DESIGN CALCULATION
Effective Date
PROJECT :-
LOCATION :-
CLIENT:
M/s.
Page No. 4
PURPOSE
To analyse and design the anchor bolt as per the tensile and shear strength
REFERENCES
(1) Pvsyst report for the project configuration
(2) Module Data sheets
Check :
Vua/ϕVn = 0.85 > 0.2 (ACI 318-19, CL.17.8.3)
Nua/ϕNn = 0.29 > 0.2 (ACI 318-19, CL.17.8.3)
Distance of anchor from the concrete edge, ca1= 185 mm > 180 OK (ACI 318-19, Table 17.9.2(a))
Distance of anchor from the concrete edge, ca2= 185 mm > 180 OK (ACI 318-19, Table 17.9.2(a))
Spacing between anchors, s = 185 mm > 180 OK (ACI 318-19, Table 17.9.2(a))
< 1440 OK (ACI 318-19, CL.17.5.1.3.1) (Anchors will act as a group)
Modified hef = 123 mm (ACI 318-19, CL.17.6.2.1.2)
1.5hef = 720 mm
Area of the single anchor, ANco = 136900 mm2 (ACI 318-19, CL.17.6.2.1.4)
Nominal steel strength of anchor in tension, Nsa = 0.6*Ase,V*futa (ACI 318-19, CL.17.7.1.2(b))
= 88201.5975 N
= 88.20 kN > 75 kN OK
The lateral shear force is transferred from the anchors to the reinforcement by struts
Provide 25 mm vertical bars with 2-12 mm diamond ties in the top 127 mm. (ACI 318-19, CL.10.7.6.1.6)
The anchors furthest from the edge are subjected to 100% of the anchor force
Maximum projected area for the single anchor, Avco = 154012.5 mm2 (ACI 318-19, CL.17.7.2.1.3)
Total projected area of the anchor group, Avc = (ca2+s+ca2)*1.5ca1
= 308025 mm2 < 616050 OK (ACI 318-19, CL.17.7.2.1.1)
Load-bearing length of the anchor for shear,le = 240 mm (ACI 318-19, CL.17.7.2.2.1)
Basic single anchor breakout strength = 7*(le/da)^0.2*√da)*λa*√f'c*(ca1)^1.5 (ACI 318-19, CL.17.7.2.2.1a)
= 731146.258 N
Single anchor breakout strength = 9*λa*√f'c*ca1^1.5 (ACI 318-19, CL.17.7.2.2.1b)
= 113232.242 N
Vb = 113232.242 N (ACI 318-19, CL.17.7.2.2.1)
As the factored shear strength exceeds the concrete breakout strength, anchor reinforcement in shear is provided.
Column base plate anchor holes are usually oversized. For this condition, designer to assume the two anchors closest to theACI 318 permits the edge in the
direction of the shear force resist 1/2 the wind force, while the rear anchors are assumed not to be critical (Case 1)
The lateral shear force is transferred from the anchors to the reinforcement by struts
Provide 25 mm vertical bars with 2-12 mm diamond ties in the top 127 mm. (ACI 318-19, CL.10.7.6.1.6)
Check :
Vua/ϕVn = 0.85 > 0.2 (ACI 318-19, CL.17.8.3)
Nua/ϕNn = 0.29 > 0.2 (ACI 318-19, CL.17.8.3)
(Nua/ϕNn) + (Vua/ϕVn) = 1.15 < 1.2 OK
DESIGN OF ANCHOR BOLT