You are on page 1of 24

Installation

Operation
Maintenance
ODYSSEY
Light Commercial
Split System 5-20 Tons
TTA Model 50 Hz

Single Circuit; Dual Circuit; Manifolded Compr.;


TTA 075 RD00 TTA 150 RD00 TTA 150 RD0G
TTA 100 RD00 TTA 200 RD00 TTA 200 RD0G
TTA 120 RD00 TTA 240 RD00 TTA 240 RD0G

August 2001 TTA-IOM01-EN


Model Nomenclature

Condensing Unit
Model Nomenclature
TTA 075 R D 0 0 M A

Service Digit
TTA = Cooling Only Condensing Unit A = First Parts list
Minor Design Sequence
M = First Design Sequence
Nominal Gross Cooling Capacity (MBh)
N = Second Design Sequence
075 = 75 MBh
100 = 100 MBh Factory Installed Options
120 = 120 MBh 00 = No Options
150 = 150 MBh 0E = Copper Fin
200 = 200 MBh 0F = Blue Fin
240 = 240 MBh 0G = Manifolded Compressor
0S = Special request to be defined and approved
Electrical Characteristics
D = 380-415/3/50
Refrigerant Type
R = R22

2
© American Standard Inc. 2001 TTA-IOM01-EN
Contents

Model Nomenclature 2
General Information 4
Installation 5
Refrigerant Piping Guidelines 6
Refrigerant Charging and Evacuation 9
General Data 10
Electrical Wiring 13
Dimension Data 18
Operation 21
Maintenance 22
Maintenance Log1 22
Trouble Shooting 23

TTA-IOM01-EN 3
General Information

This manual covers the installation of Installation Checklist Inspection Checklist


the TTA075, TTA100, and TTA120 An “Installation Checklist” is provided To protect against loss due to
(single circuit), TTA150, TTA200, and at the end of the installation section damage incurred in transit, complete
TTA240 (dual circuit) system outdoor of this manual. Use the checklist to the following checklist upon receipt
units. Installation procedures should verify that all necessary installation of the unit.
be performed in the sequence that procedures have been completed. • Inspect individual pieces of the
they appear in this manual. Do not Do not use the checklist as a shipment before accepting the unit.
destroy or remove the manual from substitute for reading the information Check for obvious damage to the
the unit. The manual should remain contained in the manual. Read the unit or packing material.
weather-protected with the unit entire manual before beginning • Inspect the unit for concealed
until all installation procedures are installation procedures. damage before it is stored and as
complete. soon as possible after delivery.
Unit Inspection Concealed damage must be
Note: It is not the intention of this Inspect material carefully for any reported within 15 days. If con
manual to cover all possible shipping damage. If damaged, sealed damage is discovered,
variations in systems that may it must be reported to, and claims stop unpacking the shipment.
occur or to provide comprehensive made against the transportation Do not remove damaged material
information concerning every possible company. Compare the information from the receiving location.
contingency that may be encountered that appears on the unit nameplate Take photos of the damage if
during an installation. If additional with ordering and submittal data to possible. The owner must
information is required or if specific insure the proper unit was shipped. provide reasonable evidence that
problems arise that are not fully Available power supply must be the damage did not occur after
discussed in this manual, contact compatible with electrical delivery.
your local Sales office. characteristics specified on • Notify the carrier’s terminal of
component nameplates. damage immediately by phone
Note: “Warnings” and “Cautions” Replace damaged parts with and by mail. Request an immediate
appear at appropriate places in this authorized parts only. joint inspection of the damage by
manual. Your personal safety and the carrier and the consignee.
the proper operation of this machine • Notify the sales representative and
require that you follow them carefully. arrange for repair. Do not repair the
The Company assumes no liability for unit until the damage is inspected
installations or servicing performed by by the carrier’s representative.
unqualified personnel.

Table 1 - Total Unit Weight and Corner Weights Kgs (lbs)

Corner Weight-Kgs (lbs)


Shipping Maximum Net maximum
Model Kgs Lbs Kgs Lbs #1 #2 #3 #4
TTA075RD 177 389.4 157 345.4 64.5 26.1 41.0 25.4
TTA100RD 197 433.4 177 389.4 72.7 29.4 46.2 28.6
TTA120RD 241 530.2 221 486.2 90.8 23.7 80.8 13.1
TTA150RD 403 886.6 368 809.6 93.0 93.0 91.0 91.0
TTA200RD 443 974.6 408 897.6 103.0 103.0 101.0 101.0
TTA240RD 459 1009.8 424 932.8 107.0 107.0 105.0 105.0

Note: See corner weight position at Dimensional Data, p 15-16

Warning: open and lock unit disconnect to prevent injury or death from
electric shock or contact with moving parts before attempting any installation
or maintenance.

4 TTA-IOM01-EN
Installation

Lifting Recommendations Clearances


Before preparing the unit for lifting, Provide enough space around the
estimate the approximate center of unit to allow unrestricted access
gravity for lifting safety. Because of to all service points. Refer to unit
placement of internal components, dimensional data for minimum
the unit weight may be unevenly required service and free air
distributed. Approximate unit clearances. Observe the following
weights are given in Table 1. points to insure proper unit operation.

Warning: On-sight lifting equipment A. Do not install the unit under a low
must be capable of lifting the unit overhang. Condenser discharge
weight with an adequate safety factor. clearance is not less than 2.5 mm.
The use of under-capacity lifting
devices may result in severe personal Important: Do not obstruct condenser
injury or death and can seriously discharge air. This can result in warm
damage the unit. air recirculation through the coil.

The crated unit can be moved using a B. Do not locate the unit in a position
forklift of suitable capacity. For lifting where runoff water can fall into the
the unit, attach lifting straps or slings fan discharge openings.
securely to the lifting holes at each
corner. Use spreader bars to protect C. Condenser intake air is supplied
the unit casing from damage. Test lift from three sides of the unit. Adhere
the unit to determine proper balance to the minimum required clearances
and stability. given in dimensional data.

Caution: Use spreader bars to prevent Unit Mounting


lifting straps from damaging the unit. “For ground level installation, the
Install bars between lifting straps. unit base should be adequately
This will prevent the straps from supported and hold the unit near
crushing the unit cabinet or level. The installation must meet the
damaging the unit finish. guidelines set forth in local codes.”
The support should extend two inches
beyond the unit base channels at all
points. The unit and support must be
isolated from any adjacent structure to
prevent possible noise or vibration
problems. Any ground level location
must comply with required clearances
given in dimensional data.

TTA-IOM01-EN 5
Refrigerant Piping Guidelines

Refrigerant Piping C. Recommended line sizes: E. Recommended Line sizes:


To ensure the return of oil in the TTA075RD00 (Single circuit) TTA150,200 and TTA240RD0G
refrigerant lines, it is necessary to TTA150RD00 (Dual circuit) (Manifolded compressor)
follow these recommendations: Suction line Suction line
1 1/8 inch sealed type L 1 5/8 inch sealed type L
1. Select the tube lengths with care refrigerant tubing. refrigerant tubing.
and try to avoid having a final few Liquid line Liquid line
meters of tube to use up. Refer to 1/2 inch sealed type L 5/8 inch sealed type L
table 2 for tube sizes. refrigerant tubing. refrigerant tubing.
2. Pitch all horizontal suction lines
down towards the unit to assist D. Recommended Line sizes: Note: Insulate all refrigerant piping
gravity oil drainage back to the TTA100RD00 and TTA120RD00 and connections.
compressor. (single circuit)
3. Avoid creating large oil traps in TTA200RD00 and TTA240RD00
horizontal suction lines as this will (Dual circuit) Valve Cap
reduce oil circulating in the system Suction line
and may eventually lead to failure 1 3/8 inch sealed type L Valve Stem
of the compressor. refrigerant tubing.
4. A small oil trap at the end of a Liquid line Service Valve
horizontal suction line before a long 1/2 inch sealed type L
vertical riser (of more that 2.5 refrigerant tubing.
metres) has the advantage of
assisting the high velocity gas to Seal Cap
carry the oil up the vertical pipe.
5. Liquid lines require no special
installation techniques as the liquid
refrigerant R-22 and the oil mix.
The densities of the refrigerant and Gauge
oil are near enough the same so Stub Port
any movement of liquid refrigerant Connection Cap
will carry oil with it.
6. The installation of a liquid line Figure 1
sight is recommended. It is very
useful during the maintenance Table 2 - Recommended Interconnecting Lines - Condensing Units
procedures.
Length of Interconnecting Line (feet)
Refrigerant Piping Guidelines
Model 0-20 21-40 41-60 61-80
A. Maximum recommended line
lengths: (per circuit) Liq. Suct. Liq. Suct. Liq. Suct. Liq. Suct.
Maximum linear length 200 Ft. TTA075RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
(W/o accumulator) TTA100RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8
Maximum suction line lift 60 Ft.
Maximum liquid line lift 60 Ft. TTA120RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8
TTA150RD001 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
B. Maximum allowable pressure TTA200RD001 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8
drops (R-22): 1
TTA240RD00 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 3/8
Suction line 6 psi.
Liquid line 35 psi. TTA150RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
(without subcooler) TTA200RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8
Route refrigerant piping for TTA240RD0G 5/8 1 5/8 5/8 1 5/8 5/8 1 5/8 3/4 1 5/8
minimum linear length,
minimum number of bends and
Notes: 1. Two line sets are required for dual circuits units.
fittings (no reducers) and minimum
2. For line lengths over 80 linear feet and 15 feet liquid line riser,
amount of line exposed to outdoor
consult your local Trane representative.
ambients.

6 TTA-IOM01-EN
Refrigerant Piping Guidelines

Refrigerant Piping Procedures All brazing should be done using 2 1. Remove both seal caps from the
(Outdoor units) to 8 psig dry nitrogen purge flowing indoor unit connection stubs.
Each TTA unit ships with a fully through the pipe being brazed 9
charge. Due to this minimal amount, (Figure 2). Caution: Do not remove seal caps until
we recommend that it be removed prepared to braze refrigerant lines to
and the entire system evacuated Caution: Install a regulating valve the connections. Extended exposure to
(at the proper time) to avoid possible between the nitrogen source and atmosphere may allow moisture or dirt
contamination. the gauge manifold (Figure 2). to contaminate the system, damaging
1. Remove the compressor service Unregulated pressures can damage system components.
access panel. system components.
2. Locate the liquid and suction line 2. Turn nitrogen supply on. Nitrogen
service valves. Check that the Caution: Wet-wrap all valves and enters through the liquid line
piping connection stubs on the protect painted surfaces from gauge port.
valves (Figure 1) line up properly excessive heat. Heat can damage 3. Braze the liquid line connections.
with the holes in the unit cabinet. system components and the unit 4. Open the gauge port on the suction
3. Front-seat (close) both of the finish. line and then braze suction line to
service valves must be closed the connection stub. Nitrogen will
before the system is opened. 6. Shut off nitrogen supply. bleed out the open gauge port on
7. Shut off the manifold valve for the suction line.
Caution: Fully close the liquid and the line that is connected to the 5. Shut off nitrogen supply.
suction line service valves before suction line service valve.
puncturing the seal caps on the Disconnect the line from the gauge Leak Check
connection stubs. If the seal caps are port on the value. After the brazing operation of
punctured with the valves open, the refrigerant lines to both the outdoor
refrigerant contained in each circuit Refrigerant Piping Procedure and indoor unit is completed, the field
will be lost. (Indoor Unit) brazed connections must be checked
Once liquid and suction lines are for leaks. Pressurize the system
Warning: Do not heat the seal caps complete to the refrigerant through the service valve with dry
unless they have been punctured. If connections on the indoor unit, heat nitrogen to 200 psi. Use soap bubbles
caps are intact, application of heat and remove the seal caps on the or other leak-checking methods to
may generate excessive pressure in indoor unit connection stubs to ensure that all field joints are leak free.
the connection stub, causing personal release the dry nitrogen charge. If not, release pressure, repair and
injury or death due to rupturing of repeat leak test.
components and damage to the
service valve.
Suction Line Service Valve
4. Heat and remove the seal caps. Suction Line Gauge Port
Liquid Line Service Valve
Caution: Do not remove the seal
caps from refrigerant connections Liquid Line
unit prepared to braze refrigerant Gauge Port
lines to the connections. Excessive
exposure to atmosphere may allow
moisture or dirt to contaminate the
system, damaging valve seats and
causing ice formation in system
components.

5. Cut, fit and braze tubing, starting


at the outdoor unit and work toward Dry
the indoor unit. Nitrogen
Manifold Supply
Note: Use long radius ells for all 90 Gauge Pressure
degree bends. Regulating
Valve
Figure 2
TTA-IOM01-EN 7
Refrigerant Charging
and Evacuation

System Evacuation Table 3 - TTA refrigerant Charge (R-22)1


1. After completion of leak check,
evacuate the system. Model Number (Circuits) Refrigerant Charge (kg)
2. Attach appropriate hoses from TTA075RD00 5.4
manifold gauge to gas and liquid
line pressure taps. TTA100RD00 6.3
TTA120RD00 6.75
Note: Unnecessary switching of TTA150RD00 5.4 (ea. Ckt.)
hoses can be avoided and complete
TTA200RD00 6.3 (ea. Ckt.)
evacuation of all lines leading to
sealed system can be accomplished TTA240RD00 6.75 (ea. Ckt.)
with manifold center hose and TTA150RD0G 10.8
connecting branch hose to a cylinder
TTA200RD0G 12.6
of R-22 and vacuum pump.
TTA240RD0G 13.5
3. Attach center hose of manifold
gauges to vacuum pump. 1
Sufficient operating charge for outdoor unit and 25 feet
4. Evacuate the system to hold a of nominally sized refrigerant piping.
350 micron vacuum.
5. Close off valve to vacuum pump
and observe the micron gauge. Table 4 - Additional Required Refrigerant
If gauge pressure rised above
500 microns in one (1) minute, Tubing Sizes Additional Additional See
then evacuation is incomplete or Suction Liquid Tubing Length Refrigerant Note
the system has a leak.
1 1/8” 3/8” 15 ft. 0 lb. 11.5 oz. (1)
6. If vacuum gauge does not rise
above 500 microns in one (1) 1 1/8” 3/8” 25 ft. 1 lb. 3.0 oz. (1)
minute, the evacuation should be 1 1/8” 3/8” 32 ft. 1 lb. 8.0 oz. (1)
complete. 1 1/8” 3/8” 40 ft. 1 lb. 14.0 oz. (1)
7. With vacuum pump and micron
gauge blanked off, open valve on 1 3/8” 1/2” 15 ft. 1 lb. 4.0 oz. (2)
R-22 cylinder and allow refrigerant 1 3/8” 1/2” 25 ft. 2 lb. 1.0 oz. (2)
pressure to build up to about 1 3/8” 1/2” 32 ft. 2 lb. 11.0 oz. (2)
40 psig.
1 3/8” 1/2” 40 ft. 3 lb. 5.0 oz. (2)
8. Close valve on the R-22 supply
cylinder. Close valves on manifold 1 5/8” 5/8” 15 ft. 1 lb. 15.5 oz. (3)
gauge set and remove refrigerant 1 5/8” 5/8” 25 ft. 3 lb. 5.5 oz. (3)
charging hoses from liquid and gas
1 5/8” 5/8” 32 ft. 4 lb. 3.2 oz. (3)
gauge ports.
9. Leak test the entire system. Using 1 5/8” 5/8” 40 ft. 5 lb. 4.0 oz. (3)
proper procedures and caution,
1
repair any leaks found and repeat Amounts shown are based on .75 ounces of refrigerant per foot
the leak test. of 1 1/8” and 3/8” lines.
2
Amounts shown are based on 1.33 ounces of refrigerant per foot
Caution: Do not connect a of 1 3/8” and 1/2” lines.
3
dual-circuit outdoor unit to a single Amounts shown are based on 2.1 ounces of refrigerant per foot
circuit evaporating unit. (blower) of 1 5/8” and 5/8” lines.

Note: for tubing over 40 ft. calculate the additional refrigerant needed,
based on notes above.

8 TTA-IOM01-EN
Refrigerant Charging
and Evacuation

Additional Charge Procedure Pressure reading should fall


Refrigerant suitable for a tube length 1. Open liquid valve that refrigerant approximately at the points shown
of 3.5 to 7.5 meters is charged in the go through air handler unit and by the pressure curves in Service
outdoor unit at the factory. When the open suction valve. Facts. Add or remove refrigerant
tube is longer than 7.5 m, additional 2. Turn on power to the unit. Allow the (gas only) as required to obtain
charging is necessary. For the system to run for five to ten correct head and suction pressure.
additional amount, using the table 4 minutes to stabilize operating Check suction line superheat and
for recommended amounts: conditions. condenser sub-cooling to ensure
3. Measure airflow across the indoor the unit is operating properly.
Caution coil. Compare the measurements 4. Disconnect all power to the unit.
• Freon Gas “R22” only. with the fan performance data 5. Remove the charging system from
• Always evacuate air from the tubing in the Data/Submittal or Service the unit and close the opening in
before adding refrigerant. Facts. Once proper airflow is the bottom of the control box with
• Add refrigerant through the established, observe the suction the pivotal cover before attempting
charging port of liquid line valve and head pressure gauges on the to replace access panel.
after the completion of evacuation. gauge manifold. 6. Replace all panels.
• The refrigerant provided by the
manufacturer meets all the
requirements of our units. When Suction Line Service Valve
using recycled or reprocessed
refrigerant, it is advisable to ensure Suction Line Gauge Port
its quality is equivalent to that of a Liquid Line Service Valve
new refrigerant. For this, it is
necessary to have a precise Liquid Line
analysis made by a specialized Gauge Port
laboratory. If this condition is not
respected, the manufacturer’s
warranty could be cancelled.

Gaseous Charging
This procedure is accomplished
with the unit operating. Electrical
connections must be complete.
Do not proceed until the system is
ready to operate.
Manifold
Gauges

Figure 3

TTA-IOM01-EN 9
General Data

General Data - Condensing Units

TTK060KD TTA075RD TTA100RD TTA120RD


Electrical Data
Main Power supply V/Ph/Hz 380-415/3/50
Min.Brch.Cir.Ampacity A 13.4 22.45 25.82 26.87
Compressor
Number 1 1 1 1
Type Hermetic Scroll
Rated Amps (each) A 10.0 16.4 19.2 19.6
Locked rotor Amps (each) A 74 95 125 125
Motor RPM rpm 2,900 2,900 2,900 2,900
System Data
Refrigerant circuit 1 1 1 1
Suction line inch 1”1/8 1”1/8 1”3/8 1”3/8
Liquid line inch 3/8” 1/2” 1/2” 1/2”
Outdoor Coil
Type Louver fin Slit fin Slit fin Slit fin
Tube size inch 3/8 3/8 3/8 3/8
Face Area ft2 11.7 15.1 20.0 25.0
Rows # 2 2 2 2
Fins per inch (fpf) # 21(252) 16(192) 16(192) 16(192)
Outdoor Fan
Type Propeller
Number 2 1 1 1
Diameter ft 18 28 28 28
Drive type Direct
Air flow cfm 2,700 4,900 5,800 6,800
Motors Number 2 1 1 1
Motor HP (each) hp 1/15 3/4 3/4 3/4
Rated Amps (each) A 0.45 1.95 1.82 2.37
Locked rotor Amps (each) A 0.95 2.33 3.07 7.46
Motor RPM rpm 930 700 800 950
R-22 Refrigerant Charge Fully Refrigerant Charge
Dimensions HxWxD HxWxD HxWxD HxWxD
Crated mm 1,371x1,131x450 1,190x1,194x1,042 1,190x1,194x1,042 1,190x1,397x1,143
Uncrated mm 1,254x1,038x350 1,050x1,060x950 1,050x1,060x950 1,050x1,260x1,050
Weight
Net Weight kg 94.1 157 177 221

10 TTA-IOM01-EN
General Data

General Data - Condensing Units

TTA150RD00 TTA200RD00 TTA240RD00


Electrical Data
Main Power supply V/Ph/Hz 380-415/3/50
Min.Brch.Cir.Ampacity A 40.8 46.84 48.84
Compressor
Number 2 2 2
Type Hermetic Scroll
Rated Amps (each) A 16.4 19.2 19.6
Locked rotor Amps (each) 125 95 125 125
Motor RPM rpm 2,900 2,900 2,900
System Data
Refrigerant circuit 2 2 2
Suction line inch 1”1/8 1”3/8 1”3/8
Liquid line inch 1/2” 1/2” 1/2”
Outdoor Coil
Type Slit fin Slit fin Slit fin
Tube size inch 3/8 3/8 3/8
Face Area ft2 30.2 40.0 42.5
Rows # 2 2 2
Fins per inch (fpf) # 16(192) 16(192) 16(192)
Outdoor Fan
Type Propeller
Number 2 2 2
Diameter ft 28 28 28
Drive type Direct
Air flow cfm 9,800 11,600 13,600
Motors Number 2 2 2
Motor HP (each) hp 3/4 3/4 3/4
Rated Amps (each) A 1.95 1.82 2.37
Locked rotor Amps (each) A 2.33 3.07 7.46
Motor RPM rpm 700 800 950
R-22 Refrigerant Charge Fully Refrigerant Charge
Dimensions HxWxD HxWxD HxWxD
Crated mm 1,190x2,312x1,118 1,190x2,312x1,118 1,190x2,312x1,118
Uncrated mm 1,050x2,200x1,050 1,050x2,200x1,050 1,050x2,200x1,050
Weight
Net Weight kg 368 408 424

TTA-IOM01-EN 11
General Data

General Data - Condensing Units

TTA150RD0G TTA200RD0G TTA240RD0G


Electrical Data
Main Power supply V/Ph/Hz 380-415/3/50
Min.Brch.Cir.Ampacity A 40.8 46.84 48.84
Compressor
Number 2 2 2
Type Hermetic Scroll
Rated Amps (each) A 16.4 19.2 19.6
Locked rotor Amps (each) 125 95 125 125
Motor RPM rpm 2,900 2,900 2,900
System Data
Refrigerant circuit 1 1 1
Suction line inch 1”5/8 1”5/8 1”5/8
Liquid line inch 5/8” 5/8” 5/8”
Outdoor Coil
Type Slit fin Slit fin Slit fin
Tube size inch 3/8 3/8 3/8
Face Area ft2 30.2 40.0 42.5
Rows # 2 2 2
Fins per inch (fpf) # 16(192) 16(192) 16(192)
Outdoor Fan
Type Propeller
Number 2 2 2
Diameter ft 28 28 28
Drive type Direct
Air flow cfm 9,800 11,600 13,600
Motors Number 2 2 2
Motor HP (each) hp 3/4 3/4 3/4
Rated Amps (each) A 1.95 1.82 2.37
Locked rotor Amps (each) A 2.33 3.07 7.46
Motor RPM rpm 700 800 950
R-22 Refrigerant Charge Fully Refrigerant Charge
Dimensions HxWxD HxWxD HxWxD
Crated mm 1,190x2,312x1,118 1,190x2,312x1,118 1,190x2,312x1,118
Uncrated mm 1,050x2,200x1,050 1,050x2,200x1,050 1,050x2,200x1,050
Weight
Net Weight kg 368 408 424

12 TTA-IOM01-EN
Electrical Wiring

Electrical Wiring Ground the unit according to local Warning: Open the electrical
TTA field wiring consists of providing codes and provide flexible conduit if disconnect switch and lock in open
power supply to the unit, installing the codes require and/or if vibration position to prevent accidental power
system indoor thermostat. Access to transmission may cause noise application. Failure to do so may
electrical connection locations is problems. result in personal injury or death due
shown in dimensional data. to electrical shock.
Important: All wiring must comply
Unit Power Supply with applicable local and national Determine proper wire sizes and unit
The installer must provide line voltage (NEC) codes. Type and location of protective fusing requirements by
circuit (s) to the unit main power disconnect switches must comply referring to the unit nameplate and/or
terminals as shown by the unit wiring with all applicable codes. in Table 5 Field wiring diagrams for
diagrams in wiring. Power supply accessories are shipped with the
must include a disconnect switch Caution: Use copper conductors only. accessory.
in a location convenient to the unit. Unit terminals are not designed for use
with aluminum conductors. Use of
improper wiring materials can result in
equipment damage.

Refrigerant Circuit
TTA075-120RD00
(Single Circuit)
TTA150-240RD00
NOTE A
(Dual Circuit)

FIELD SUPPLIED
INTER-CONNECTING
SERVICE TUBING NOTE A
VALVE
NOTE C EQUALIZER
LOW PRESSURE TUBE
SWITCH (LPCO)
OUTDOOR COIL

EXPANSION
VALVE BULB
INDOOR COIL

NOTE A S
TXV

NOTE B
D V
COMPRESSURE
GAUGE
CONNECTION
NOTE C SERVICE
DRIER VALVE
SUB-COOLING CIRCUIT

NOTE A
HI PRESSURE INDICATES DIRECTION OF
SWITCH (HPCO) REFRIGERANT FLOW

NOTE A : ONLY ONE OUTDOOR AND INDOOR


COIL REFRIGERANT ENTRY AND
EXIT CIRCUIT IS SHOWN; ALL
MODELS HAVE MULTIPLE ENTRY
AND EXIT CIRCUITS.

Figure 6
Typical Split System Cooling Refrigerant Circuit

TTA-IOM01-EN 13
Electrical Wiring

Refrigerant Circuit
TTA150-240RD0G
(Manifolded Compressor)

NOTE A

FIELD SUPPLIED
INTER-CONNECTING
GAUGE LOW PRESSURE SERVICE TUBING
CONNECTION SWITCH (LPCO) NOTE A
VALVE
EQUALIZER
TUBE
OUTDOOR COIL

EXPANSION
VALVE BULB

INDOOR COIL
NOTE A D D
TXV

S S V
COMPRESSOR COMPRESSOR
"A" "B"
OIL EQUALIZER SERVICE
DRIER VALVE
SUB-COOLING CIRCUIT

NOTE A
HIGH PRESSURE INDICATES DIRECTION OF
SWITCH (HPCO) REFRIGERANT FLOW

NOTE A : ONLY ONE OUTDOOR AND INDOOR


COIL REFRIGERANT ENTRY AND
EXIT CIRCUIT IS SHOWN; ALL
MODELS HAVE MULTIPLE ENTRY
AND EXIT CIRCUITS.

Table 5 - TTA Unit Electrical Data


Compressor Motor Outdoor Fan Motor
Allowable Minimum Maximum Amps (each) Amps (each)
Model Electrical Voltage Circuit Fuse
Number Characteristics Range Ampacity Size Qty. RLA LRA Qty. Watt.output (each) RLA LRA
TTA075RD00 380-415/3/50 342-440 22.45 30 1 16.4 95.0 1 607 1.95 2.33
TTA100RD00 380-415/3/50 342-440 25.82 30 1 19.2 125.0 1 706 1.82 3.07
TTA120RD00 380-415/3/50 342-440 26.87 30 1 19.6 125.0 1 935 2.37 7.46
TTA150RD00 380-415/3/50 342-440 40.80 30 2 16.4 95.0 2 607 1.95 2.33
TTA150RD0G
TTA200RD00 380-415/3/50 342-440 46.84 30 2 19.2 125.0 2 706 1.82 3.07
TTA200RD0G
TTA240RD00 380-415/3/50 342-440 48.84 30 2 19.6 125.0 2 935 2.37 7.46
TTA240RD0G

14 TTA-IOM01-EN
Electrical Wiring

TTA 075, 100, 120 RD

TTA-IOM01-EN 15
Electrical Wiring

TTA 150, 200, 240 RD00

16 TTA-IOM01-EN
Electrical Wiring

TTA 150, 200, 240 RD0GM

TTA-IOM01-EN 17
Dimensional Data

TTA 075-100-120 RD

#1 #4

#3 #2

18 TTA-IOM01-EN
Dimensional Data

TTA 150-200-240 RD00

#1 #2

#3 #4

TTA-IOM01-EN 19
Dimensional Data

TTA 150-200-240 RD0G

20 TTA-IOM01-EN
Operation

Sequence of Operation Safety Controls ❏ Inspect unit location for proper


General Note: All of these controls may not be required service clearances.
Operation of the system cooling installed on your unit, check electrical ❏ Inspect unit location for proper free
cycles is controlled by the position of schematic. air clearances.
the system switch on the room ❏ Inspect unit location for secure.
thermostat. Low Pressure Cut-Out (LPCO) Level mounting position.
This control’s sensor is located in the
Evaporator Fan (Indoor Supply Air) suction (gas line, near the compressor. Refrigerant Piping
The evaporator fan is controlled by This control will stop the compressor ❏ Performed initial leak test?
an ON/AUTO switch on the room and the outdoor fans in suction ❏ Connected properly sized and
thermostat. With the switch positioned pressure drops below the Low constructed liquid and suction lines
at AUTO and the system operating in Pressure Cut-Out setting. to the connection stubs at both the
the cooling mode, fan operation indoor and outdoor units?
coincides with the cooling run cycles. High Pressure Cut-Out (HPCO) ❏ Insulated the entire suction line?
When the fan switch is positioned at This control’s sensor is located in the ❏ Insulated portions of liquid line
ON, fan operation is continuous. liquid line. This device will shut off the exposed to extremes in
compressor and the outdoor fan (s) if temperature?
Cooling Mode the discharge pressure exceeds the ❏ Evacuated each refrigerant circuit
With the disconnect switch in the High Pressure Cut-Out’s setting. to 350 microns?
“ON” position, current is supplied ❏ Charge each circuit with proper
to the compressor crankcase heater Internal Overload Protector (IOL) amount of R-22?
(s) and control transformer. The This device is a current/thermal
crankcase heater (s) supplies heat to actuated warp switch, imbedded Electrical Wiring
the compressor (s) during the “OFF” in the compressor motor windings. ❏ Provided unit power wiring (with
cycle. With the room thermostat If will shut off the compressor if disconnect) to proper terminals in
system switch positioned at COOL the temperature or current of the the unit control Section?
and the fan switch at AUTO, the compressor motor windings exceeds ❏ Installed system indoor thermostat?
compressor contactor energizes on a its design trip temperature. ❏ Installed system low voltage
call for cooling. When the contacts of interconnecting wiring to proper
the compressor contactor energizes Note: The IOL will put the terminals of outdoor unit, indoor
on a call for cooling. When the compressor back in operation once unit and system thermostat?
contacts of the compressor contactor the compressor motor heat has
close, operation of the compressor dropped below the trip setting; Unit Start-Up
and condenser fan begins. however, a check of the refrigerant Once the unit is properly installed and
The evaporator fan contactor also and electrical systems should be pre-start procedures are complete,
energizes on a call for cooling and made to determine the cause and start the unit by turning the System
initiates evaporator fan operation. be corrected. Switch on the indoor thermostat to
either COOL or AUTO. The system
On dual circuit units, when second Installation Checklist should operate normally.
stage cooling is required, Y2 from the Complete this checklist once the
indoor thermostat will energize 2nd unit is installed to verify that all Caution: Ensure the disconnect for
compressor. recommended procedures have the indoor air handler is closed before
been accomplished before starting operating the system. Operating the
Note: With the thermostat fan switch the system. Do not operate the outdoor unit without the indoor fan
in the ON position, the evaporator system until all items covered by this energized, can cause unit trip-out on
fan will operate continuously, checklist are complete. high pressure control and/or liquid
regardless of compressor or flood-back to the compressors.
condenser fan operation.

TTA-IOM01-EN 21
Maintenance

Maintenance • Inspect the evaporator and • Remove any accumulation of dust


Perform all of the indicated condenser coils for dirt and debris. and/or dirt from the unit casing.
maintenance procedures at the If the coils appear dirty, clean them. • Remove corrosion from any surface
intervals scheduled. This will prolong • With the unit operating in the and re-paint. Check the gasket
the life of the unit and reduce the cooling mode, check the suction around the control panel door to
possibility of costly equipment failure. and discharge pressures and insure it fits correctly and is in good
compare them with the values condition to prevent water leakage.
Monthly provided in “Pressure Curves”. • Remove corrosion from any surface
Conduct the following maintenance Record these readings on the and re-paint. Check the gasket
inspections once per month. “Maintenance Log”. around the control panel door to
• Observe indoor fan operation and insure it fits correctly and is in good
Warning: Open and lock unit correct any unusual or excessive condition to prevent water leakage.
disconnect to prevent injury or death vibration. Clean blower wheels as • Inspect the evaporator fan belt. If it
from electrical shock or contact with needed. is worn or frayed, replace it.
moving parts. • Inspect the control panel wiring to
Annually (Cooling Season) insure that all connections are tight
• Inspect air filters and clean if The following maintenance procedures and that the insulation is intact.
necessary. must be performed at the beginning of
• Check unit wiring to ensure all each cooling season to insure efficient Lubricate the indoor fan motor
connections are tight and that the unit operation. bearings with a non-detergent,
wiring insulation is intact. 20-weight oil. (To insure good bearing
• Check drain pans and condensate • Perform all of the monthly lubrication, condenser fan motor
piping to insure they are free of maintenance inspections. bearings should be lubricated once
obstacles. • With the unit operating, check unit every six months).
• Manually rotate the outdoor fan to superheat and record the reading
insure proper operation. Inspect in the “Maintenance Log”. Note: Some motors are permanently
the fan mounting hardware for • Remove any accumulation of dust lubricated.
tightness. and/or dirt from the unit casing. • Check refrigerant piping and fittings
for leaks.
Maintenance Log1

Evaporator
Ambient Entering air Compressor Superheat Subcooling
Temp Dry Wet Suction Discharge Circuit Circuit
Date (F) Bulb Bulb Pressure pressure No. 1 (1) No. 1 (F)

Notes:
1. Perform each inspection once per month (during cooling season) while unit is operating.
22 TTA-IOM01-EN
Trouble Shooting

Table 9: Troubleshooting Chart

Refrigerant circulation Restrictions

Change Over Valve Coil Defect


Compressor Internal Overload

Expansion Valve Stuck Open

Defrost Time Switch Defect


Excessive Evaporator Load

Restricted Outside Airflow


Refrigerant Undercharge

Change Over Valve Leak


Restricted Inside Airflow
Outside Air Recirculates
Refrigerant Overcharge
Inefficient Compressor

Defrost Control Defect


Defrost Relay Defect
Check Valve leaking
Control Transformer
High Voltage Wiring

Contactor contacts
Low Voltage Wiring

Stuck Compressor

Non Condensable
Low Voltage Fuse
Start Capacitor

Contactor Coil
Run Capacitor
Power Supply

Thermostat

Superheat
Start relay

Refrigerant Circuit
Head Pressure Too High P S P S S
Head Pressure Too Low S P S S S P
Suction pressure too high S P P S S S P
Suction pressure too low P S P S
Liquid overfeeding P P
(expansion valve)
Liquid overfeeding P S S S P
(cap tube)
Inside coil frosting P S S
Compress. runs-inadequate S P S S S P S S S S
or no cooling/heating

Electrical
Compressor and outside P P S P S P P
fan won’t start
Compressor will not start P S P P S S P
but outside fan runs
Outside fan won’t start P P S
Compressor hums P P S S P
but won’t start
Compressor cycles P S P S S S P S P P S S S P S
on internal overload
Inside fan won’t start P P S P S S

P : primary cause
S : secondary cause

TTA-IOM01-EN 23
Safety recommendations Maintenance contract Training
To avoid accidents and damage, the It is strongly recommended that you The equipment described in this
following recommendations should be sign a maintenance contract with your manual is the result of many
observed during maintenance and local Service Agency. This contract years of research and continuous
service visits: provides regular maintenance of your development. To assist you in
1. The maximum allowable pressures installation by a specialist in our obtaining the best use of it, and
for system leak testing on low and equipment. Regular maintenance maintaining it in perfect operating
high pressure side are given in the ensures that any malfunction is condition over a long period of time,
chapter “Installation”. Always detected and corrected in good time the constructor has at your disposal
provide a pressure regulator. and minimizes the possibility that a refrigeration and air conditioning
2. Disconnect the main supply before serious damage will occur. Finally, service school. The principal aim
any servicing on the unit. regular maintenance ensures the of this is to give operators and
3. Service work on the refrigeration maximum operating life of your maintenance technicians a better
system and the electrical system equipment. We would remind you knowledge of the equipment they are
should be carried out only by that failure to respect these installation using, or that is under their charge.
qualified and experienced and maintenance instructions may Emphasis is particularly given to the
personnel. result in immediate cancellation of importance of periodic checks on the
the warranty. unit operating parameters as well as
on preventive maintenance, which
reduces the cost of owning the unit
by avoiding serious and costly
breakdown.

Trane Thailand Literature Order Number: TTA-IOM01-EN 0801


7th Floor, Ploenchit Center Building
Supersedes: TTA-IOM01-EN 0201
2 Sukhumvit Road, Klongtoey
Bangkok 10110 Stocking Location: Bangkok, Thailand
Amair Limited
35 Mu 8, Poochaosamingprai Road ∫√‘…—∑ ·Õ¡·Õ√Ï ®”°—¥ 35 À¡ŸË 8 ∂.ªŸË‡®È“ ¡‘ßæ√“¬ µ. ”‚√ß„µÈ Õ.æ√–ª√–·¥ß ®. ¡ÿ∑√ª√“°“√ 10130
Samrong Tai, Samutprakarn 10130
http://www.trane.com Since The Trane Company has a policy of continuous product and product data improvement,
An American Standard Company it reserves the right to change design and specifications without notice.

You might also like