PROPOSED CAPITOL TWINPEAKS CONDOMINIUM

DEVELOPMENT, COLOMBO 2.
DETAIL DESIGN DRAWINGS
ISSUE 03
JANUARY 2017

STRUCTURAL LIST OF DRAWINGS

DRAWING NO. DRAWING TITLE REV 00. (DATE)

16004-S00 COVER SHEET & LIST OF DRAWINGS 00 ( 31-01-2017)

16004-S3.201 R/F DETAILS OF LIFT TOWER 1 (BASEMENT 2 TO LEVEL 9) 00 ( 31-01-2017)

16004-S3.202 R/F DETAILS OF LIFT TOWER 1 (LEVEL 10 TO LEVEL 20) 00 ( 31-01-2017)

16004-S3.203 R/F DETAILS OF LIFT TOWER 1 (LEVEL 21 TO LEVEL 30) 00 ( 31-01-2017)

16004-S3.204 R/F DETAILS OF LIFT TOWER 1 (LEVEL 31 TO LEVEL 40) 00 ( 31-01-2017)

16004-S3.205 R/F DETAILS OF LIFT TOWER 1 (LEVEL 41 TO LEVEL 50) 00 ( 31-01-2017)

16004-S3.206 R/F DETAILS OF LIFT TOWER 2 (LEVEL BASEMENT 2 TO LEVEL 9) 00 ( 31-01-2017)

16004-S3.207 R/F DETAILS OF LIFT TOWER 2 (LEVEL 10 TO LEVEL 20) 00 ( 31-01-2017)

16004-S3.208 R/F DETAILS OF LIFT TOWER 2 (LEVEL 21 TO LEVEL 30) 00 ( 31-01-2017)

16004-S3.209 R/F DETAILS OF LIFT TOWER 2 (LEVEL 31 TO LEVEL 40) 00 ( 31-01-2017)

16004-S3.210 R/F DETAILS OF LIFT TOWER 2 (LEVEL 41 TO LEVEL 50) 00 ( 31-01-2017)

16004-S3.301 REINFORCEMENT DETAILS OF COLUMNS (SHEET 1) 00 ( 31-01-2017)

16004-S3.302 REINFORCEMENT DETAILS OF COLUMNS (SHEET 2) 00 ( 31-01-2017)

16004-S3.303 REINFORCEMENT DETAILS OF COLUMNS (SHEET 3) 00 ( 31-01-2017)

16004-S3.304 REINFORCEMENT DETAILS OF COLUMNS (SHEET 4) 00 ( 31-01-2017)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING
COVER SHEET & LIST OF DRAWINGS
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED CAPITOL TWINPEAKS CONDOMINIUM DEVELOPMENT, COLOMBO 2.
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : Prof.PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S00 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2 W2

UNLESS OTHERWISE INDICATED:-


T16-C-200 T16-B-200 T16-C-200 T16-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T16 AT 200 CTS.
A A A A 3. LINKS SHALL BE T8 BASE 8mm
4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

850

850
5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
LINKS BEND AT SITE FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B C B
6. CONCRETE GRADE SHALL BE C70

150
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T16-A-200(`U' BAR) T16-A-200(`U' BAR) 100 SHALL BE USED.

150
T16-E-200
E F
LINK DETAILS

W1
W1
D F LONGITUDINAL WALL BARS NOTE - 1
2xW1 850 T16-D-200

35Ø
T16-F-200(`U' BAR)
1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
HEIGHT.
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION LINK ARRANGEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

2 2 (PLAN) STAGGER ALTERNATE BARS. BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE
AREA (INCLUDING SPLICES), THE BARS MUST BE
MECHANICALLY SPLICED.
T16-35-200 T16-47-200 3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
1300 850 850 1300
850 T16-41-200 T16-42-200 850 OF THE SPECIFIED BAR YIELD CAPACITY.
3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32
3T32

3T32

3T32

3T32
3T32

3T32

3T32

3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32
4. CLEAR DISTANCE BETWEEN A CONTACT LAP

SEE NOTE 1
33 41 36 46 41 48
SPLICE AND ADJACENT BARS SHALL BE NOT LESS
42 35 47 42 THAN 1.5 TIMES THE BAR DIAMETER NOR.

3T32 2T32 2T32 3T32 850 40 36 46 40 850

850

850
3T32 2T32 2T32 3T32 T16-37-200 T16-40-200 T16-43-200 T16-46-200 TOP OF SLAB NOTE - 2
T16-36-200

750

750

750

750
2T32 3T32 T16-33-200 T16-48-200
3T32 2T32 FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S
3T32 2T32 2T32 3T32 35 T16-34-200 T16-49-200 47 DRAWINGS.
3T32 2T32 2T32 3T32
31 32 31 38 38 44 44 51 50 51
3T32 2T20 2T20 3T32
WALL
3T25 2T20 2T20 3T25

850

850

850

850
3T25 2T20 2T20 3T25

3T25 2T20 2T20 3T25

3T25 2T20 2T20 3T25 34 33 34 37 37 43 43 49 48 49 TYPICAL MECHANICAL SPLICE DETAIL


3T32 2T20 2T20 3T32

3T32 2T32 2T32 3T32 T16-32-200 T16-50-200


3T32 2T32 2T32 3T32

3T32 2T32 2T32 3T32

3T32 2T32 2T32 3T32 T16-31-200 T16-30-200 T16-38-200 T16-39-200 T16-44-200 T16-45-200 T16-52-200 T16-51-200

3T32 2T32 2T32 3T32 30 39 45 52


3T32 3T32 30 39 45 52
3T32 3T32
32 50
2T32

2T32
2T32
2T32

2T32
2T32
2T32

2T32

2T32

2T32
2T32

2T32

2T32
2T32
2T32

2T32
2T32
2T32
2T32

2T32
2T32

2T32

2T32

2T32
2T32
2T32

2T32
2T32
2T32

2T32
C C
750 750

A SIMILAR DIAMETER
REINFORCEMENT

52XØ
Z

T16@150
T16@200
300x800x150 RECESS

Y
100Ø HOLE

T16-26-200 T12-27-200 A

52XØ
1300 850
850
2T32

2T32
2T32

2T32

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T32

2T32

2T32
2T32
2T32

2T32

X
25 27 26
3T32 2T32 3T32

3T32 2T32 3T32

3T32 2T32 2T32 3T32 27 26

900
850
3T32 2T32 2T32 3T32 T16-28-200 T12-19-200 T16-17-200
2T32 3T32
3T32 2T32

900
2T32 T16-18-200
3T32 T16-25-200 18
3T32

3T32
2T32

2T32
2T32
3T32 28 16 15 14
SECTION A-A
2T32
3T32
2T32
3T32 T16-24-200 28
19
TYPICAL ELEVATION OF
3T32 3T32 22 23 22

850
3T25 3T25
19 HOLD CALL BUTTON
3T25
3T25 850
3T25 17 18 17
3T25

3T25 3T25

3T25 24 25 24 AS SHOWN
2T32
3T32
3T25 2T32 B/F C
3T32 29
2T32 3T25 29

600
3T32
2T32
3T32 2T32 3T25
2T32 D
C
2T32 3T25 T16-23-200
3T32
2T32 T16-29-200

600
3T32 2T32 3T25
2T32 T16-22-200 OPENING
3T32 2T32 3T25 20 21 D
2T32
3T32 2T32 3T25
2T32 2T32

3T32 2T32 3T25


2T20
23 20 21
SECTION X-X
2T32

2T32
2T32

2T32

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T32

2T32

2T32
2T32

3T25 850
2T20
3T25 1300 850 AS PER PLAN
2T20
3T25 T16-21-200 T12-20-200

0
80

80
2T20

0
3T25 T16-15-200
2T20
3T25 1700 X 1700 FLOOR LEVEL
2T20 T12-09-200 2T32 B/F
T16-16-200 T16-14-200
3T25

T16 AT 200 CTS.


2T20

0
80

600

80
0
3T25
2T20 T16 AT 150 B/F

lap

H
3T25 T16 AT 200 B/F
2T20
3T25
2T20
3T25 13 12 13
2T20 80

0
0

80
2T20 3T25 2T32 B/F
08 08

850
2T20

H/2
3T25 2T20 B/F
2T20 3T25 TYP. X
01 80

850
0

0
80
2T20 3T25
3T40 16 15 14 AS PER PLAN
2T20 01
3T32
3T40
T16-01-200 T16-13-200 T16-12-200 OPENING
2T20 3T32
3T40 09 09
850

2T32 B/F 2T32 B/F


2T32 3T32 04 10
3T40

900
2T32 3T32 T16-02-200 T16-08-200
3T40 T16-11-200
600
T16-03-200
2T32 3T32 T16-05-200 T16-10-200
02
850

850
3T40 T16-04-200
2T32 3T32
3T40 05 03 11 05
3T40 3T32
07 04 10 07
3T40 3T32
FLOOR LEVEL
3T40 3T32
B B 2T32 B/F
3T32

3T32

3T32

3T32

3T32

3T32

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32
3T32

3T32

3T32
3T32

3T32
3T32

3T32

3T32

3T32

3T25

3T25

3T25
3T25

3T25

3T32

3T32

3T32

3T32

3T32
3T32

850 02 06 03 11 06 12 850
AS SHOWN
1300 850 850 1300
T16-06-200 T16-07-200

- VERTICAL BAR ARRANGEMENT OF LIFT- TOWER 1 - HORIZONTAL BAR ARRANGEMENT OF LIFT - TOWER 1 TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL
-
- Scale: 1:30
(BASEMENT 2 TO LEVEL 9) Scale: 1:30 (BASEMENT 2 TO LEVEL 9)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING
R/F DETAILS OF LIFT-TOWER 1
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. (BASEMENT 2 TO LEVEL 9)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.201 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2 W2

UNLESS OTHERWISE INDICATED:-


T16-C-200 T16-B-200 T16-C-200 T16-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T16/ T12 AT 200 CTS.
A A A A 3. LINKS SHALL BE T8 BASE 8mm
4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

850

850
5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
LINKS BEND AT SITE FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B C B
6. CONCRETE GRADE SHALL BE C35

150
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T16-A-200(`U' BAR) T16-A-200(`U' BAR) 100 SHALL BE USED.

150
T16-E-200
E F
LINK DETAILS

W1
W1
D F LONGITUDINAL WALL BARS NOTE - 1
2xW1 850 T16-D-200

35Ø
T16-F-200(`U' BAR)
1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
HEIGHT.
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION LINK ARRANGEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

2 2 (PLAN) STAGGER ALTERNATE BARS. BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE
AREA (INCLUDING SPLICES), THE BARS MUST BE
MECHANICALLY SPLICED.
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
1300 650 850 1300
T16-29-200 OF THE SPECIFIED BAR YIELD CAPACITY.
3T32

2T32

3T32

2T32

2T32

2T32

2T32

2T32

2T32

2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32
2T32

2T32

2T32

2T32
2T32

2T32

2T32

2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32
2T32
2T32

2T32

2T32

2T32

2T32

2T32

2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32

3T32
2T32

3T32
4. CLEAR DISTANCE BETWEEN A CONTACT LAP

SEE NOTE 1
29 24 33 29
SPLICE AND ADJACENT BARS SHALL BE NOT LESS
THAN 1.5 TIMES THE BAR DIAMETER NOR.

2T32 2T32 2T32 2T32 850 28 24 33 28 850


2T32 2T32 2T32 T12-25-200 T16-28-200 T12-30-200 T16-33-200 TOP OF SLAB NOTE - 2
2T32
T16-24-200

750

750

750

750
2T32 2T32 2T32 2T32 FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S
2T32 2T32 2T32 2T32 DRAWINGS.
T16-23-200 T16-34-200
2T32 2T32 2T32 2T32
22 22 26 26 31 31 35 35
2T32 2T20 2T20 2T32
WALL

650

650
2T25 2T20 2T20 2T25

850

850
2T25 2T20 2T20 2T25

2T25 2T20 2T20 2T25


25 25 30 30

2T25 2T20 2T20 2T25 23 23 34 34 TYPICAL MECHANICAL SPLICE DETAIL


2T32 2T20 2T20 2T32

2T32 2T32 2T32 2T32

2T32 2T32 2T32 2T32

2T32 2T32 2T32 2T32

2T32 2T32 2T32 2T32 T16-22-200 T12-21-200 T12-26-200 T12-27-200 T12-31-200 T12-32-200 T12-36-200 T16-35-200
2T32 2T32 2T32 2T32 21 27 32 36
2T32 2T32 21 27 32 36
3T32 3T32
2T32

2T32
2T32
2T32

2T32
2T32
2T32

2T32

2T32

2T32

2T32
2T32

2T32
2T32
2T32

2T32
2T32
2T32
2T32

2T32
2T32

2T32

2T32

2T32
2T32
2T32

2T32
2T32
2T32

2T32
C C

A SIMILAR DIAMETER
REINFORCEMENT

52XØ
Z

T16@150
T16@200
300x800x150 RECESS

Y
100Ø HOLE

T12-17-200 T12-18-200 A

52XØ
1300 650
2T32

2T32
2T32

2T32

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T32

2T32

2T32
2T32

X
18 17
3T32 2T32 2T32 3T32

2T32 2T32 2T32 2T32

2T32 2T32 2T32 2T32 18 17

900
2T32 2T32 2T32 2T32 T12-19-200 T12-12-200 T16-11-200
2T32 2T32
2T32 2T32

900
2T32
2T32
2T32

2T32
2T32

2T32
2T32
2T32 19 10 09
SECTION A-A
2T32
2T32
2T32
2T32 T16-16-200 19
12
TYPICAL ELEVATION OF
2T25 2T32 15 15
HOLD CALL BUTTON

850
12
2T25 2T25

2T25

850
2T25

2T25 2T25 11 11

2T25 2T25

2T25 16 16 AS SHOWN
2T25
2T25 2T32 B/F 2T32
2T32 20
C
2T32 2T32 2T25 20
2T32

600
2T32 2T32 2T25
2T32
2T32 2T25 T16-15-200
2T32 D
2T32 T12-20-200 C
2T32 2T32 2T25
2T32 OPENING

600
2T32 2T32 2T25 13 14
2T32
2T32 2T32 2T25 D
2T32
3T32 2T32 2T25
2T32
2T20
2T32

2T32
2T32

2T32

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T32

2T32

2T32
2T32

2T25 13 14
2T20

2T20
2T25 1300 650
SECTION X-X
2T25 T12-14-200 T12-13-200 0 AS PER PLAN
80

80
2T20

0
2T25
2T20
2T25 1700 X 1700 FLOOR LEVEL
2T20 T12-06-200 2T32 B/F
2T25
T16-10-200 T16-09-200
2T20 0
80

80

600
0
2T25
2T20 T16 AT 150 B/F

T12 AT 200 CTS.


2T25 T16 AT 200 B/F
2T20
2T25

lap

H
2T20
2T25 08 08
2T20

80
80
2T25

0
2T20 2T32 B/F

850
2T20 2T25 2T20 B/F
2T20 2T25
05 05 TYP.
X
01 0

H/2
80

80
2T20

0
2T25 10 09

650
3T32
2T20 01
2T32
2T32
T16-01-200 OPENING
AS PER PLAN
2T20 2T32
2T32 06 06 T16-08-200
2T32 B/F 2T32 B/F
2T32 2T32
2T32

900
2T32 2T32 T12-05-200
2T32 T16-07-200

600
T16-02-200
2T32 2T32 T16-03-200
2T32
2T32 2T32
2T32 03 02 07 03
3T32 3T32

2T32 2T32
FLOOR LEVEL
3T32 3T32
B B 2T32 B/F
2T32

2T32
2T32

2T32

2T32

2T32

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32
2T32

2T32

2T32

2T32

2T32
2T32

2T32

2T32

2T32

2T25

2T25

2T25
2T25

2T25

2T32

2T32

2T32

2T32

2T32
2T32

04 02 07 04
AS SHOWN
1300 850 850 1300
T16-04-200

- VERTICAL BAR ARRANGEMENT OF LIFT- TOWER 1


-
Scale: 1:30 - HORIZONTAL BAR ARRANGEMENT OF LIFT - TOWER 1 TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL
(LEVEL 10 TO LEVEL 20) -
Scale: 1:30
(LEVEL 10 TO LEVEL 20)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 1
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. (LEVEL 10 TO LEVEL 20)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.202 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2 W2

UNLESS OTHERWISE INDICATED:-


T12-C-200 T12-B-200 T12-C-200 T12-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T12 AT 200 CTS.
3. LINKS SHALL BE T8 BASE 8mm
A A A A 4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

650

650
5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
LINKS BEND AT SITE FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B C B
6. CONCRETE GRADE SHALL BE C30

150
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T12-A-200(`U' BAR) T12-A-200(`U' BAR) 100 SHALL BE USED.

150
T12-E-200
E F
LINK DETAILS

W1
W1
D F LONGITUDINAL WALL BARS NOTE - 1
2xW1 650 T12-D-200

35Ø
T12-F-200(`U' BAR)
1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
HEIGHT.
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION LINK ARRANGEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
OF SMALLER BAR). WHEN TOTAL LONGITUDINAL
2 2 (PLAN) STAGGER ALTERNATE BARS. BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE
AREA (INCLUDING SPLICES), THE BARS MUST BE
MECHANICALLY SPLICED.
1300 650 650 1300
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
T12-29-200 OF THE SPECIFIED BAR YIELD CAPACITY.
3T25

2T25

3T25

2T25

2T25

2T25

2T25

2T25

2T25

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25

2T25
2T25

2T25

2T25

2T25

2T25
2T25

2T25

2T25

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25

2T25
2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25

3T25

2T25

3T25
4. CLEAR DISTANCE BETWEEN A CONTACT LAP

SEE NOTE 1
29 24 33 29
SPLICE AND ADJACENT BARS SHALL BE NOT LESS
THAN 1.5 TIMES THE BAR DIAMETER NOR.

2T25 2T25 2T25 2T25 850 28 24 33 28 850


2T25 2T25 2T25 2T25 T12-25-200 T12-28-200 T12-30-200 T12-33-200 TOP OF SLAB NOTE - 2
T12-24-200

750

750
750

750
2T25 2T25 2T25 2T25
FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S
2T25 2T25 2T25 2T25 T12-23-200 T12-34-200 DRAWINGS.
2T25 2T25 2T25 2T25
22 22 26 26 31 31 35 35
2T25 2T20 2T20 2T25
WALL

650

650

650

650
2T20 2T20 2T20 2T20

2T20 2T20 2T20 2T20

2T20 2T20 2T20 2T20


23 23 25 25 30 30 34 34

2T20 2T20 2T20 2T20 TYPICAL MECHANICAL SPLICE DETAIL


2T25 2T20 2T20 2T25

2T25 2T25 2T25 2T25

2T25 2T25 2T25 2T25

2T25 2T25 2T25 2T25

2T25 2T25 2T25 2T25 T12-22-200 T12-21-200 T12-26-200 T12-27-200 T12-31-200 T12-32-200 T12-36-200 T12-35-200
2T25 2T25 2T25 2T25 21 27 32 36
2T25 2T25 21 27 32 36
3T25 3T25
2T25

2T25
2T25
2T25

2T25
2T25
2T25

2T25

2T25

2T25

2T25

2T25
2T25
2T25

2T25
2T25
2T25
2T25

2T25

2T25

2T25

2T25
2T25
2T25

2T25
2T25
2T25

2T25
C C

A SIMILAR DIAMETER
REINFORCEMENT

52XØ
Z

T16@150
T16@200
300x800x150 RECESS

Y
100Ø HOLE

T12-17-200 T12-18-200 A

52XØ
1300 650
2T25

2T25
2T25

2T25

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T25

2T25

2T25
2T25

X
18 17
3T25 2T25 2T25 3T25

2T25 2T25 2T25 2T25

2T25 2T25 2T25 2T25 18 17

900
2T25 2T25 2T25 2T25 T12-19-200 T12-12-200 T12-11-200
2T25 2T25
2T25 2T25

900
2T25
2T25 2T25 2T25

2T25 2T25
2T25
2T25 19 10 09 SECTION A-A
2T25
2T25 2T25 T12-16-200 19
TYPICAL ELEVATION OF

650
2T25 12
2T25 2T25 15 15

2T20 2T20
12 HOLD CALL BUTTON

650
11 11
2T20
2T20

2T20 2T20
16 16
2T20 2T20

2T20 AS SHOWN
2T25
2T20 2T32 B/F 2T32
2T25 20
2T25 2T20 C
2T25 20
2T20
2T20

600
2T25 2T25
2T20
2T25 2T20 T12-15-200
2T25 D
2T20 T12-20-200 C
2T25 2T25 2T20
2T20 OPENING

600
2T25 2T25 2T20 13 14
2T20
2T25 2T25 2T20 D
2T20
3T25 2T25 2T20
2T32
2T16
2T25

2T25
2T25

2T25

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T25

2T25

2T25
2T25

2T20 13 14
2T16
1300 650
2T16
2T20

2T20
SECTION X-X
T12-14-200 T12-13-200 0 AS PER PLAN
80

80
2T16

0
2T20
2T16
2T20 1700 X 1700 FLOOR LEVEL
2T16 T12-06-200 2T32 B/F
2T20
T12-10-200 T12-09-200
2T16 0
80

80

600
2T20

0
2T16 T16 AT 150 B/F

T12 AT 200 CTS.


2T20 T16 AT 200 B/F
2T16
2T20

lap
2T16

H
2T20
2T16

80
80
2T20 08 08

0
2T16 2T32 B/F

2T16 2T20

650
2T20 B/F
2T16 2T20
05 05
TYP.
X
01 0

H/2
80

80
2T16 2T20

0
10 09

650
3T25
2T16 01
2T25
2T25
2T16
T12-01-200 AS PER PLAN
2T25 OPENING
2T25 06 06 T12-08-200
2T20 2T32 B/F 2T32 B/F
2T25
2T25

900
2T20 2T25 T12-05-200
2T25 T12-07-200

600
T12-02-200
2T20 2T25 T12-03-200
2T25
2T20 2T25
2T25 03 02 07 03
3T25 3T25

2T25 2T25
FLOOR LEVEL
3T25 3T25
B B 2T32 B/F
2T25

2T25

2T25

2T25

2T25

2T25

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25
2T25

2T25

2T25

2T25

2T25
2T25

2T25

2T25

2T25

2T20

2T20

2T20
2T20

2T20

2T25

2T25

2T25

2T25

2T25
2T25

04 02 07 04
AS SHOWN
1300 650 650 1300
T12-04-200

- R/F DETAILS OF LIFT- TOWER 1


-
Scale: 1:30 - HORIZONTAL BAR ARRANGEMENT OF LIFT - TOWER 1 TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL
(LEVEL 21 TO LEVEL 30) -
Scale: 1:30
(LEVEL 21 TO LEVEL 30)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 1
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. (LEVEL 21 TO LEVEL 30)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.203 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2 W2

UNLESS OTHERWISE INDICATED:-


T12-C-200 T12-B-200 T12-C-200 T12-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T12 AT 200 CTS.
3. LINKS SHALL BE T8 BASE 8mm
A A A A 4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

650

650
5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
LINKS BEND AT SITE FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B C B
6. CONCRETE GRADE SHALL BE C30

150
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T12-A-200(`U' BAR) T12-A-200(`U' BAR) 100 SHALL BE USED.

150
T12-E-200
E F
LINK DETAILS

W1
W1
D F LONGITUDINAL WALL BARS NOTE - 1
2xW1 650 T12-D-200

35Ø
T12-F-200(`U' BAR)
1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
HEIGHT.
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION LINK ARRANGEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

2 2 (PLAN) STAGGER ALTERNATE BARS. BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE
AREA (INCLUDING SPLICES), THE BARS MUST BE
MECHANICALLY SPLICED.
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
1300 650 650 1300
T12-29-200 OF THE SPECIFIED BAR YIELD CAPACITY.
3T25

2T25

3T25

2T20

2T20

2T20

2T20

2T20

2T20

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20

2T25
2T25

2T25

2T20

2T20

2T20
2T20

2T20

2T20

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20

2T25
2T25

2T25

2T20

2T20

2T20

2T20

2T20

2T20

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20

3T25

2T25

3T25
4. CLEAR DISTANCE BETWEEN A CONTACT LAP

SEE NOTE 1
29 24 33 29
SPLICE AND ADJACENT BARS SHALL BE NOT LESS
THAN 1.5 TIMES THE BAR DIAMETER NOR.

2T20 2T20 2T20 2T20 850 28 24 33 28 850


2T20 2T20 2T20 2T20 T12-25-200 T12-28-200 T12-30-200 T12-33-200 TOP OF SLAB NOTE - 2
T12-24-200

750

750
750

750
2T20 2T20 2T20 2T20 FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S
2T20 2T20 2T20 2T20 T12-23-200 T12-34-200 DRAWINGS.
2T20 2T20 2T20 2T20
22 22 26 26 31 31 35 35
2T20 2T16 2T16 2T20
WALL

650

650

650

650
2T16 2T16 2T16 2T16

2T16 2T16 2T16 2T16

2T16 2T16 2T16 2T16


23 23 25 25 30 30 34 34

2T16 2T16 2T16 2T16 TYPICAL MECHANICAL SPLICE DETAIL


2T20 2T16 2T16 2T20

2T20 2T20 2T20 2T20

2T20 2T20 2T20 2T20

2T20 2T20 2T20 2T20

2T20 2T20 2T20 2T20 T12-22-200 T12-21-200 T12-26-200 T12-27-200 T12-31-200 T12-32-200 T12-36-200 T12-35-200
2T20 2T20 2T20 2T20 21 27 32 36
2T25 2T25 21 27 32 36
3T25 3T25
2T25

2T25
2T25
2T25

2T25
2T25
2T25

2T25

2T25

2T25

2T25

2T25
2T25
2T25

2T25
2T25
2T25
2T25

2T25

2T25

2T25

2T25
2T25
2T25

2T25
2T25
2T25

2T25
C C

A SIMILAR DIAMETER
REINFORCEMENT

52XØ
Z

T16@150
T16@200
300x800x150 RECESS

Y
100Ø HOLE

T12-17-200 T12-18-200 A

52XØ
1300 650
2T20

2T20
2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

2T20

2T20

2T20
2T20
2T25

2T25

X
18 17
3T25 2T20 3T25

2T25 2T20 2T25

2T20 2T25 2T20 2T25 18 17

900
2T20 2T25 2T20 2T25 T12-19-200 T12-12-200 T12-11-200
2T20 2T25
2T20 2T25

900
2T20
2T25 2T25
2T20

2T20 2T25
2T20
2T25 19 10 09
SECTION A-A
2T20
2T20 2T25 T12-16-200 19 TYPICAL ELEVATION OF

650
2T20 12
2T16 2T25 15 15

2T16 2T16
12 HOLD CALL BUTTON

650
11 11
2T16
2T16

2T16 2T16
16 16
2T16 2T16

2T16 AS SHOWN
2T16
2T16 2T32 B/F 2T32
2T20 20
2T25 2T16 C
2T20 20
2T20
2T25 2T16

600
2T20
2T20
2T25 2T16 T12-15-200
2T20 D
2T20 T12-20-200 C
2T20 2T25 2T16
2T20 OPENING

600
2T20 2T25 2T16 13 14
2T20
2T25 2T25 2T16 D
2T20
3T25 2T25 2T16
2T12 2T32
2T20

2T20
2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

2T20

2T20

2T20
2T20

2T16 13 14
2T12
1300 650
2T12
2T16

2T16
SECTION X-X
T12-14-200 T12-13-200 0 AS PER PLAN
80

80
2T12

0
2T16
2T12
2T16 1700 X 1700 FLOOR LEVEL
2T12 T12-06-200 2T32 B/F
2T16
T12-10-200 T12-09-200
2T12 0
80

80

600
0
2T16
2T12 T16 AT 150 B/F

T12 AT 200 CTS.


2T16 T16 AT 200 B/F
2T12
2T16

lap
2T12

H
2T16
2T12

80
80
2T16 08 08

0
2T12 2T32 B/F

2T12 2T16

650
2T20 B/F
2T12 2T16
05 05 TYP.
X
01 0

H/2
80

80
2T12 2T16

0
10 09

650
3T25
2T12 01
2T20
2T25
T12-01-200 AS PER PLAN
2T12 2T20 OPENING
2T20 06 06 T12-08-200
2T20 2T32 B/F 2T32 B/F
2T20
2T20

900
2T20 2T20 T12-05-200
2T20 T12-07-200

600
T12-02-200
2T20 2T20 T12-03-200
2T20
2T20 2T20
2T20 03 02 07 03
3T25 3T25

2T25 2T25
FLOOR LEVEL
3T25 3T25
B B 2T32 B/F
2T20

2T20

2T20

2T20

2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20
2T20

2T25

2T25

2T20

2T20
2T20

2T20

2T20

2T20

2T16

2T16

2T16
2T16

2T16

2T20

2T20

2T20

2T20

2T20
2T20

04 02 07 04
AS SHOWN
1300 650 650 1300
T12-04-200

- R/F DETAILS OF LIFT- TOWER 1


-
Scale: 1:30 - HORIZONTAL BAR ARRANGEMENT OF LIFT - TOWER 1 TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL
(LEVEL 31 TO LEVEL 40) -
Scale: 1:30
(LEVEL 31 TO LEVEL 40)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 1
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. (LEVEL 31 TO LEVEL 40)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.204 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2 W2

UNLESS OTHERWISE INDICATED:-


T10-C-200 T10-B-200 T10-C-200 T10-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T10 AT 200 CTS.
3. LINKS SHALL BE T8 BASE 8mm
4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
A A A A FOR LONGITUDINAL BARS LESS THAN 16Ø.
5. LINKS SPACING SHOULD BE 300mm (in vertical direction)

550

550
LINKS BEND AT SITE FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B C B
6. CONCRETE GRADE SHALL BE C30

150
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T10-A-200(`U' BAR) T10-A-200(`U' BAR) 100 SHALL BE USED.

150
T10-E-200
E F
LINK DETAILS

W1
W1
D F LONGITUDINAL WALL BARS NOTE - 1
2xW1 550 T10-D-200

35Ø
T10-F-200(`U' BAR)
1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
HEIGHT.
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION LINK ARRANGEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

2 2 (PLAN) STAGGER ALTERNATE BARS. BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE
AREA (INCLUDING SPLICES), THE BARS MUST BE
MECHANICALLY SPLICED.
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
1300 550 550 1300
T10-29-200 OF THE SPECIFIED BAR YIELD CAPACITY.
3T20

2T20

3T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T20
2T20

2T20

2T16

2T16

2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T20
2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

3T20

2T20

3T20
4. CLEAR DISTANCE BETWEEN A CONTACT LAP

SEE NOTE 1
29 24 33 29
SPLICE AND ADJACENT BARS SHALL BE NOT LESS
THAN 1.5 TIMES THE BAR DIAMETER NOR.

2T16 2T16 2T16 2T16 850 28 24 33 28 850


2T16 2T16 2T16 T10-25-200 T10-28-200 T10-30-200 T10-33-200 TOP OF SLAB NOTE - 2
2T16
T10-24-200

750

750

750

750
2T16 2T16 2T16 2T16 FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S
2T16 2T16 2T16 2T16 DRAWINGS.
T10-23-200 T10-34-200
2T16 2T16 2T16 2T16
22 22 26 26 31 31 35 35
2T20 2T16 2T16 2T16
WALL

550

550

550

550
2T16 2T16 2T16 2T16

2T16 2T16 2T16 2T16 23 23 25 25 30 30 34 34


2T16 2T16 2T16 2T16

2T16 2T16 2T16 2T16 TYPICAL MECHANICAL SPLICE DETAIL


2T16 2T16 2T16 2T16

2T16 2T16 2T16 2T16

2T16 2T16 2T16 2T16

2T25 2T16 2T16 2T16

2T25 2T16 2T16 2T25 T10-22-200 T10-21-200 T10-26-200 T10-27-200 T10-31-200 T10-32-200 T10-36-200 T10-35-200
2T25 2T16 2T16 2T25 21 27 32 36
2T25 2T25 21 27 32 36
3T25 3T25
2T20

2T25
2T25
2T25

2T25
2T25
2T25

2T20

2T20

2T20

2T20

2T25
2T25
2T25

2T25
2T25
2T25
2T20

2T20

2T20

2T20

2T25
2T25
2T25

2T25
2T25
2T25

2T20
C C

A SIMILAR DIAMETER
REINFORCEMENT

52XØ
Z

T16@150
T16@200
300x800x150 RECESS

Y
100Ø HOLE

T10-17-200 T10-18-200 A

52XØ
1300 550
2T16

2T16
2T16

2T16

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12
2T12

2T16

2T16

2T16
2T16
2T20

2T20

X
18 17
3T25 2T20 3T25

2T25 2T20 2T25

2T25 2T20 2T16 2T25 18 17

900
2T25 2T20 2T16 2T25 T10-19-200 T10-12-200 T10-11-200
2T16 2T20
2T16 2T20

900
2T16
2T20
2T16

2T16
2T25

2T25
2T16
2T16 19 10 09
SECTION A-A
2T25
2T16 2T16 T10-16-200 19 TYPICAL ELEVATION OF

550
2T25 12
2T16 2T16 15 15

2T16 2T16
12
11 11 HOLD CALL BUTTON

550
2T16
2T16
2T16 16 16
2T16

2T16 2T16
AS SHOWN
2T16 2T16

2T16 2T32 B/F 2T32


2T16 20
C
2T16 2T25 2T16 20
2T25

600
2T16 2T25 2T16
2T25
2T20 2T16 T10-15-200
2T16 D
2T25 T10-20-200 C
2T25 2T20 2T16
2T20 OPENING

600
2T25 2T20 2T16 13 14
2T16
2T25 2T20 2T16 D
2T16
2T20 2T16
3T25 2T32
2T12
2T16

2T16
2T16

2T16

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12
2T12

2T16

2T16

2T16
2T16

2T16 13 14
2T12

2T12
2T16 1300 550
SECTION X-X
2T16 T10-14-200 T10-13-200 0 AS PER PLAN
80

80
2T12

0
2T16
2T12
2T16 1700 X 1700 FLOOR LEVEL
2T12 T10-06-200 2T32 B/F
2T16
T10-10-200 T10-09-200
2T12 0
80

80

600
0
2T16
2T12 T16 AT 150 B/F

T12 AT 200 CTS.


2T16 T16 AT 200 B/F
2T12
2T16

lap

H
2T12
2T16
2T12

80
80
2T16

0
2T12 2T32 B/F
08 08
2T12 2T16 2T20 B/F
X

550
2T12 2T16 TYP.
01 05 05 0

H/2
80

80
2T12

0
2T16
3T25 10 09

550
2T12 01
2T16
2T25
2T12
T10-01-200 OPENING
AS PER PLAN
2T16 06 06 T10-08-200
2T25
2T32 B/F 2T32 B/F
2T16 2T16
2T25

900
2T16 2T16 T10-05-200
2T20 T10-07-200

600
T10-02-200
2T16 2T16 T10-03-200
2T20
2T16 2T16
2T20 03 02 07 03
3T20 3T20

2T20 2T20
FLOOR LEVEL
3T20 3T20
B B 2T32 B/F
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

2T20

2T20

2T16

2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

04 02 07 04
AS SHOWN
1300 550 550 1300
T10-04-200

- R/F DETAILS OF LIFT- TOWER 1


-
Scale: 1:30 - HORIZONTAL BAR ARRANGEMENT OF LIFT - TOWER 1 TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL
(LEVEL 41 TO LEVEL 50) -
Scale: 1:30
(LEVEL 41 TO LEVEL 50)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 1
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. (LEVEL 41 TO LEVEL 50)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.205 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2

AS SHOWN
UNLESS OTHERWISE INDICATED:-
2T32 B/F
T16-C-200 T16-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T16 AT 200 CTS.
A A 3. LINKS SHALL BE T8 BASE 8mm
4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

850
OPENING 5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B
6. CONCRETE GRADE SHALL BE C70
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T16-A-200(`U' BAR) SHALL BE USED.
T16-E-200
AS PER PLAN E F

W1
0
80

80
0

1700 X 1700 FLOOR LEVEL


D F NOTE - 1
2T32 B/F 2xW1 850 T16-D-200
T16-F-200(`U' BAR)
LONGITUDINAL WALL BARS 1. LAP WALL BARS AT THE MIDDLE OF ANY STORY

T16 AT 200 CTS.


0
80

600

80
0

HEIGHT.

35Ø
T16 AT 200 B/F
T16 AT 150 B/F
A SIMILAR DIAMETER
REINFORCEMENT TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER

lap

H
2T32 OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

52XØ
C
BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE
Z AREA (INCLUDING SPLICES), THE BARS MUST BE
80 STAGGER ALTERNATE BARS.
0

W2

600
0 MECHANICALLY SPLICED.
80

2T32 B/F
D
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
2T20 B/F
C T16@150 OF THE SPECIFIED BAR YIELD CAPACITY.
X T16@200

H/2
TYP.
300x800x150 RECESS T16-C-200 T16-B-200 4. CLEAR DISTANCE BETWEEN A CONTACT LAP

600
80
8 00 0 SPLICE AND ADJACENT BARS SHALL BE NOT LESS

SEE NOTE 1
D 100Ø HOLE THAN 1.5 TIMES THE BAR DIAMETER NOR.
AS PER PLAN
A A
2T32
OPENING

850
2T32 B/F 2T32 B/F

SECTION X-X A LINKS BEND AT SITE


NOTE - 2

52XØ
C B

150
TOP OF SLAB FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S

X
DRAWINGS.

2xW2
100 T16-A-200(`U' BAR)

150
FLOOR LEVEL
LINK DETAILS

W1
2T32 B/F
AS SHOWN WALL

SECTION A-A
TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL TYPICAL ELEVATION OF TYPICAL MECHANICAL SPLICE DETAIL LINK ARRANGEMENT TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION
HOLD CALL BUTTON (PLAN)
6 7 6 7

T16-33-200 T16-32-200 T16-24-200 T16-22-200 T16-02-200


850 T16-31-200 T16-25-200 T16-23-200 T16-01-200 850
3T32

3T32

3T32
3T32

3T32

3T32

3T32

3T32

3T32

3T25
3T25
3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32
3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T25

3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T40

3T40

3T40

3T40

3T40

3T40

3T40
35 31 34 22 24 04
3T40
32 33 23 25
3T40

3T40 01

3T32 2T32 2T32 2T32 3T32 750 31 850 34 900 22 850 24 01 850 02

750
850

850

850
850
1300

1300

1300

1300
F 3T32 2T32 2T32 2T32 3T32 F
2T32 3T32
T16-34-200 T16-30-200
3T32 2T32 2T32

850
32 T16-26-200 T16-03-200
3T32 2T32 2T32 2T32 3T32 30
33 25 23 02
3T32 2T20 2T20 3T32 30 T16-04-200
T16-35-200 T16-36-200 T16-21-200
3T32 2T20 2T20 3T32
3T25 41 42 40 27 27 20 20 05 07 06
3T25 2T20 2T20

3T25 2T20 2T20 3T25

850

850

850

850
2T20 2T20 3T25
3T25
2T20 2T20 3T25
3T32
2T20 2T20 3T25
3T32
36 35 36 39 26 26 21 21 03 04 03
2T20 2T20 3T25
3T32 2T32
3T25
39
2T20 2T20
3T32 2T32
2T20 2T20 3T25
3T32 2T32 T16-37-200 T16-38-200
2T32

2T32

2T32

2T32

2T32

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T32

2T32

2T32

2T32

2T32

2T32 2T32 3T25 T12-27-200 T12-20-200


3T32 2T32
38 37
2T32 2T32 3T25
3T32 2T32
3T32 2T32 2T32 2T32
3T25
2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32
2T32

2T32

3T32 2T32 2T32 2T32 28


3T25
2T32 2T32 38 37
3T32 2T32 3T25 750 850 28 T16-05-200 T16-06-200
3T32 2T32 2T32 2T32 3T25 29
3T32 2T32 29 T16-07-200
3T25 T16-39-200
3T32 2T32 T16-28-200 T16-29-200
3T25
3T32 3T25

3T32 3T25 T16-41-200 T16-40-200


3T25 3T25
T16-42-200
3T25 3T25

3T25 3T32

3T32 3T32
3T32 3T32

3T32 2T32 3T32

3T32 2T32 3T32 T12-19-200 T12-09-200 850 600


2T32

2T32

2T32

2T32

2T32

2T32

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T32

2T32

2T32

2T32
2T32

2T32

2T32

2T32
2T32
2T32

2T32

2T32

2T32

3T32 2T32 3T32 T16-43-200 T16-44-200 19 08 09


2T32

2T32

2T32

2T32

2T32

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T32

2T32

2T32

2T32

2T32

3T32 2T32 3T32


44 43 19
3T32 2T32 3T32
3T32 2T32
3T32 08 09
3T32 2T32
3T32 T16-08-200
3T32 2T32 750 44 850 43
3T32
3T32 2T32
3T32 T16-45-200
3T32 2T32
3T32
3T32 2T32 45
3T32
3T32 46 47 46 45 11 10 11
3T25
3T32
3T25
3T25 850

850
3T25
3T25
3T25
3T25
3T25
3T32 41 42 40 05 07 06
3T32
3T32 3T32 T16-47-200 T16-46-200
3T32 52
3T32 48 01
2T32 52
850
3T32 3T32
50 T16-11-200 T16-10-200
2T32
T16-49-200 900 850 T16-13-200

1300
1300

3T32 3T32 T16-16-200 850 900

850
2T32
850

750 850 T16-52-200 850

750
3T32 2T32 3T32 51 49 18 16 17 13 16
E E
3T32 3T32
15 18 12 15
3T32 3T32
50 48
3T32 3T32

51 49
3T32

3T32

3T32

3T32

3T32

3T32

3T25
3T25
3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

47 14 17
3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T32

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25
3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T25

3T32

3T32

3T32

3T32

3T32

3T32

850 13 14 10 850
T16-51-200
T16-17-200 T16-18-200 T16-14-200 T16-15-200 T16-12-200
T16-48-200 T16-50-200

- VERTICAL BAR ARRANGEMENT OF LIFT- TOWER 2 - HORIZONTAL BAR ARRANGEMENT OF LIFT- TOWER 2
- -
Scale: 1:30 Scale: 1:30
(BASEMENT 2 TO LEVEL 9) (BASEMENT 2 TO LEVEL 9)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 2
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. ( BASEMENT 2 TO LEVEL 9)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.206 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2

AS SHOWN
UNLESS OTHERWISE INDICATED:-
2T32 B/F
T16-C-200 T16-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T16 / T12 AT 200 CTS.
A A 3. LINKS SHALL BE T8 BASE 8mm
4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

850
OPENING 5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B
6. CONCRETE GRADE SHALL BE C35
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T16-A-200(`U' BAR) SHALL BE USED.
T16-E-200
E F

W1
AS PER PLAN

0
80

80
0

1700 X 1700 FLOOR LEVEL


D F NOTE - 1
2T32 B/F 2xW1 850 T16-D-200
T16-F-200(`U' BAR)
0 LONGITUDINAL WALL BARS 1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
80

600

80
0

HEIGHT.

35Ø
T16 AT 150 B/F
A SIMILAR DIAMETER
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION

T12 AT 200 CTS.


T16 AT 200 B/F REINFORCEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
2T32 OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

lap

52XØ
BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE

H
C
Z AREA (INCLUDING SPLICES), THE BARS MUST BE
80 STAGGER ALTERNATE BARS.
0

W2

600
0 MECHANICALLY SPLICED.
80

2T32 B/F
D
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
2T20 B/F
C T16@150 OF THE SPECIFIED BAR YIELD CAPACITY.
TYP.
X T16@200
T16-C-200 T16-B-200 4. CLEAR DISTANCE BETWEEN A CONTACT LAP
300x800x150 RECESS

600
80
00 SPLICE AND ADJACENT BARS SHALL BE NOT LESS

H/2
8 0

SEE NOTE 1
D 100Ø HOLE THAN 1.5 TIMES THE BAR DIAMETER NOR.
A A
2T32 AS PER PLAN
OPENING

850
2T32 B/F 2T32 B/F

SECTION X-X A LINKS BEND AT SITE


NOTE - 2

52XØ
C B

150
TOP OF SLAB FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S

X
DRAWINGS.

2xW2
100 T16-A-200(`U' BAR)

150
FLOOR LEVEL
LINK DETAILS

W1
2T32 B/F
AS SHOWN WALL

SECTION A-A
TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL TYPICAL ELEVATION OF TYPICAL MECHANICAL SPLICE DETAIL LINK ARRANGEMENT TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION
HOLD CALL BUTTON (PLAN)
6 7 6 7

T16-16-200 T16-15-200
T16-22-200 T16-01-200
3T32

2T32

3T32

2T32

2T32

2T32

2T32

2T32

2T32

2T25
2T25
2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32
2T32

3T32

3T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T25

2T25

2T25

2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32

2T32

3T32

3T32

2T32

2T32

2T32

2T32

2T32

2T32
22 23 15 16
3T32

2T32

3T32 01

2T32 2T32 2T32 2T32 2T32 750 22 850 23 900 15 850 16 01

1300

1300

1300

1300
F 2T32 2T32 2T32 2T32 2T32 F
2T32 2T32
T16-23-200 T12-21-200
2T32 2T32 2T32

850
T12-17-200 T12-14-200 T16-02-200
2T32 2T32 2T32 21
2T32 2T32

2T32 2T20 2T20 2T32 21


T16-24-200
2T32 2T20 2T20 2T32
2T25
29 28 18 18 13 13 03 04
2T25 2T20 2T20

2T25 2T20 2T20 2T25

650

650
850

850
2T20 2T20 2T25
2T25
2T20 2T20 2T25
2T32 17 17 14 14
2T20 2T20 2T25
2T32 24 24 02
27 02
2T20 2T20 2T25
2T32 2T32 27
2T20 2T20 2T25
2T32 2T32
2T20 2T20 2T25
2T32 2T32 T12-25-200 T12-26-200
2T32

2T32

2T32

2T32

2T32

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T32

2T32

2T32

2T32

2T32

2T32 2T32 2T25 T12-18-200 T12-13-200


2T32 2T32 26 25
2T32 2T32 2T25
2T32 2T32
2T32 2T32 2T32 2T32
2T25
2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32 2T32 2T32 2T32 19


2T25
2T32 2T32 2T32 2T32 750 26 650 25 19
2T25 T16-03-200 T16-04-200
2T32 2T32 2T32 2T32 2T25 20
2T32 2T32 T12-27-200 20
2T25
2T32 2T32 T12-19-200 T12-20-200
2T25
2T32 2T25

2T32 2T25

2T25 2T25
T16-29-200 T16-28-200
2T25 2T25

2T25 2T32

2T32 2T32
2T32 2T32

2T32 2T32 2T32

2T32 2T32 2T32 T12-12-200 T12-06-200 650 600


2T32

2T32

2T32

2T32
2T32
2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T32

2T32

2T32

2T32 2T32 2T32 12


2T32 T12-30-200 T12-31-200 05 06
2T32

2T32

2T32

2T32

2T32

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T32

2T32

2T32

2T32

2T32

2T32 2T32 2T32 31 30 12


2T32 2T32 2T32
2T32 2T32 05 06
2T32
2T32 2T32
2T32 T12-05-200
2T32 2T32 750 31 650 30
2T32
2T32 2T32
2T32 T12-32-200
2T32 2T32
2T32
2T32 2T32 32
2T32
2T32 33 33 32 07 07
2T25
2T32
2T25
2T25

850

850
2T25
2T25
2T25
2T25
2T25
2T32
29 28 03 04
2T32
2T32 2T32 T16-33-200
2T32
36
2T32
2T32 36
850
2T32 2T32 T16-07-200
2T32
T16-34-200 900 850 T16-08-200
1300

1300
2T32 2T32 T16-10-200
2T32 750 850 T12-36-200 850 900
2T32 2T32 2T32 35 34 10 11 08 10
E E
3T32

2T32

3T32
35 34
2T32

2T32

2T32

2T32

2T32

2T32

2T25
2T25
2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T32

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25
2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T32

2T32

2T32

2T32

2T32

2T32

3T32

2T32

3T32

09 11 08 09
3T32

3T32

T16-35-200
T16-11-200 T16-09-200

- HORIZONTAL BAR ARRANGEMENT OF LIFT- TOWER 2


- VERTICAL BAR ARRANGEMENT OF LIFT- TOWER 2 -
(LEVEL 10 TO LEVEL 20) Scale: 1:30
-
Scale: 1:30
(LEVEL 10 TO LEVEL 20)

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 2
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. ( LEVEL 10 TO LEVEL 20)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.207 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2

AS SHOWN
UNLESS OTHERWISE INDICATED:-
2T32 B/F
T12-C-200 T12-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T12 AT 200 CTS.
3. LINKS SHALL BE T8 BASE 8mm
A A 4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

650
OPENING 5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B
6. CONCRETE GRADE SHALL BE C30
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T12-A-200(`U' BAR) SHALL BE USED.
T12-E-200
E F

W1
AS PER PLAN

0
80

80
0

1700 X 1700 FLOOR LEVEL


D F NOTE - 1
2T32 B/F 2xW1 650 T12-D-200
T12-F-200(`U' BAR)
0 LONGITUDINAL WALL BARS 1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
80

600

80
0

HEIGHT.

35Ø
T16 AT 150 B/F
A SIMILAR DIAMETER
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION

T12 AT 200 CTS.


T16 AT 200 B/F REINFORCEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
2T32 OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

lap

52XØ
BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE

H
C
Z AREA (INCLUDING SPLICES), THE BARS MUST BE
80 STAGGER ALTERNATE BARS.
0

W2

600
0 MECHANICALLY SPLICED.
80

2T32 B/F
D
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
2T20 B/F
C T16@150 OF THE SPECIFIED BAR YIELD CAPACITY.
TYP.
X T16@200
T12-C-200 T12-B-200 4. CLEAR DISTANCE BETWEEN A CONTACT LAP
300x800x150 RECESS

600
80
00 SPLICE AND ADJACENT BARS SHALL BE NOT LESS

H/2
8 0

SEE NOTE 1
D 100Ø HOLE THAN 1.5 TIMES THE BAR DIAMETER NOR.
2T32 AS PER PLAN
OPENING A A
2T32 B/F 2T32 B/F

650
SECTION X-X A LINKS BEND AT SITE
NOTE - 2

52XØ
C B

150
TOP OF SLAB FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S

X
DRAWINGS.

2xW2
100 T12-A-200(`U' BAR)

150
FLOOR LEVEL
LINK DETAILS

W1
2T32 B/F
AS SHOWN WALL

SECTION A-A
TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL TYPICAL ELEVATION OF TYPICAL MECHANICAL SPLICE DETAIL LINK ARRANGEMENT TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION
HOLD CALL BUTTON (PLAN)
6 7 6 7

T12-16-200 T12-15-200
T12-22-200 T12-01-200
3T25

2T25

3T25

2T25

2T25

2T25

2T25

2T25

2T25

2T20
2T20
2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25
2T25

3T25

3T25

2T25
2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T20

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

3T25

3T25

2T25

2T25

2T25

2T25

2T25

2T25
22 23 15 16
3T25

2T25

3T25 01

2T25 2T25 2T25 2T25 2T25 750 22 650 23 900 15 650 16 01

1300

1300

1300

1300
F 2T25 2T25 2T25 2T25 2T25 F
2T25 2T25
T12-23-200 T12-21-200
2T25 2T25 2T25

850
T12-17-200 T12-14-200 T12-02-200
2T25 2T25 2T25 21
2T25 2T25

2T25 2T20 2T20 2T25 21


T12-24-200
2T25 2T20 2T20 2T25
2T20
29 28 18 18 13 13 03 04
2T20 2T20 2T20

2T20 2T20 2T20 2T20

650

650

650

650
2T20 2T20 2T20
2T20
2T20 2T20 2T20
2T25 24 24 17 17 14 14 02 02
2T20 2T20 2T20
2T25
2T20 27
2T20 2T20
2T25 2T25 27
2T20 2T20 2T20
2T25 2T25
2T20 2T20 2T20
2T25 2T25 T12-25-200 T12-26-200
2T25

2T25

2T25

2T25

2T25

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25 2T25 2T20 T12-18-200 T12-13-200


2T25 2T25 26 25
2T25 2T25 2T20
2T25 2T25
2T25 2T25 2T25
2T20
2T25 2T25 2T25 2T25 19
2T20
2T25 2T25 2T25 2T25 750 26 650 25 19
2T20 T12-03-200 T12-04-200
2T25 2T25 2T25 2T25 20
2T20
2T25

2T25

2T25

2T25

2T25

20
2T25

2T25

2T25

2T25

2T25

2T25 2T25 T12-27-200


2T20
2T25 2T25 T12-19-200 T12-20-200
2T20
2T25 2T20

2T25 2T20

2T20 2T20
T12-29-200 T12-28-200
2T20 2T20

2T20 2T25

2T25 2T25
2T25 2T25

2T25 2T25 2T25

2T25 2T25 2T25 T12-12-200 T12-06-200 650 600


2T25

2T25

2T25

2T25
2T25
2T25

2T25

2T25

2T25

2T20

2T20

2T20

2T20

2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T20

2T20

2T20

2T25 2T20 2T25 12


2T25 T12-30-200 T12-31-200 05 06
2T25

2T25

2T25

2T25

2T25

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25 2T25 2T25 12


31 30
2T25 2T25 2T25
2T25 05 06
2T25
2T25 2T25
2T25 T12-05-200
2T25 2T25 750 31 650 30
2T25
2T25 2T25
2T25 T12-32-200
2T25 2T25
2T25
2T25 2T25 32
2T25
2T25 32
2T20
2T25
2T20 33 33 07 07
2T20
2T20
650

650
2T20
2T20
2T20
2T20
2T25
29 28 03 04
2T25
2T25 2T25 T12-33-200
2T25
36
2T25
2T25 36
850
2T25 2T25 T12-07-200
2T25
T12-34-200 900 650 T12-08-200
1300

1300
2T25 2T25 T12-10-200
2T25 750 650 T12-36-200 650 900
2T25 2T25 2T25 35 34 10 11 08 10
E E
3T25 3T25

2T25 2T25

3T25 3T25
2T25

2T25

2T25

2T25

2T25

2T25

2T20
2T20
2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25

2T25

35 34
3T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20
2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T25

2T25

2T25

2T25

2T25

2T25

09 11 08 09
3T25

T12-35-200
T12-11-200 T12-09-200

- R/F DETAILS OF LIFT- TOWER 2 - HORIZONTAL BAR ARRANGEMENT OF LIFT- TOWER 2


-
Scale: 1:30 -
(LEVEL 21 TO LEVEL 30) (LEVEL 21 TO LEVEL 30) Scale: 1:30

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 2
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. ( LEVEL 21 TO LEVEL 30)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.208 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2

AS SHOWN
UNLESS OTHERWISE INDICATED:-
2T32 B/F
T12-C-200 T12-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T12 AT 200 CTS.
3. LINKS SHALL BE T8 BASE 8mm
A A 4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
FOR LONGITUDINAL BARS LESS THAN 16Ø.

650
OPENING 5. LINKS SPACING SHOULD BE 300mm (in vertical direction)
FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B
6. CONCRETE GRADE SHALL BE C30
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T12-A-200(`U' BAR) SHALL BE USED.
T12-E-200
E F

W1
AS PER PLAN

0
80

80
0

1700 X 1700 FLOOR LEVEL


D F NOTE - 1
2T32 B/F 2xW1 650 T12-D-200
T12-F-200(`U' BAR)
0 LONGITUDINAL WALL BARS 1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
80

600

80
0

HEIGHT.

35Ø
T16 AT 150 B/F
A SIMILAR DIAMETER
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION

T12 AT 200 CTS.


T16 AT 200 B/F REINFORCEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
2T32 OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

lap

52XØ
BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE

H
C
Z AREA (INCLUDING SPLICES), THE BARS MUST BE
80 STAGGER ALTERNATE BARS.
0

W2

600
0 MECHANICALLY SPLICED.
80

2T32 B/F
D
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
2T20 B/F
C T16@150 OF THE SPECIFIED BAR YIELD CAPACITY.
TYP.
X T16@200
T12-C-200 T12-B-200 4. CLEAR DISTANCE BETWEEN A CONTACT LAP
300x800x150 RECESS

600
80
00 SPLICE AND ADJACENT BARS SHALL BE NOT LESS

H/2
8 0

SEE NOTE 1
D 100Ø HOLE THAN 1.5 TIMES THE BAR DIAMETER NOR.
2T32 AS PER PLAN
OPENING A A
2T32 B/F 2T32 B/F

650
SECTION X-X A LINKS BEND AT SITE
NOTE - 2

52XØ
C B

150
TOP OF SLAB FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S

X
DRAWINGS.

2xW2
100 T12-A-200(`U' BAR)

150
FLOOR LEVEL
LINK DETAILS

W1
2T32 B/F
AS SHOWN WALL

SECTION A-A
TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL TYPICAL ELEVATION OF TYPICAL MECHANICAL SPLICE DETAIL LINK ARRANGEMENT TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION
HOLD CALL BUTTON (PLAN)
6 7 6 7

T12-16-200 T12-15-200
T12-22-200 T12-01-200
3T25

2T25

3T25

2T20

2T20

2T20

2T20

2T20

2T20

2T16
2T16
2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20
2T25

3T25

3T25

2T25
2T20

2T20

2T20

2T20

2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20

2T25

3T25

3T25

2T25

2T20

2T20

2T20

2T20

2T20
22 23 15 16
3T25

2T25

3T25 01

2T20 2T25 2T20 2T20 2T20 750 22 650 23 900 15 650 16 01

1300

1300

1300

1300
F 2T20 2T25 2T20 2T20 2T20 F
2T25 2T20
T12-23-200 T12-21-200
2T20 2T20 2T20

850
T12-17-200 T12-14-200 T12-02-200
2T20 2T25 2T20 21
2T20 2T20

2T20 2T16 2T16 2T20 21


T12-24-200
2T20 2T16 2T16 2T20
2T16
29 28 18 18 13 13 03 04
2T16 2T16 2T16

2T16 2T16 2T16 2T16

650

650

650

650
2T16 2T16 2T16
2T16
2T16 2T16 2T16
2T20 24 24 17 17 14 14 02 02
2T16 2T16 2T16
2T20
2T16 27
2T16 2T16
2T20 2T25 27
2T16 2T16 2T16
2T20 2T25
2T16 2T16 2T16
2T20 2T25 T12-25-200 T12-26-200
2T20

2T20

2T20

2T20

2T20

2T16

2T16
2T16
2T16

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20 2T20 2T16 T12-18-200 T12-13-200


2T20 2T25 26 25
2T20 2T20 2T16
2T25 2T25
2T25 2T20 2T20
2T16
2T25 2T25 2T20 2T20 19
2T16
2T20 2T25 2T25 2T25 750 26 650 25 19
2T16 T12-03-200 T12-04-200
2T20 2T25 2T25 2T25 20
2T16
2T25

2T25

2T25

2T25

2T25

20
2T25

2T25

2T25

2T25

2T25

2T20 2T25 T12-27-200


2T16
2T20 2T25 T12-19-200 T12-20-200
2T16
2T20 2T16

2T20 2T16

2T16 2T16
T12-29-200 T12-28-200
2T16 2T16

2T16 2T20

2T20 2T20
2T20 2T20

2T20 2T25 2T20

2T20 2T25 2T20 T12-12-200 T12-06-200 650 600


2T20

2T20

2T20

2T20
2T20
2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T20

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T20

2T20

2T20

2T20 2T20 2T20 12


2T25 T12-30-200 T12-31-200 05 06
2T20

2T20

2T20

2T20

2T20

2T16

2T16
2T16
2T16

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20 2T25 2T25 12


31 30
2T25 2T25 2T25
2T25 05 06
2T20
2T25 2T25
2T20 T12-05-200
2T20 2T25 750 31 650 30
2T20
2T20 2T25
2T20 T12-32-200
2T20 2T25
2T20
2T20 2T25 32
2T20
2T20 32
2T16
2T20
2T16 33 33 07 07
2T16
2T16
650

650
2T16
2T16
2T16
2T16
2T20
29 28 03 04
2T20
2T20 2T20 T12-33-200
2T20
36
2T20
2T25 36
850
2T20 2T20 T12-07-200
2T25
T12-34-200 900 650 T12-08-200
1300

1300
2T20 2T20 T12-10-200
2T25 750 650 T12-36-200 650 900
2T20 2T25 2T20 35 34 10 11 08 10
E E
3T25 3T25

2T25 2T25

3T25 3T25
2T20

2T20

2T20

2T20

2T20

2T20

2T16
2T16
2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20

2T25

35 34
3T25
2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T25

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T20

2T20

2T20

2T20

2T20

2T20

09 11 08 09
3T25

T12-35-200
T12-11-200 T12-09-200

- R/F DETAILS OF LIFT- TOWER 2 - HORIZONTAL BAR ARRANGEMENT OF LIFT- TOWER 2


-
Scale: 1:30
(LEVEL 31 TO LEVEL 40) -
(LEVEL 31 TO LEVEL 40) Scale: 1:30

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 2
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. ( LEVEL 31 TO LEVEL 40)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.209 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00
W2

AS SHOWN
UNLESS OTHERWISE INDICATED:-
2T32 B/F
T10-C-200 T10-B-200
1. ALL VERTICAL BAR SPACING TO BE 150mm.
2. HORIZONTAL BARS TO BE T10 AT 200 CTS.
3. LINKS SHALL BE T8 BASE 8mm
4. LINKS SPACING SHOULD BE 400mm (in vertical direction)
A A FOR LONGITUDINAL BARS LESS THAN 16Ø.
5. LINKS SPACING SHOULD BE 300mm (in vertical direction)

550
OPENING
FOR LONGITUDINAL BARS GREATER THAN 16Ø.
C B
6. CONCRETE GRADE SHALL BE C30
7. ALL REINFORCING STEEL SHALL COMPLY WITH EN

2xW2
10080:2005. ONLY STEEL BARS OF GRADE B500B
T10-A-200(`U' BAR) SHALL BE USED.
T10-E-200
E F

W1
AS PER PLAN

0
80

80
0

1700 X 1700 FLOOR LEVEL


D F NOTE - 1
2T32 B/F 2xW1 550 T10-D-200
T10-F-200(`U' BAR)
0 LONGITUDINAL WALL BARS 1. LAP WALL BARS AT THE MIDDLE OF ANY STORY
80

600

80
0

HEIGHT.

35Ø
T16 AT 150 B/F
A SIMILAR DIAMETER
TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "L" JUNCTION

T12 AT 200 CTS.


T16 AT 200 B/F REINFORCEMENT 2. LAP WALL BARS A DISTANCE OF 52Ø (Ø - DIAMETER
2T32 OF SMALLER BAR). WHEN TOTAL LONGITUDINAL

lap

52XØ
BAR AREA EXCEEDS 0.05 TIMES THE CONCRETE

H
C
Z AREA (INCLUDING SPLICES), THE BARS MUST BE
80 STAGGER ALTERNATE BARS.
0

W2

600
0 MECHANICALLY SPLICED.
80

2T32 B/F
D
3. SPLICES MAY BE CAPABLE OF DEVELOPING 125%
2T20 B/F
C T16@150 OF THE SPECIFIED BAR YIELD CAPACITY.
TYP.
X T16@200
T10-C-200 T10-B-200 4. CLEAR DISTANCE BETWEEN A CONTACT LAP
300x800x150 RECESS

600
80
00 SPLICE AND ADJACENT BARS SHALL BE NOT LESS

H/2
8 0

SEE NOTE 1
D 100Ø HOLE THAN 1.5 TIMES THE BAR DIAMETER NOR.
2T32 AS PER PLAN
OPENING
2T32 B/F 2T32 B/F A A
SECTION X-X

550
A LINKS BEND AT SITE
NOTE - 2

52XØ
C B

150
TOP OF SLAB FOR WALL OPENING SIZES REFER M&E AND ARCHITECT'S

X
DRAWINGS.

2xW2
100 T10-A-200(`U' BAR)

150
FLOOR LEVEL
LINK DETAILS

W1
2T32 B/F
AS SHOWN WALL

SECTION A-A
TYPICAL OPENING DETAIL FOR RC WALLS TYPICAL SECTION THRO. WALL TYPICAL ELEVATION OF TYPICAL MECHANICAL SPLICE DETAIL LINK ARRANGEMENT TYPICAL HORIZONTAL BAR LAPPING DETAIL AT "T" JUNCTION
HOLD CALL BUTTON (PLAN)
6 7 6 7

T10-16-200 T10-15-200
T10-22-200 T10-01-200
3T20

2T20

3T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T25

2T25
2T25

3T25

3T25

2T25
2T25

2T25

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T25

2T25

2T25

3T25

3T25

2T25

2T25

2T25

2T20

2T20

2T20
22 23 15 16
3T20

2T20

3T20 01

2T16 2T20 2T16 2T16 2T16 750 22 550 23 900 15 550 16 01

1300

1300

1300

1300
F 2T16 2T25 2T16 2T16 2T16 F
2T25 2T16
T10-23-200 T10-21-200
2T16 2T16 2T16

850
T10-17-200 T10-14-200 T10-02-200
2T16 2T25 2T16 21
2T16 2T16

2T16 2T12 2T12 2T16 21


T10-24-200
2T16 2T12 2T12 2T16
2T16
29 28 18 18 13 13 03 04
2T16 2T12 2T12

550

550

550

550
2T16 2T12 2T12 2T16

2T12 2T12 2T16


2T16 24 24 17 17 14 14 02 02
2T12 2T12 2T16
2T16
2T12 2T12 2T16
2T16
2T16 27
2T12 2T12
2T16 2T25 27
2T12 2T12 2T16
2T16 2T25
2T12 2T12 2T16
2T16 2T25 T10-25-200 T10-26-200
2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16 2T16 2T16 T10-18-200 T10-13-200


2T16 2T20 26 25
2T16 2T16 2T16
2T20 2T20
2T20 2T16 2T16
2T16
2T20 2T20 2T16 2T16 19
2T16
2T16 2T20 2T20 2T20 750 26 550 25 19
2T16 T10-03-200 T10-04-200
2T16 2T25 2T20 2T20 20
2T16
2T20

2T20

2T20

2T25

2T25

20
2T25

2T25

2T20
2T20

2T20

2T16 2T25 T10-27-200


2T16
2T16 2T25 T10-19-200 T10-20-200
2T16
2T16 2T16

2T16 2T16

2T16 2T16
T10-29-200 T10-28-200
2T16 2T16

2T16 2T16

2T16 2T16
2T16 2T16

2T16 2T25 2T16

2T16 2T25 2T16 T10-12-200 T10-06-200 550 600


2T20

2T20

2T16

2T16
2T16
2T16

2T16

2T25

2T25

2T25

2T25

2T25

2T20

2T16

2T16

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T12

2T16

2T16

2T16

2T16 2T16 2T16 12


2T25 T10-30-200 T10-31-200 05 06
2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16 2T20 2T20 12


31 30
2T20 2T20 2T20
2T20 05 06
2T16
2T20 2T20
2T16 T10-05-200
2T16 2T20 750 31 550 30
2T16
2T16 2T25
2T16 T10-32-200
2T16 2T25
2T16
2T16 2T25 32
2T16
2T16 32
2T16
2T16
2T16
2T16 33 33 07 07
2T16
2T16 550

550
2T16
2T16
2T16
2T16
29 28 03 04
2T16
2T16 2T16 T10-33-200
2T16
36
2T16
2T25 36
850
2T16 2T16 T10-07-200
2T25 T10-08-200
T10-34-200 900 550
1300

1300
2T16 2T16 T10-10-200
2T25 750 550 T10-36-200 550 900
2T16 2T20 2T16 35 34 10 11 08 10
E E
3T20 3T20

2T20 2T20

3T20 3T20
2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T25

2T25

2T25

2T25

35 34
3T25

2T25

2T25

2T25

2T20

2T20

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16
2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

2T16

09 11 08 09
3T25

T10-35-200
T10-11-200 T10-09-200

- R/F DETAILS OF LIFT- TOWER 2 - HORIZONTAL BAR ARRANGEMENT OF LIFT- TOWER 2


-
Scale: 1:30 -
(LEVEL 41 TO LEVEL 50) (LEVEL 41 TO LEVEL 50) Scale: 1:30

STRUCTURAL ENGINEER DESIGN AND BUILT BY NOTE PROJECT DRAWING TITLE


CIVIL AND STRUCTURAL ENGINEERING R/F DETAILS OF LIFT-TOWER 2
CONSULTANTS(PVT)LTD. SANKEN CONSTRUCTION (Pvt) Ltd. CHECK ALL DIMENSIONS ON SITE
PRIOR TO CONSTRUCTION. DO NOT
PROPOSED RESIDENTIAL DEVELOPMENT AT STAPLE STREET, COLOMBO 2. ( LEVEL 41 TO LEVEL 50)
64, Barnes Place, 1, 33rd Lane , Floor 12A, SCALE FROM DRAWING. REPORT
No.295, MADAMPITIYA ROAD,COLOMBO 14,
Colombo-07. Bagathale Road, PARKLAND, Park Street, ANY DISCREPANCIES. IF IN DOUBT
SRI LANKA. DATE SCALE SHEET SIZE
Colombo-03. Colombo-02. ASK. COPYRIGHT AND AUTHORITY DESIGNED : Eng. SHIROMAL FERNANDO DRAWN : SURANGA PEIRIS SHEET No
T-0112 522939 F-0112 522942 31-01-2017
FOR ANY REPRODUCTION OF AS GIVEN A1
E mail -sanken@sanken.lk DESIGN SHOWN HERE IS RETAINED. SURANGA PEIRIS
BW SH 12/09/2016 DRAFTING CHECKED : Eng. BATHIYA WADUGE
T1 +94 (11) 2 683 979 T2 +94 (11) 2 501 727 DESIGN CHECKED : PROF. PRIYAN MENDIS
Web - www.sanken.lk DO NOT KEEP SUPERSEDED Revision PROJECT No 16004-S03.210 REVISION
F +94718802859 FILE NAME, PATH AND OTHER INFO.
DRAWINGS ON SITE. No Note: * indicates signatures on original issue Drawn Chkd. Appd. Date
E mail - contact@csec.lk Web - www.csec.lk of drawing or last revision of drawing
APPROVED : Eng. SHIROMAL FERNANDO 16004 00