You are on page 1of 1

OPAL HVAC ENGINEERS Pvt Ltd SCHEMATIC DESIGN AIRFLOW DIAGRAM

CFM
Low RH Area at MAXIM LAB ALANDI exfiltration 300

AHU 10 primary packing : 20C+/-2C & RH


NOT EXCEEDING 20% 1700 cfm Sensible 51397 BTU/hr
Latent 51238 gr/hr 2000 CFM
68 F Inside 68 F 43.0 F
Area Details 15.2 GR 15.2 gr/lb 8.5 GR/LB
Area Details 398 sqft ROOM
Ht 2.5 metres
Occupancy 8 persons
Eqpt Load 11.78 KW 1700 CFM
Doors 2 no 7ft x 3ft 68 DB F
opening 6times/hr 15.2 GR DX COIL
7.80
TONS
2000 CFM
86.3 F
647 CFM 8.5 GR/LB
68.0 F
15.2 GR
1053 CFM
68.0 F
15.2 GR/LB

FA 1353 CFM 1353 CFM


DEHUMIDIFIER
CFM 300
DB F 56
GR/LB 64
2352.94
65.3 F 95.0 F
26.0 GR/LB 5.3 GR/LB
18.5 C 35 C
3.7 G/KG 0.75 G/KG
dehumidifier capacity
2000 Ft3 60 min 1 lb 6.7 gr 61783.62 GR/HR
ahu min hr 13.06 ft3 lb