PLAN SECTION
Anchor group area, Anc = 2121 * 2121 = 4,498,641 mm 2 ACI 17.4.2.1 -
Single anchor area, Anco = 9 hef2 = 9 * 957^2 = 8,242,641 mm 2 ACI Eq. (17.4.2.1c)
Single anchor strength, Nb = 10 sqrt(f'c)*hef1.5 = 1566.6 kN ACI Eq. (17.4.2.2a)
Eccentricity factor , Ψec = 1.00 (no eccentric load) ACI 17.4.2.4
Ca,min 685.5
Edge effects factor, Ψed = 0.7 + 0.3 = 0.7 + 0.3 = 0.84 ACI 17.4.2.5
1.5 hef 1.5 * 957
Cracking factor, Ψcn = 1.25 (Uncracked concrete at service load level) ACI 17.4.2.6
Anc
Breakout strength, Ncbg = Ψec Ψed Ψcn Ψcp Nb ACI Eq. (17.4.2.1b)
Anco
4498641
Ncbg = (1 * 0.84 * 1.25 * 1 * 1566.56)= 901.23 kN < 5771.39 kN
8242641
THE FACTORED TENSILE FORCE, N U EXCEEDS THE CONCRETE BREAKOUT STRENGTH OF THE ANCHORS;
THUS, ANCHORAGE REINFORCING BARS ARE REQUIRED!
Nu 5771.39
Breakout strength ratio = = = 8.54 ACI 17.3.1.1
Φ Ncbg 0.75 * 901.23
Bar strength ratio controls ( 0.96 < 8.54 ) 0.96 < 1.0 OK ACI 17.4.2.9
a) l dh = 463.64 mm
b) l dh = 8*db = 256 mm
c) l dh = 150 mm
Use, l dh = 464 mm < h'ef OK
2) Development length, l d ACI 18.8.5.1
a) l d = 1,159 mm
b) l d = 1,507 mm
Use, l d = 1,525 mm
Thus, Total embedment depth of Anchorage Reinforcement, l e; ACI 18.8.5.3
l e = l dh + l d
l e = 1,989 mm
say 2,000 mm
-Required Distance of Anchorage Reinf. Bars from the extreme edge of Anchor Bolts group,
0.50*hef = 479 mm
Furnished distance = 150 mm < 0.50*hef OK
Total Length = 5,050 mm for inverted U-Shape.