ASSESMENT DATE
24/07/2023
Assessor
Date of assessment
Previous assessment
1. The Premises
2. Occupants and Users
3. Occupants Especially at Risk from fire
4. Fire loss Experience
5. Other Information
6. Relevant Fire Safety Legislation
7. Sources of Ignition (Electrical)
8. Smoking
9. Arson
10. Portable heaters and heating Installation
11. Cooking
12. Lightning
13. House keeping
14. Building works and Contractors on premises
15. Dangerous Substances
16. Significant Fire Hazards that warrant consideration including process hazard that impact on
general fire precautions
17. Means of Escape from fire
18. Measures to Limit fire spread and development
19. Emergency escape lightning
20. Fire safety signs and notices
21. Means of giving
iving warning in case of fire
22. Manual fire extinguisher
23. Automatic fire extinguisher system
24. Fixed system and equipment
25. Arrangements and procedure
26. Training and drills
27. Testing and Maintaince
28. Records
29. Fire Risk Assessment analysis
30. Action plan
The purpose of this report is to provide an assessment of the risk to life ffrom
rom fire in these premises
and where appropriate to make recommendation to ensure compliance with fire legislation.
This report does not address the risk to property or business continuity from fire.
The assessors believe the information contained within this risk assessment report to be correct at
the time of printing. The assessors do not accept responsibility for any consequences arising from
the use of the information herein. It does not include any areas, activities or processes that the
assessor was not made aware or could not gain access to whilst on site. The report is based on
matters which were observed or came to the attention of the assessors during the day of the
assessment and should not be relied upon as an Exhaustive record of all possible risks
r or hazards
that may exist or potential improvements that can be made.
It should not be assumed that the omission of any area of the premises from this report should be
considered as compliance with legislative requirements appertaining to that part of the premises.
1 THE PREMISES
Loft-2 Rooms
2. OCCUPANTS
Guest(Sleeping Occupants) 10
0
Young Persons N/A
Disabled Occupants N/A
Contractors 0
Others 0
*AS APPLICABLE
PAS 79 2012 FIRE RISK ASSESMENT GUIDANCE
SOURCES OF IGNITION
ELECTRICAL
REASONABLE MEASURE NO
TAKEN TO PREVENT
FIRES OF ELECTRICAL
ORIGIN
FIXED WIRING NO
INSTALLATION
PORTABLE APPLAINCES NO
TEST
SUITBLE POLICY NO
REGARDING USE OF
PERSONAL ELECTRICAL
APPLIANCES
SUITABLE LIMITATION
TION NO
OF TRAILING LEADS OR
ADAPTOR
Comments
ELECTRICAL INSTALLATION CONDITION REPORT REQUIRED FOR
PREMISES
LOSE WIRING AT PREMISES, REQUIRE A QUALIFIED ELECTRICIAN
TO RECTIFY AND ISSUE AND EICR TO STATE ELECTRICAL
INSTALLATION IS SAFE TO USE AT PREMISES
PREMISES.
REASONABLE NO
MEASURE FOR FIRE
PREVENTION
SMOKING YES SIGNAGE REQUIRED
PROHIBITED IN
BUILDING
SMOKING AREA NO
AVAILABLE
COMMENTS
REASONABLE NO
MEASURE FOR
FIRE
PREVENTION
CANOPY N/A
CLEANED
EXTRACTOR
WORKING
SUITABLE FIRE NO
EXTINGUISHER
AVAILABLE
Comments
Comments
Cleaning material stored on premises
Fire safety NO
conditions
imposed on
outside
contractors
NOT APPLICABLE
N/A
SUITABLE PROTECTION O
OF NO
ESCAPE ROUTE
SUITABLE FIRE PRECAUTION FOR NO
INNER ROOMS
ESCAPE ROUTES UNOBSTRUCTED YES
REASONABLE ARRANGEMENTS N/A
FOR MEANS OF ESCAPE FOR
DISABLED PEOPLE
COMMENTS
18-Measures
Measures to Limit fire spread and development
Comments
FIRE DELAY DOORS REQUIRED AT PROPERTY
FD 30 DOORS ARE REQUIRED
Door frames has a gap of more than 3mm
Note
Doors Do Not Meet British Standard Bs4787 Ie Fd30s 30 Minutes Fire
Protection From Both Sides Of The Door , Complete With Fire Door
Furniture 3*100mm Fire Rated Steel Hinges
Hinges,, Intumescent Strip, Cold
Smoke Seal
COMMENTS
Fire
re safety signs and notices required at premises
COMMENT
23-AUTOMATIC
AUTOMATIC FIRE EXTINGUISHING SYSTEM
SYSTEM-----NOT
NOT APPLICABLE
24-FIXED
FIXED SYSTEM AND EQUIPMENT
EQUIPMENT—NOT
NOT APPLICABLE
MOHAMAD AUJOYEB
COMMENTS
28-RECORDS
FIRE DRILLS NO
FIRE TRAINING NO
29-PRELIMINARY
PRELIMINARY FIRE RISK ASSESMENT ANALAYS
Taking into account the nature of the building and the occupant as well as
fire protection and procedural arrangements observed at time of risk
assessment it is considered that the consequences for life safety in event of
fire would be
(MODERATE HARM)
MODERATE HARM
HARM: OUTBREAK OF FIRE COULD FORESEEABLY RESULT
IN INJURY(INCLUDING SERIOUS INJURY)OF ONE OR MORE OCCUPANTS, BUT
IS UNLIKELY TO INVOLVE MULTIPLE FATALITIES
Comments
Comments:
The current fire safety arrangements needs improvement and are not
satisfactory as can be seen in fire Action plan below
DEFINATION OF PRIORITIES
HIGH
MEDIUM
LOW
RESPONSIBLE PERSON
NITISH CHABRA
7-Electrical Sources of (HIGH) NITISH CHABRA ASAP
Ignition
ELECTRICAL
INSTALLATION
CONDITION
REPORT
REQUIRED FOR
PREMISES
LOSE WIRING
AT PREMISES,
REQUIRE A
QUALIFIED
ELECTRICIAN
TO RECTIFY
AND ISSUE
AND EICR TO
STATE
ELECTRICAL
INSTALLATION
IS SAFE TO USE
AT PREMISES.
GAS SAFETY
CERTIFICATE
REQUIRED TO
ENSURE ALL
GAS
APPLIANCES
ARE SAFE TO
USE
12-LIGHTNING NIL
15DANGEROUSSUBSTNCE NIL
18-Measures to (HIGH
HIGH)
Limit fire spread
and development UPGRADE
REQUIRED IN
TERMS OF
ESCAPE ROUTE
SIGNAGE ROOMS
NEEDS FIRE
DOORS (FD30)
SAFE
EVACUATION
PLAN NEED TO
BE
IMPLEMENTED
FOR RESIDENT IN
OUTHOUSE AS
IN EVENT OF FIRE
THEY SHOULD
NOT ENTER
MAIN BUILDING
FD30s 30
minutes fire
protection from
both sides of the
Room partition
from kitchen is
done by plywood
need to be
segregated by
fire rated wood
Room next to
kitchen has an
open able
window in
corridor
Understairs
utility area needs
to be protected
by fire rated
utility cupboard
Electrical
consumer uni
units
in room need a
fire rated
cupboard
FIRE DELAY
DOORS
REQUIRED AT
PROPERTY
FD 30 DOORS
ARE REQUIRED
FIRE DOORS
British standard
BS4787 ie FD30s
30 minutes fire
protection from
both sides of the
door , complete
with fire door
furniture
3*100mm fire
rated steel
hinges,
intumescent
strip, cold smoke
(HIGH)
(HIGH)
INTERLINKED
FIRE ALARAM
AND HEAT
DETECTOR WITH
SOUNDER AS
AND GLASS
BREAK POINT
REQUIRED IN
PREMISES
COMPLYING
Clause 45 of BS
5839
5839-1:2017
ADDITIONAL LINK
REQUIRED
BETWEEN MAIN
BUILDING AND
REAR OUTHOUSE
WITH SUITABLE
SYSTEM TO
ALERT RESIDENT
IN EVENT OF FIRE
(HIGH)
22- MANUAL FIRE Reasonable NITISH CHABRA ASAP
EXTINGUISHING provision of
SAFE
EVACUALTION
PLAN NEEDS TO
BE IMPLEMENTED
FOR RESIDENT IN
OUT HOUSE FLAT
IN EVENT OF FIRE
(HIGH)
ANNUAL
MAINTANACE OF
FIRE
EXTINGUISGER