Installation Instructions

EM-MPO/350
Multi-parameter Electricity Meter

Important: Retain these instructions

Contents
1 Unpacking................................................1 3 Installation................................................1
2 Storing......................................................1 4 Disposal....................................................8

1 Unpacking

EM-MPO/350
Installation Instructions
TG201107

2 Storing -25 °C +70 °C <75 %RH


-23 °F +158 °F
H2 O

3 Installation
It is recommended that the
installation should comply with the
Mounting Requirements HSE Memorandum of Guidance on
1 Electricity at Work Regulations 1989.

106 mm (4.18”) 58 mm (2.28”)


-10 °C +65 °C
15 16 17 29 30 31 32 +14 °F +149 °F
Isolated Isolated
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
95.5 mm (3.75”)

EM-MPO/350
<75 %RH

H2 O
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-

Protection IP20
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12

15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
15 16 17 29 30 31 32
Isolated Isolated 15 16 17 29 30 31 32
Serial Comms Pulse outputs 15 16 17 29 30 31 32 Isolated Isolated
A B 0V Pls2 Pls1 Serial Comms Pulse outputs
Isolated Isolated A B 0V Pls2 Pls1
Serial Comms Pulse outputs
A B 0V Pls2 Pls1

EM-MPO/350

CURRENT INPUTS - DO NOT USE STANDARD CTs


CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
- + Vn V1 V2 V3 +l1- +l2- +l3- Current
Current Inputs
Inputs CURRENT INPUTS - DO NOT USE STANDARD CTs 1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12 use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12

EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011 1


EM-MPO/350 Installation Instructions

3 Installation (continued)

Mounting Requirements (continued)
1
Use EM-MPO/350 with either the EMIC or IQ3/XNC/SER (with
MODBUS driver)
2.5 m (9’10”) cable supplied with EMIC
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V Pls2 Pls1

EMIC
EM-MPO/350

IQ3/XNC/SER
- +
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
Vn V1 V2 V3 +l1- +l2- +l3-
(MODBUS DRIVER)
Current
Inputs 15 16 17 29 30 31 32
1 2 3 4 5 6 7 8 9 10 11 12
Isolated Isolated 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
1 2 3 4 5 6 7 8 9 10
Serial Comms Pulse outputs + 0 + 0 + 0 + 0 + 0 + 0 + 0 + 0 + 0
A B 0V Pls2 Pls1

EM-MPO/350

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers 100-240 V A 11 12 13 14 15 16
P 0 P 0 P 0 P 0 P 0 P 0

24 V

24 V
OK RX P 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

0V
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current

RS485
Inputs
1 2 3 4 5 6 7 8 9 10 11 12

Mount DIN Rail Mount Meter on DIN Rail


2 3
106 mm (4.17”) minimum

Connect Power Input to Meter


4 230 Vac 50/60 Hz ±15 % @ 5 W maximum
_
15 16 17
Isolated Isolated
29 30 31 32
+ O
Serial Comms Pulse outputs
A B 0V Pls2 Pls1
1 2 I
EM-MPO/350

DO NOT SWITCH
ON
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
L N ~
1 2 3 4 5 6 7 8 9 10 11 12
230 Vac

Single part screw terminals, maximum cross section area cable 4 mm2 (12 AWG)
Note that this instrument does not require an earth (ground) connection

2 EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011


Installation Instructions EM-MPO/350

3 Installation (continued)

Connect Measurement Connections


5
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V Pls2 Pls1

EM-MPO/350

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12

Single part screw terminals,


maximum cross section area
cable 4 mm2 (12 AWG) 3 phase 3 or 4 wire - Star or Delta (can use VTs)

nominal current: 5 A,

nominal voltage:
230 Vac (phase to neutral),
400 Vac (phase to phase)

Programmable:
CTs primary: 5 A to 25 kA,
CSENSORS: primary
5 A to 800 A
VTs primary: 11 V to
440 kV (EM-MPO/350) Single phase (can use VT)
55 kV (EM-MPO/350e)

Note that
EM-MPO/350 uses CTs,

EM-MPO/350e uses
current sensors
(CSENSOR) - see step 6

3 phase high voltage using 2 VTs and 2 CTs (EM-MPO/350 only)

3 phase using 2 CTs - Delta (EM-MPO/350 only)

EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011 3


EM-MPO/350 Installation Instructions

3 Installation (continued)

Ensure CTs and CSENSORs have Correct Polarity


6
S1 (+) red S2 (-) Black

P1 P2
Supply Load

Current

CT

S2 (-) white S1 (+) black


(black/white)

P1 P2
P1 P2 S1 (+) Black
Supply Load Supply Load
K

Current Current S2 (-) White (Black/white)


K L
CSENSOR
10A, 100A CSENSOR
150A, 400A, 800A

P = Primary S = Secondary

Ensure connection to a meter has correct polarity.


CT (Trend): +(red), - (black);
CSENSOR (Trend):+(black),-(white or black/white).
Ensure current passes through CT or CSENSOR in correct direction.
Ensure CT or sensor is connected to same phase as associated VT..

Mount EMIC or IQ3.../XNC/SER


7

EMIC Installation Instructions,TG201082, Section 3.1 steps 1 to 6


OR
IQ3xcite Installation Instructions,TG200626,
IQ3xact Installation Instructions,TG200766,
IQ3/XNC Installation Instructions,TG200911
IQ3/XNC MODBUS Drivers Manual,TE201101

4 EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011


Installation Instructions EM-MPO/350

3 Installation (continued)

Connect Pulse Outputs


8 If required
100 mA ac/dc max., 100 V ac/dc max., 0.5 W max load
29
15 16 17 29 30 31 32

Pulse 2
Isolated Isolated

Monitor
Serial Comms Pulse outputs
A B 0V Pls2 Pls1

EM-MPO/350 kVArh 30 A

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers
31
- + Vn V1 V2 V3 +l1- +l2- +l3-

Pulse 1 Monitor
Current
Inputs
1 2 3 4 5 6 7 8 9 10 11 12

Note: Output Pulse Rate (value of each pulse - kWh, kWh 32 B


kVArh), Pulse On Time (duration - s) settable in step 12

Connect to EMIC
9
If using EMIC

Single part screw terminals, maximum cross section area cable 4 mm2 (12 AWG)
2.5 m (9’10”) cable supplied with EMIC

15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V

EM-MPO/350

15 16 17

A B 0V
CURRENT INPUTS - DO NOT USE STANDARD CTs
use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
1 2 3 4 5 6

EMIc

RJ45 Port 1
0V
3 2 4
Orange
Black

Red

observe correct polarity


Black terminator
terminator

Red
Orange
15 16 17 15 16 17 15 16 17 15 16 17

a B 0V a B 0V a B 0V a B 0V
meter meter meter meter

For runs >30 m use 150 ohm terminators each end.


Maximum length is 1000 m @ 9600 Baud, with 26 AWG cable
Maximum number of meters (8, 16, 32 dependant on EMIC version).

EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011 5


EM-MPO/350 Installation Instructions

Connect to IQ3../XNC/SER (for MODBUS Driver)


10 If using MODBUS driver

IQ3/XNC/SER
(MODBUS DRIVER)
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V

EM-MPO/350 T

T T

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
1 2 3 4 5 6
Inputs
RS485

integral
RB
terminator
IQ3/XNC/SER

RA

B
T
terminator
T
a observe correct polarity
0V

15 16 17 15 16 17 15 16 17

a B 0V a B 0V a B 0V

meter meter meter

For runs >30 m use 120 ohm terminators each end.


Maximum length is 1000 m @ 9600 Baud, with 26 AWG cable

Switch On
11
O

6 EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011


Installation Instructions EM-MPO/350

3 Installation (continued)

Configure Meter
12
15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V

EM-MPO/350

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers
5s
EM-MPO/350 Operating Manual,
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current
Inputs
1 2 3 4 5 6

TE201114

Pages Parameters Default Note


Pin Security code (not Set Up)
Ct A CT(CSENSOR) primary 200 A 1,3
Un V Nominal line to line V 400 V 2,3
PLr KWh Output Pulse Rate 0.1 kWh 4
PLt Pulse On Time 0.1 s 4
Pto Pulse Output Test
Hr Hours Run Trip Point 100 5
trUE 3Ph Voltage Input Mode 6
Auto rot CT Auto Rotation Mode 7
Br Baud Rate 9600 8

Addr Unique Modbus Address 25


Stor in9 Store to non Volatile Memory 9

Press P E , to increase, decrease value respectively

Notes:
1. EM-MPO/350, CT set values 5 to 25 kA. EM-MPO/350e,CSENSOR values 5, 50, 100, 150, 400,
800
2. If no VT, set to 400 (set PT scale to 1).
If VT fitted and primary volts <60 kV, set Nominal Volts to VT primary (set PT scale to 1).
If VT fitted and primary volts >60 kV, set Nominal Volts to 6600 (set PT Scale to primary volts/6600)
Note that PT Scale is set over MODBUS.
[Readable voltage range: EM-MPO/350 (11 V to 440 kV) EM-MPO/350e (11 V to 55 kV)]
3. Fine adjust Nominal volts and CT primary (EM-MPO/350 only) allows settings other than
those in default tables. P I enters and exits Fine Adjust.

4 The Output Pulse Rate sets the value of each pulse in kWh - pulse 1, kVArh - pulse 2 (range 1 to
1000 counts of register). The Pulse On Time is the pulse duration in secs (range 0.1 to 20 s)
5. The hours run trip point is the 3 phase current level, (I1+I2+I3)/3, above which the hours run
counter will increment. The setting is a percentage of CT Primary current.
6. Voltage input mode can be changed to Balanced Voltage Mode (bAL 3Ph) (recommended EM-
MPO/350e only). Voltage measured on phase 1 is copied to other two phases, all 3 power factors
set to unity. Valid for near unity power factors, and balanced 3 phase voltages.
7. CT Auto Rotation Mode (default) ignores CT connection polarity. De-select auto rotation (truE
rot) if power is to be imported or exported.
8. Set baud rate to match controller (and other meters), can be set to 4k8, 9k6, 19k2 baud.
Note that meter protocol fixed at MODBUS RTU (IEEE) with 16 bit CRC, 8 bit + start bit+ stop
bit, no parity
9 Selecting ‘Storing’ (Stor in9) stores changes to non-volatile memory.

EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011 7


EM-MPO/350 Installation Instructions

3 Installation (continued)

Configure MODBUS Driver


13 If using MODBUS driver

The MODBUS driver needs to be configured to


read the meter. This requires understanding the
communication codes for the parameters to be read. IQ3/XNC MODBUS Driver Manual, TE201101.
EM-MPO/350 MODBUS Communications
Manual, TE201115

Check System
14 Either
A
V
kW
Or

15 16 17 29 30 31 32
Isolated Isolated
Serial Comms Pulse outputs
A B 0V

EM-MPO/350
IQ3/XNC/SER
TX

RX

RTS/TXEN

(MODBUS DRIVER)
CTS/RXEN

CURRENT INPUTS - DO NOT USE STANDARD CTs


use only special 0.33V ac output transducers
- + Vn V1 V2 V3 +l1- +l2- +l3-
Current

A
Inputs
1 2 3 4 5 6

V
kW

4 Disposal

WEEE Directive:
At the end of their useful life the packaging and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.

Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com

© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.

Trend Control Systems Limited


Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control System USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trendcontrols.com

8 EM-MPO/350 Installation Instructions TG201107 Issue 2, 19/01/2011