BEL 600-2 smoke exhaust duct


according to DIN 12101, Part 7
Set 1
BEL 600-2
with flat flanges

Set 2
BEL 600-2 with
adapter duct parts
Declaration of Performance 01/16
Type BEL 600-2 smoke exhaust duct DoP Bohl BEL 600-2

This document is issued in accordance with the EU Regulation no. 305/2011 of 9 March 2011 as the EU Construction Products
Regulation, as published in the EU Gazette, and the corresponding Amending Regulations (EU) no. 568/2014 of 18 February 2014
and (EU) no. 574/2014 of 21 February 2014 and the corrigendum L92/118 in the EU Gazette of 8 April 2015 on the
EU Regulations no. 568/2014.

1. Unambiguous identification code Bohl BEL 600–2 with accessories


Bohl compensator type BWK 600-2

2. Intended purpose Smoke extractor duct for individual sections


according to Figure 3.14 of the harmonised
technical specification DIN EN 12101-7: 2011-8 –
in rectangular form.

3.Name and contact address of the manufacturer Bohl GmbH


Rudolf-Diesel-Straße 3 · D-74124 Schöntal
info@bohl.eu

4. Authorised representative Currently not named

5. System for reviewing and assessing constancy of System 1


performance

6. Harmonised standard and notified office Harmonised standard: DIN EN 12101-7:2011-08


Notified office: No. 0761 - MPA Braunschweig,
Beethovenstraße 52, D-38106 Braunschweig

7. Essential characteristics
Declared overall performance (for ducts up to max. cross-section 1,250 mm x 1,000 mm) according to
the harmonised technical specification DIN EN 12101-7:2011-8 with individual verification according to
Figure 5.2.2 of the technical specification.

E600120(ho)S1500single
A declaration is provided of the following individual performances under Fig. 4.1.2 of the above-mentioned
technical specification:

Room closure E according to Fig. 4.1.2 - a): 120 minutes fulfilled

Smoke-tightness S according to Fig. 4.1.2 - b): 120 minutes fulfilled

Mechanical stability of form (E) and maintenance of according to Fig. 4.1.2 - c) and d) of the Technical
cross-section (E) Specification DIN 12101-7: 2011-8, as given in
the above sub-categories c)/d), each proven in the
evidence of the above performance “Room closure”
– i.e. fulfilled for 120 minutes.

The performance of the above product constantly corresponds to the declared performances, if, in further assembly and in further opera-
tion, the information provided in our separate assembly and operating instructions in the version valid at the time of assembly is followed.
Only the manufacturer mentioned above under Fig. 4 of this Declaration of Performance is responsible for preparing the Declaration of
Performance in accordance with Regulation (EU) no. 305/2011.

Signed for the manufacturer and in the name of the manufacturer by


Bohl Befestigungssysteme - klimatechnisches Zubehör GmbH:

Werner Ehrler, Managing Director


BEL 600-2 smoke exhaust duct

Smoke exhaust ducting in general

The Bohl BEL 600-2 smoke exhaust duct is a complete system According to the test carried out, the maximum edge length of the
for the removal of smoke from individual sections according to duct is 1250 x 1000 mm. In the system, an underpressure of up to
DIN EN 12101-7: 2011 and for installation in a horizontal direction. 1500 Pa and an overpressure of max. 500 Pa are allowed. The smoke
Testing was carried out at 600°C over a period of 120 minutes by exhaust duct comprises ducting and shaped pieces in galvanised steel
MPA Braunschweig. The results are summarised in the corresponding sheet, multilayer fabric compensators and temperature-resistant
test report no. 3027/614/11, the certificate of constancy of ceramic fibre sealing strips. The smoke exhaust duct parts are
performance (0761-CPR-0354) and the classification report provided with a CE mark and the compensators bear a reference to
(K-3327/44/13-MPA BS). the certificate.

Technical data

Duct parts in 1 mm beaded galvanised steel sheet, Available accessories n C rails with threaded rods
30 mm air duct profile n Ceramic fibre tape

n Thread clips
Compensator multiple layers of fabric
n Fixing material
Flange 30 mm x 6 mm based on DIN 24193
Simple mounting of Because of the multilayer construction,
Series 2
compensator no special flanges, guide rods or
Tested quality Function maintained 120 min 600°C – support rings are necessary
certificate of constancy of performance
Premounted In connection with adapter ducts
by MPA Braunschweig
compensator (set2), connection is via corner screws
Classification Smoke exhaust duct in and thread clips
individual sections
Dimensions Individual dimensions up to
Classification of fire max. 1250 mm x 1000 mm available
resistance E600 120 (h0)S1500single
Designation CE designation according to Regulation
(EU) no. 305/2011 (Construction
products regulation) with DIN EN 13501-
4: 2010-01 and DIN EN 12101-7

Dimensions and options (without and with duct support)


up to max.1000 mm

Duct support

up to max.630 mm < 1500 mm max.1250 mm < 1000 mm


up to max.1000 mm

Duct support

Duct support

up to max.1250 mm < 500 mm max.1250 mm 1001–1500 mm


BEL 600-2 smoke exhaust duct

Assembly

Beyond the instructions provided here, assembly must be carried out in accordance with the locally relevant guidelines, the
standards and provisions of the law. Assembly may only be carried out by trained, instructed specialist personnel. The provisions
of these instructions and any other instructions for the assembly of components and fixing material must be followed.

Suspension of smoke exhaust duct Connecting the components

The horizontal ducts must be mounted with unclad steel structures The sheet metal ducts are connected with screws DIN 933 M
(mounting brackets). For this, the ducts are to be supported on 8 x 35 mm, washers DIN 125 at the corners and connecting clips
cross-pieces made from C profiles 30/30/1.5 mm. max. 200 mm apart. The individual components are sealed with a
The fixing structure must be designed in such a way that the ceramic fibre tape (Bohl Fiberfrax 15 x 6 mm). The compensator is
mathematical tensile stress does not exceed 6N/mm². screwed to the air duct profile with a flat flange 30 x 6 mm.
The mathematical shear stress may not exceed 10N/mm².
The mounting brackets are made from M8 threaded steel rods
according to DIN 975, a large-diameter washer as specified in
DIN 9021 and M8 nuts as specified in DIN 934. The bearing
structure must be fixed to solid construction elements in fire
resistance class F90 using steel expansion plugs ≥ M 8. The plugs
must comply with the requirements of valid approvals and also be
installed twice as deep as required in the approval, and at least 60
mm deep. Alternatively, plugs may be used for which it has been
demonstrated in fire tests that they can absorb the extraction forces
resulting from the structural loading calculation for a fire resistance
duration of more than 90 minutes.
The mounting brackets must be mounted for every shaped piece and
before and after the compensator at the same height with a max.
height difference of ± 20 mm. Suspension from the ceiling shall be
Compensator
at a clear distance of max. 1500 mm using cross-pieces 30 x 30 mm
and threaded rods as specified in DIN 975 M10 and the appropriate To balance out duct expansion and to prevent any horizontal forces
DIN 934 nuts and washers as specified in DIN 9021. The mounting caused by this, fabric expansion joints must be installed in smoke
bracket must be fixed with a side distance of max. 50 mm. exhaust ducts. With ducts with a length of ≥ 5 m between walls,
a compensator must be installed. The maximum distance between
the compensators may not exceed 10 m. If the ducting changes
direction, the possibility of installing the compensators closer tog-
ether should be considered.

Compensator Compensator
max.1500 mm

50 mm 50 mm max. 10000 mm

Subject to technical changes


Befestigungssysteme -
klimatechnisches Zubehör
GmbH

Our range of HVAC accessories


■ Ventilation hoses ■ Air filter mats ■ Filter pads ■ Ventilation valves ■ Damper
Bohl actuators ■ ELAV elastic connections ■ ELAS elastic strips ■ Weather protection
Befestigungssysteme – grilles ■ Louvre dampers ■ Inspection covers ■ Sealing strips ■ Cold shrink tapes
klimatechnisches Zubehör ■ Duct sealing tapes ■ Sealants ■ Tools

GmbH
Our range of fixing systems for technical insulation
Rudolf-Diesel-Straße 3 ■ Bohl GS 100accu+/Bohl GH 950 stud welding equipment ■ Clip-Pin insulating
D-74214 Schöntal welding pins ■ Drawn-arch welding pins ■ other welding pins ■ Lock washers
Phone +49 (0)7943 / 944889-0 ■ Protective caps ■ CLAVU-fix self-adhesive pins ■ CLAVU-por fixing pins with
Fax +49 (0)7943 / 944889-889 perforated base plate ■ Insulation fixing ■ Insulation manufacture ■ Marking
www.bohl.eu · info@bohl.eu according to DIN requirements

You might also like