DANDRES

MOTOR INSULATION RESISTANCE


TEST REPORT

Project Name: Ammonia Package Glycol Chiller


Plant Name: Ginebra San Miguel
Location: Silangan Industrial Estate,Cabuyao,Laguna

MOTOR DATA

Unit Designation Compressor Motor


Equipment:
Speed (rpm) 3500 RPM
Volts 440V
FLA 110 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 250 MΩ
V1-G= 250 MΩ
MOTOR READINGS
W1-G= 250 MΩ
Remarks Passed

MOTOR DATA

Unit Designation Evaporative Condenser pump Motor


Equipment:
Speed (rpm) 1725 RPM
Volts 440V
FLA 4.34 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 70 MΩ
V1-G= 70 MΩ
MOTOR READINGS
W1-G= 70 MΩ
Remarks Passed

1|Page
MOTOR DATA

Unit Designation Evaporative Condenser Fan 1 and 2 Motor


Equipment:
Speed (rpm) 1725 RPM
Volts 440V
FLA 6.75 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 50 MΩ
V1-G= 50 MΩ
MOTOR READINGS
W1-G= 50 MΩ
Remarks Passed

MOTOR DATA

Unit Designation Primary Glycol pump no.1


Equipment:
Speed (rpm) 1735 RPM
Volts 440V
FLA 7.5 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 75 MΩ
V1-G= 75 MΩ
MOTOR READINGS
W1-G= 75 MΩ
Remarks Passed

2|Page
MOTOR DATA

Unit Designation Primary Glycol pump no.2


Equipment:
Speed (rpm) 1735 RPM
Volts 440V
FLA 7.5 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 75 MΩ
V1-G= 75 MΩ
MOTOR READINGS
W1-G= 75 MΩ
Remarks Passed

MOTOR DATA

Unit Designation Secondary Glycol pump no.1


Equipment:
Speed (rpm) 1745 RPM
Volts 440V
FLA 10 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 55 MΩ
V1-G= 55 MΩ
MOTOR READINGS
W1-G= 55 MΩ
Remarks Passed

3|Page
MOTOR DATA

Unit Designation Secondary Glycol pump no.2


Equipment:
Speed (rpm) 1745 RPM
Volts 440V
FLA 10 Amps
Phase 3~
Hertz 60 Hz
Date: Sep. 26,2022
Insulation Resistance (Mega-Ohms at 1000V,2000MΩ)

U1-G= 55 MΩ
V1-G= 55 MΩ
MOTOR READINGS
W1-G= 55 MΩ
Remarks Passed

INSULATION RESISTANCE TEST REPORT


ACCEPTANCE
COMPRESSOR UNIT /EVAPORATIVE PUMP AND FANS/ PRIMARY AND
SECONDARY PUMPS

Prepared and Conducted By: Witnessed and Accepted By:

Eugene, Mejidana ___________________________


DANDRES

Signature and Date: Signature and Date:

___________________________ ___________________________

4|Page