EM-MPO/350
Multi-parameter Electricity Meter
Contents
1 Unpacking................................................1 3 Installation................................................1
2 Storing......................................................1 4 Disposal....................................................8
1 Unpacking
EM-MPO/350
Installation Instructions
TG201107
3 Installation
It is recommended that the
installation should comply with the
Mounting Requirements HSE Memorandum of Guidance on
1 Electricity at Work Regulations 1989.
EM-MPO/350
<75 %RH
H2 O
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Protection IP20
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
15 16 17 29 30 31 32
Isolated Isolated 15 16 17 29 30 31 32
Serial Comms Pulse outputs 15 16 17 29 30 31 32 Isolated Isolated
A B 0V Pls2 Pls1 Serial Comms Pulse outputs
Isolated Isolated A B 0V Pls2 Pls1
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
EM-MPO/350
3 Installation (continued)
Mounting Requirements (continued)
1
Use EM-MPO/350 with either the EMIC or IQ3/XNC/SER (with
MODBUS driver)
2.5 m (9’10”) cable supplied with EMIC
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
EMIC
EM-MPO/350
IQ3/XNC/SER
- +
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
Vn V1 V2 V3 +l1- +l2- +l3-
(MODBUS DRIVER)
Current
Inputs 15 16 17 29 30 31 32
1 2 3 4 5 6 7 8 9 10 11 12
Isolated Isolated 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10
Serial Comms Pulse outputs + 0 + 0 + 0 + 0 + 0 + 0 + 0 + 0 + 0
A B 0V Pls2 Pls1
EM-MPO/350
24 V
24 V
OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
0V
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
RS485
Inputs
1 2 3 4 5 6 7 8 9 10 11 12
DO NOT SWITCH
ON
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
L N ~
1 2 3 4 5 6 7 8 9 10 11 12
230 Vac
Single part screw terminals, maximum cross section area cable 4 mm2 (12 AWG)
Note that this instrument does not require an earth (ground) connection
3 Installation (continued)
EM-MPO/350
nominal current: 5 A,
nominal voltage:
230 Vac (phase to neutral),
400 Vac (phase to phase)
Programmable:
CTs primary: 5 A to 25 kA,
CSENSORS: primary
5 A to 800 A
VTs primary: 11 V to
440 kV (EM-MPO/350) Single phase (can use VT)
55 kV (EM-MPO/350e)
Note that
EM-MPO/350 uses CTs,
EM-MPO/350e uses
current sensors
(CSENSOR) - see step 6
3 Installation (continued)
P1 P2
Supply Load
Current
CT
P1 P2
P1 P2 S1 (+) Black
Supply Load Supply Load
K
P = Primary S = Secondary
3 Installation (continued)
Pulse 2
Isolated Isolated
Monitor
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
EM-MPO/350 kVArh 30 A
Pulse 1 Monitor
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12
Connect to EMIC
9
If using EMIC
Single part screw terminals, maximum cross section area cable 4 mm2 (12 AWG)
2.5 m (9’10”) cable supplied with EMIC
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V
EM-MPO/350
15 16 17
A B 0V
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
1 2 3 4 5 6
EMIc
RJ45 Port 1
0V
3 2 4
Orange
Black
Red
Red
Orange
15 16 17 15 16 17 15 16 17 15 16 17
a B 0V a B 0V a B 0V a B 0V
meter meter meter meter
IQ3/XNC/SER
(MODBUS DRIVER)
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V
EM-MPO/350 T
T T
integral
RB
terminator
IQ3/XNC/SER
RA
B
T
terminator
T
a observe correct polarity
0V
15 16 17 15 16 17 15 16 17
a B 0V a B 0V a B 0V
Switch On
11
O
3 Installation (continued)
Configure Meter
12
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V
EM-MPO/350
TE201114
Notes:
1. EM-MPO/350, CT set values 5 to 25 kA. EM-MPO/350e,CSENSOR values 5, 50, 100, 150, 400,
800
2. If no VT, set to 400 (set PT scale to 1).
If VT fitted and primary volts <60 kV, set Nominal Volts to VT primary (set PT scale to 1).
If VT fitted and primary volts >60 kV, set Nominal Volts to 6600 (set PT Scale to primary volts/6600)
Note that PT Scale is set over MODBUS.
[Readable voltage range: EM-MPO/350 (11 V to 440 kV) EM-MPO/350e (11 V to 55 kV)]
3. Fine adjust Nominal volts and CT primary (EM-MPO/350 only) allows settings other than
those in default tables. P I enters and exits Fine Adjust.
4 The Output Pulse Rate sets the value of each pulse in kWh - pulse 1, kVArh - pulse 2 (range 1 to
1000 counts of register). The Pulse On Time is the pulse duration in secs (range 0.1 to 20 s)
5. The hours run trip point is the 3 phase current level, (I1+I2+I3)/3, above which the hours run
counter will increment. The setting is a percentage of CT Primary current.
6. Voltage input mode can be changed to Balanced Voltage Mode (bAL 3Ph) (recommended EM-
MPO/350e only). Voltage measured on phase 1 is copied to other two phases, all 3 power factors
set to unity. Valid for near unity power factors, and balanced 3 phase voltages.
7. CT Auto Rotation Mode (default) ignores CT connection polarity. De-select auto rotation (truE
rot) if power is to be imported or exported.
8. Set baud rate to match controller (and other meters), can be set to 4k8, 9k6, 19k2 baud.
Note that meter protocol fixed at MODBUS RTU (IEEE) with 16 bit CRC, 8 bit + start bit+ stop
bit, no parity
9 Selecting ‘Storing’ (Stor in9) stores changes to non-volatile memory.
3 Installation (continued)
Check System
14 Either
A
V
kW
Or
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V
EM-MPO/350
IQ3/XNC/SER
TX
RX
RTS/TXEN
(MODBUS DRIVER)
CTS/RXEN
A
Inputs
1 2 3 4 5 6
V
kW
4 Disposal
WEEE Directive:
At the end of their useful life the packaging and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.
Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com
© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.