SYSTEM FLOW DIAGRAM


Project Name : OPAL HVAC AC CENTAUR PHARMA PUNE Date : 20-Jan-2016
Area : AHU-54- PHARMA By : BNN

CONDITIONED SPACE

Internal Latent Load :187479 Grs/Hr


SUPPLY
After Coil

Internal Sensible Load :


108062 BTUH
6700CFM
AIR
DBT RH Abs. Hum.
RETURN
AIR 77 °F NMT20 % 21.9 Grs/# 62.1 °F
15 Grs/#
6700 CFM
6300 CFM
87.4 °F
77 °F
15 Grs/#
21.9 Grs/#

3700 CFM , 77 °F , 21.9 Grs/#

BYPASS AIR

3000 CFM
2600 CFM
100.2 °F
77 °F
6.6 Grs/#
21.9 Grs/#

PROCESS OUT

REACT IN

Precool Coil

400 CFM
PROCESS IN
REACT OUT
FRESH AIR
3000 CFM
83 °F 56 °F
154.6 Grs/# 64.8 Grs/# 74.2 °F
44.2 BTU/# 23.5 BTU/# 27.6 Grs/# MODEL FLP-5000 x 1

Heat Addition by Dehumidifier = 75168 BTUH

UTILITIES REQD.
OUR SCOPE
Precoil Load = 35485.7 BTUH = 3 TOR
After Coil = 183070.8 BTUH = 15.3 TOR
REACTIVATION
Electric = 53 KW Steam =91.12 Kgs/Hr @ 7 Kgs/cm2

MOTOR DETAILS LEGEND


Process = 3.7 KWReactivation =1.1 KW
H.B HEATER BANK
Electrical Connection ( V /Ph/Hz)415/3/50 F.B FILTER BANK
Standard Unit Dimension( Bare Unit ) =
1050 mm X 1130 mm X 1770 mm React. REACTIVATION

Dimensions shall increase for Bypass & other options e.g. After / Pre coil , fan etc.