strip shall be paid separately under sub head "Earthing".

iv) The rate shall include painting with 2 primer coats of red oxide and two finishing coats of approved
paint.

2.3.1 Perforated Type Cable Tray :


a) 450 mm wide RM R.O
b) 300 mm wide RM 50 850
c) 150 mm wide RM 100 540
2.3.2 Misc. Works Relating to Cabling:
10.5.1 GI Pipe Installation :
Supply and installation of following sizes of `A' class GI pipe for cable sleeves in recess/ on
surface/Ground complete with all accessories pull boxes where ever required, G.I. fish wire, fixing
hardware etc. including the chasing of wall/floor, and plastering the chased portion, digging the
trench and back filling, making good the damages, sealing of pipe entry etc as required.

a) 150 mm dia RM R.O


b) 200 mm dia RM R.O

2.4 EARTHING SYSTEM :


2.4.1 Earthing Strip/Wires :
Supply, installation, testing and commissioning of following sizes of GI/ Copper strip/wire clamped to
walls, cable trays, bus ducts, cables in recess or surface etc for equipment/ System earthing
complete as required including inter connection between length at joints, all fixing accessories
saddles, clamps, lugs etc and other fixing hardware material as required for proper installation.
2.4.2 G.I. Earthing strip/wire :
a) 75 x 6 mm strip RM RO

Project: One Cube Podium-3 Gurgaon Page 7


Electrical Bil of quantities
SOPHIC DESIGNS PVT. LTD.

b) 50 x 6 mm strip RM RO
c) 40 x 6 mm strip RM RO
d) 32 x 6 mm strip RM RO
e) 25 x 6 mm strip RM 100 120

TOTAL OF LT CABLE & EARTHING

3.0 POINT WIRING :

1 The rates for point wiring shall include the circuit wiring.

2 Circuit wiring means the wiring from DB/Dimmer panel to the first point of circuit through switch
board / switch boards/Dimmer junction box

3 Circuit wiring and subsequent looping shall be done with 2.5 Sqmm, 1100V grade PVC insulated
stranded, copper conductor wires.

4 The rates of point wiring shall include MS conduit with accessories, GI Boxes (18 SWG) and
required GI flexible conduits with accessories up to the Point.

5 The rates of point wiring shall include earthing of each light, fan, switches, switch plates, boxes and
other non current carrying metallic part with 1.5 Sqm. Stranded copper, PVC flexible wire.

6 Galvanised MS Box Modular Plate, switches and sockets shall be of same make as approved by
Client.

7 All wire terminations shall be made using thimbles.

3.1 Light Points Controlled by switch

a) Wiring of light point with PVC insulated 2.5sq.mm stranded copper conductor wires & earthing with
1.5 sq.mm PVC insulated Cu. Conductor from DB. Via switch in MS conduit including chasing of
wall, filling of chases with cement mortar 1:3 mix and fixing conduit of wall/ceiling including fixing of
saddles etc. including providing and fixing galvanized MS switch box, modular 6A switch, modular Nos. 4 660
plate and cover plate, deep tee, circuit wiring etc. complete in all respects including testing &
commissioning as required.

b) Same as above but loop point Nos. 12 660

3.2 Light Points Controlled by MCB

a) Wiring of light point with PVC insulated 2.5sq.mm stranded copper conductor wires & earthing with
1.5 sq.mm PVC insulated Cu. Conductor from DB. Via switch in MS conduit including chasing of
wall, filling of chases with cement mortar 1:3 mix and fixing conduit of wall/ceiling including fixing of
saddles etc. including providing and fixing deep tee, circuit wiring etc. complete in all respects
including testing & commissioning as required.
(Cost of wiring from DB up to light point to be included. cost of MCB not to be considered as it is
considered elsewhere in tender). Nos. RO

b) Same as above but loop point Nos. RO


3.3 6A Socket Points `

a) Wiring for 1 No. 6A switched socket oultlets with 2.5 sqmm PVC insulated stranded copper
conductor wires in recessed/surface MS conduit including cutting/filling chases, providing conduit
with conduit accessories, saddles, supply and fixing of Modular Type 1 No. 5 pin 6 amps shuttered
switched sockets Modular Plate, Galvanised M.S. Box with internal wiring in G.I. box , earthing of Point 2 1420
3rd pin with PVC insulated, green colour 1.5sqmm copper wire, complete with all accessories as
required.
(with raw power and combined with lighting).

3.4 Wiring of exhaust fan point with PVC insulated 2.5 sq.mm stranded copper conductor wires &
earthing with 1.5sqmm PVC insulated CU. Conductor from DB via switch in MS conduit including
chasing of wall, filling of chases with cement mortar 1:3 mix and fixing conduit on wall/ceiling
including fixing of saddles etc. including providing and fixing galvanized MS switch box, modular 6A
switch, modular plate and cover plate, 6A socket , deep tee, circuit wiring etc. complete in all
respects including testing & commissioning as required. (5A socket shall be provided near exhaust
Fan and switch shall be near entry door of toilet). Point RO

a) Ceiling fan point wiring with 2.5 Sqmm. PVC insulated copper wires controlled by a 5A switch &
electronic fan regulator. The rate shall include G.I. fan box/ fan hook etc. Point R.O

3.4.1 Power Socket Wiring

3.4.1.1 Wiring for 1 No 5/15 Amp power outlet with 4 Sqmm PVC insulated stranded copper conductor wires
in recessed/surface MS conduit including cutting/filling chases, providing conduit with conduit
accessories, saddles, supply and fixing of 1 No. 6 pin 5/15 amps Modular Type shuttered switched
socket, Modular Plate, Galvanised M.S Box of required size with internal wiring in G.I. box, earthing
of 3rd pin with PVC insulated, green colour 2.5 Sq.mm copper wire, complete with all accessories as
required.

- (One socket in one circuit) Point 2 1750

Project: One Cube Podium-3 Gurgaon Page 8


Electrical Bil of quantities
SOPHIC DESIGNS PVT. LTD.

3.4.1.2 Wiring for 2 Nos 5/15 Amp power outlets with 6 sqmm PVC insulated stranded copper conductor
wires upto first point and 4.0 sqmm from first point to second point in recessed/surface MS conduit
including cutting/filling chases, providing conduit with conduit accessories, saddles, supply and fixing
of 2 Nos. 6 pin 5/15 amps modular type shuttered switched sockets, Modular Plate, Galvanised M.S.
Box with internal wiring in G.I. box , earthing of 3rd pin with PVC insulated, green colour 2.5 sqmm
copper wire, complete with all accessories as required.

- (Two sockets in one circuit) Point 1 1850


TOTAL OF POINT WIRING SYSTEM

4.0 FIRE ALARM SYSTEM


1.0 Supplying, installing, testing and commissioning of the following as per specification complete with
junction box, as and where required.

1.1 Analogue addressable type Photo Electric type Smoke Detector with sounder base, address switch
complete as required. Each R.O.

1.2 Analogue addressable type Photo Electric Smoke Detector with mounting base, address switch
4 2200
complete as required. Each

1.3 Analogue addressable rate of rise cum fixed temperature thermistor type heat detector with
mounting base, address switch complete as required. Each RO

1.4 Analogue addressable fixed temperature type heat detector with mounting base, address switch
complete as required. Each RO

1.5 LPG gas detector with mounting base, address switch complete as required. Each R.O.

1.6 Carbon monoxide detector with mounting base, address switch complete as required. Each R.O.

1.7 Addressable type Manual Call Point complete as required. Each 2 1300

1.8 Addressable Hooter cum strobe complete as required. Each 2 2400

1.9 Addressable strobe complete as required. Each R.O.

1.10 Projected beam detector with address switch complete as required. Each R.O.

1.11 Duct casting unit with casing of fabricated aluminium/poly carbonate and hinged inspection cover, 1
No. inlet of proper length & 1 no. outlet tube & with 1 no. analogue addressable photoelectric type
Smoke detector with mounting base, address switch complete as required. Each R.O.

1.12 Analogue addressable Fault Isolators for isolating shorted, de-wired and loose circuits between two
successive Fault isolators with automatic resetting arrangement. (max. 20 devices for one fault 1 6500
isolators). Each

1.13 Analogue addressable, automatic commandable Control Switches for switching on/off various
ventilation fans, pressurisation fans, zones of speakers etc. and other Fire operation related devices
and complete as required. Each RO

1.14 Addressable Input Card/monitor module for connecting to Flow Switch etc. Each RO

1.15 Response indicator consisting of 16 gauge MS box with 75 x 75 x 6 thick cross brushed aluminium
face plate. Each RO

1.16 Zone address module to connect conventional zones with the addressable panel. Each R.O.

4.2 Supplying, installing and jointing of MS conduits on surface or concealed complete with MS junction
boxes, cover plates, MS bends, GI saddles, base and other accessories all made in MS with GI
screws as required to complete the job. Exposed conduiting shall be painted with red enamel paint
for identification.

a) 32 mm dia* Each R.O.


b) 25 mm dia* RM 100 387
c) 20 mm dia* Each R.O.

4.5 Providing and fixing shielded 2C x 1.5 sq mm copper conductor PVC sheathed Unarmoured cable
Fire Resistant including end terminators, saddles, clamps with screws etc for laying in conduits and 125
complete as required. RM 150

4.6 Providing and fixing flexible 20 mm dia GI conduit including all necessary supports, clamps, joining
120
pieces etc for drop of cables from slab to detector. RM 20

4.7 Providing and fixing 40 x 200 x 40 x 2 mm thick slotted angle stove enamelled cable tray for fixing
on walls including all nuts, bolts, washers etc. for runs of armoured cables. RM RO

5.0 PUBLIC ADDRESS SYSTEM :

5.1 Wall mounted speaker with three tap changers in acoustically treated box with speaker and line
matching transformer (2W max).(For car park & double height areas) No. RO

5.2 Ceiling mounted baffle speaker with three tap changers (2W). No. 3 4500

5.3 Providing and fixing shielded 2C x 1.5 sq mm copper conductor PVC sheathed Unarmoured cable
Fire Resistant including end terminators, saddles, clamps with screws etc for laying in conduits and 140
complete as required. RM 200

Project: One Cube Podium-3 Gurgaon Page 9


Electrical Bil of quantities
SOPHIC DESIGNS PVT. LTD.

5.1.1 Fire Fighter Telephone System :

a) Portable UL listed fire phone handsets in a suitable enclosure. No. RO

b) Addressable fire phone jack plates with control/monitor module. Nos. RO

c) Providing and fixing shielded 2C x 1.5 sq mm copper conductor PVC sheathed Unarmoured cable
Fire Resistant including end terminators, saddles, clamps with screws etc for laying in conduits and
complete as required. RM RO

Note : Running meters (RM) for the cable/conduit is approximate. The contractor shall measure the running
meter (RM) and procurement order shall be placed accordingly. The quantities shall be confirmed
before start of work to the engineer-in charge.

TOTAL OF FIRE ALARM SYSTEM

Project: One Cube Podium-3 Gurgaon Page 10


Electrical Bil of quantities
PROJECT : ONE QUBE PODIUM-3 , PLOT NO. 20, SECTOR-18 GURGOAN
COST ESTIMATE FOR PLUMBING AND FIRE PROTECTION WORKS

Dated 4/6/2023

S.NO. Description Unit Qty Rate Amount

I PLUMBING SYSTEM:

1.0 Providing, fixing, testing & commissioning of CI (Spun) Soil, Waste, Vent Pipes
conforming to IS : 3989-1984 including all fittings with / without access door of any
degree, Single / Double / Equal / Unequal junctions, bends, offsets, Cowls, Collars,
Access / door pieces, insertions, rubber washer 3 mm thick, bolts & nuts , GI
Holder bats and clamps of approved design and jointing with drip seal joints
including cutting holes in Walls & floors and making good the same wherever
required. (Internal,Vertical & Horizontal Soil & Waste Pipe Header running in
basement ceiling, Basement Drain pipe in Basement, Sewerage sump vent pipe).

a) 75 mm dia RM R.O.
b) 100 mm dia RM 15
c) 150 mm dia RM R.O.

3.0 Painting of Cast Iron Soil, Waste, Vent. & Rain water Pipes & fittings with synthetic
enamel paint of any colour as per pipe colour code over a coat of primer ( of
approved quality).

a) 75 mm dia RM R.O.
b) 100 mm dia RM 15
c) 150 mm dia RM R.O.

5.0 Providing and fixing cast brass clean out plug with suitable insert keys for opening
in brass cap, male threaded joint/reducer with GI socket caulked to Pipe/fittings of
CI pipe including cost of lead joints etc. complete in all respect.

a) 100 mm dia. Each 4


b) 150 mm dia. Each R.O.

2.0 CPVC Pipe (Exposed) :

Providing, fixing testing, and commissioning of CPVC (Chlorinated Polyvinyle


Chloride) pipe as per CTS SDR-11 & fittings such as tees, brass FPT elbows,
reducers, male/female male adaptor with brass threads, clamps etc. as per
ASTMD-2846, jointing with CPVC solvent cement as per manufacturer
recommendations conforming to ASTM-F493. Steel Structural support as
required/directed at Site including all civil work, cutting and making good the
walls, floors, R.C.C. work etc. (Pipe running in false ceiling + connection from GI
downtake pipe in shaft) .

a) 15.9 mm (OD) RM R.O.


b) 22.2 mm (OD) RM R.O.
c) 28.6 mm (OD) RM R.O.
d) 34.9 mm (OD) RM 12
e) 41.9 mm (OD) RM 12
f) 54.0 mm (OD) RM 12
73.2 mm (OD) RM R.O.

6.0 Providing, fixing, testing & commissioning of forged brass nickle plated lever
operated ball valve of full bore with forged brass hard chrome plated ball with
min. working pressure of 10 Kg/cm2 Hydraulic test pressure at seat & shell shall be
16 Kg/cm2 and 25 Kg/cm2. Lever should be anti rust coating, complete in all
respects (For Domestic CWS/FWS Application).

a) 15 mm dia Each R.O.


b) 20 mm dia Each R.O.
c) 25 mm dia Each R.O.
d) 32 mm dia Each 8
e) 40 mm dia Each 1
f) 50 mm dia Each 1
j) 65 mm dia Each R.O.
j) 80 mm dia Each R.O.

10.0 Butterfly Valves :


Providing, fixing, testing & commissioning of wafer type cast iron butterfly valves
conforming to BS 5155 & IS 13095 tested to 15 Kg/Sq.cm pressure for maximum
working pressure of 10 bar (PN 10) including all fitting and accessories (Drain,
water meter for OH Tank/Riser).

a) 65 mm dia Each 1
b) 80 mm dia Each R.O.
c) 100 mm dia Each R.O.
d) 150 mm dia Each R.O.

II FIRE PROTECTION SYSTEM


A SPRINKLER SYSTEM:

1.0 Supply, installation, testing and commissioning of MS Pipe class 'C' (heavy duty)
conforming to IS:1239 including all accessories such as screwed/welded joints,
flanges, tees, reducers, structural steel supports and clamps etc. including lift to
all heights, welding, jointing, painting and inserted rubber gaskets, nuts, bolts etc.
as required. Pipes shall be painted with two coats of primer & two coats of post
office red synthetic enamel paint over two coats of red oxide zinc chromate
primer. Prior to application of primer surface to be cleaned including painting of
legends both direction arrow as per approval of Project Manager and shall be
fixed in ceiling, walls, columns for all heights with hangers/supports and fasteners
all as per drawing including chasing of walls/columns /ceiling etc. and making
good the same as required. G.I. pipe/PVC sleeve of suitable higher size shall be
provided whenever the pipes are crossing the walls/floors and sealing the sleeves
with glass wool in between & fire sealant compound at either end all as per
Project Manager/Consultant requirement.

a) 150 mm dia RM R.O.


b) 100 mm dia RM 6
c) 80 mm dia RM R.O.
d) 65 mm dia RM 6
e) 50 mm dia RM 6
f) 40 mm dia RM 6
g) 32 mm dia RM 6
h) 25 mm dia RM 24

Notes :

i) Pipe upto 50 mm dia shall be threaded joints and above 50 mm shall be welded
joints.

ii) For pipe upto 50mm dia standard threaded forged steel fittings and for pipe
above 50mm dia and above standard of MS fittings with welded joints shall be
used.

iii) Supports are included in this items.

iv) G.I Pipe sleeve of suitable higher size shall be provided wherever pipes are
crossing the wall/ floors and sealing the sleeves with glass wool in between and
sealant compound at either end as per project manager's requirement.

4.0 Providing, fixing, testing and commissioning of 15 mm dia quartzoid bulb type
Stainless steel sprinkler head suitable to operate at 68 deg C (UL/FM listed
/approved)

a) Pendent Sprinkler 68°C (Standard Response) with rosette plate Each 10


b) Upright Sprinkler 680C (Standard Response) Each R.O.
c) Side wall Sprinkler 680C (Standard Response) with rosette plate Each R.O.
d) Pendent Sprinkler 68°C (Quick Response) with rosette plate Each R.O.
e) Upright Sprinkler 680C (Quick Response) Each R.O.
f) Side wall Sprinkler 680C (Quick Response) with rosette plate Each R.O.
g) Concealed Sprinkler 680C Each R.O.
h) Side wall sprinkler 680C (with extended coverage) Each R.O.

Notes :
a) All sprinklers shall be chrome finish / powder coated except for conceled.

b) The concealed sprinkler shall be brass finish. The cover plate of concealed
sprinkler shall be factory painted at manufacturers work and the shade be
conformed prior to application on the cover plate.

c) The sprinkler shall be either pendent or upright type/side wall and shall not be
universal style.
d) Contractor shall ensure provision of sprinkler guard at no additional cost

e) All pendent sprinkler will be provided with rosette plate

5.0 Providing, fixing, testing and commissioning of C.I. Butterfly valve with cast iron
body, cast iron disc and seat of EPDM rubber banded on bakelite with hard back
to PN 1.6 (16 kg /cm2 pressure rating) conforming to IS : 13095 with flanges, nut,
bolts and washers complete :-

a) 150 mm dia Each R.O.


b) 100 mm dia Each R.O.
c) 80 mm dia Each R.O.
d) 65 mm dia Each 4

12 Providing and fixing brass/bronze lever operated ball valves of full flow with stainless steel
ball (AISI 304 and spindle AISI 401) with settling and gland of superior quality and having
minimum working pressure of 15 Kg/cm2.

a) 25 mm dia Each R.O.


b) 32 mm dia Each R.O.
c) 40 mm dia Each R.O.
d) 50 mm dia Each R.O.

16 Supply, installation, testing & commissioning of Sprinkler Flexible Joint of 25mm


diameter, consisting of - Flexible Tube (SS 304), S.S. Slip nut, Isolated Ring & O
Ring - for Sprinklers Drop, which shall include necessary supports with a maximum
working pressure of 14kgf/cm2 and temperature rating of 225oF. The length of Flexible
Sprinklers Pipe shall be :-

a) 1000mm Nos. 5
b) 1200mm Nos. 5
c) 1500mm Nos. 5

TOTAL OF SPRINKLER SYSTEM CARRIED OVER TO SUMMARY


APL BOQ SUMMARY

SUMMARY OF COSTS FOR HVAC, ELECTRICAL, PLUMBING & FIRE FIGHTING


WORKS

S.NO. DESCRIPTION
AMOUNT
1 ELECTRICAL

1.1 Total Of MV Swetchgear Panel


1.2 Total of LT Cables & Earthing

1.3 Total of Point Wiring

1.4 Total of Fire Alarm System

2.0 Total of HVAC

3.0 Total of Plumbing

Grand Total

Note: GST shall be paid extra.

PROPOSED COMMERCAL BUILDING AT GURGOAN SEAL SIGNATURE OF BIDDER