SERVICE REPORT

HOT OIL BOILER

CLIENT : AICA BANGKOK CO.,LTD.

LOCATION : BANGSAOTHONG, SAMUTPRAKARN

SUBJECT : SERVICE REPORT

MODEL : HOH 252

BOILER NO. : #1

TS. JOB NO : 66-090-099

PO. NO : PO

.THAI STEAM SERVICE & SUPPLY CO., LTD


SUKHUMVIT 101 BANGCHAK PHRAKANONG BANGKOK 10260 THAILAND 754/31-32
TEL: (+66) 2332-8246-7 , 2332-7700-3 , 2311-4827 FAX: (+66) 2311-4840 E-mail : thaisteam@thaisteam.co.th
TEL: (+66) 2332-8246-7 , 2332-7700-3 , 2311-4827 FAX: (+66) 2311-4840 E-mail : thaisteam@thaisteam.co.th
RVICE REPORT
T OIL BOILER

& SUPPLY CO., LTD


ANGKOK 10260 THAILAND 754/31-32
AX: (+66) 2311-4840 E-mail : thaisteam@thaisteam.co.th
AX: (+66) 2311-4840 E-mail : thaisteam@thaisteam.co.th
IPR DOC.
NO : 66-090-099
SERVICE REPORT REV. 0

SERVICE REPORT

Contents

Description Page
Inspection team & Equipment 1
service form 2
Burner Checking 3
Defect report 4
บริษัท ไทยสตีมเซอร์ วสิ แอนด์ ซัพพลาย จำกัด JOB NO. 66-090-099

THAI STEAM SERVICE & SUPPLY CO., LTD. SHEET 1 OF 4

Inspection team & Equipment


AICA BANGKOK CO.,LTD
Site/Plant: INSPECTION PREVENTIVE MAINTENANCE
Location / Boiler #: BANGSAOTHONG,SAMUTPRAKARN year. 2013 no. 1
Boiler Manufacturer: Thai Steam
National / State Board # N/A BMS Manufacturer & Model # HEATER 252kW
Type (Hot Oil /Steam) Hot oil Date:18/08/66 09.00 - 17.00

1. Inspection team & Equipment


Thai steam service name list
คุณ วิชยั นามาก
คุณวรากานต์ ขาวผิว
คุณสิ ทธิ นนท์ พงษ์ศิลา
2. Scope of work

1.งานเปลี่ยนวงแหวน HEATER
2.งานทดสอบการทำงานของอุปกรณ์

REMARK

INSPECTION BY APPROVED BY

SIGNATURE : วรากานต์ ขาวผิว SIGNATURE : วุฒิชยั สาระธรรม


NAME : คุณวรากานต์ ขาวผิว NAME : คุณวุฒิชยั สาระธรรม
POSITION : JOB HEAD POSITION : HEAD OFFICE
DATE 18 / 8 / 66 DATE 18 / 8 / 66
บริษัท ไทยสตีมเซอร์ วสิ แอนด์ ซัพพลาย จำกัด JOB NO. 66-090-099

THAI STEAM SERVICE & SUPPLY CO., LTD. SHEET 2 OF 4

HOT OIL BOILER HOT WATER BOILER STEAM BOILER


FUNCTION TEST COMMISSIONING & TEST RUN SERVICE
BOILER MODEL : HOH - 252 YEAR 2013 COMPANY : AICA BANGKOK CO.,LTD.

BURNER MODEL : HEATER ไฟฟ้า 1400 w 18ต ัว YEAR ADDRESS : 156/2 M00 17 BANGNA-TRAD K.M.23 RD.,BANGSAOTHONG,
SIZE : 252 KW BANGSAOTHONG, SAMUTPRAKARN
Tel.
CONTACT PERSON : คุณนครินทร์ JOB NO. 66-090-099 WORK DATE : 18 / 08 / 66
STEAM BOILER HOT OIL BOILER
1.SUPPLY PRESSURE BARG 1.SUPPLY TEMPERATURE ≤ ( 300 °C ) 200 0
C
2.ROOM TEMPERATURE ~
– ( 40 °C ) 0
C 2.RETURN TEMPERATURE ≤ ( 25 °C ) 202 0
C
3.FLUE GAS THERMOSTAT ≤ ( 300 °C ) 0
C 3.ROOM TEMPERATURE ~– ( 40 °C ) 35 0
C
4.SAFETY VALVE ( ) NORMAL ( ) NOT 4.FLUE GAS THERMOSTAT ≤ ( 350 °C ) - 0
C
5.GASKET ( ) NORMAL ( ) NOT 5.SAFETY THERMOSTAT ≤ ( 320 °C ) 201 0
C
6.LEAKAGE ( ) NORMAL ( ) NOT 6.DIFFERENTIAL NO.1 ( 0.15 - 0.27 ) 0.3 BARG
7.COMBUSTION CHAMBER ( ) NORMAL ( ) NOT 7.DIFFERENTIAL NO.2 ( 0.15 - 0.27 ) BARG
8.WATER LEVEL CONTROL ( ) NORMAL ( ) NOT 8.DIFFERENTIAL NO.3 ( 0.15 - 0.27 ) BARG
9.PRESSURE SWITCH ( ) NORMAL ( ) NOT 9.LEVEL SWITCH ( ü ) NORMAL ( ) NOT
10.BLOW DOWN SYSTEM ( ) NORMAL ( ) NOT 10.SAFETY VALVE ( ü ) NORMAL ( ) NOT
FEED WATER PUMP. 11.GASKET ( ü ) NORMAL ( ) NOT
1.MODEL Q. m3/h. H. m. 12.LEAKAGE ( ü ) NORMAL ( ) NOT
2.COUPLING ( ) NORMAL ( ) NOT 13.COMBUSTION CHAMBER ( ) NORMAL ( ) NOT
3.VIBRATION ( RANGE ≤ 3.5 mm/s ) ( ) NORMAL ( ) NOT CIRCULATING PUMP
NTT32-160/01-U5A-W4 m.
4.DISCHARGE PRESSURE BARG 1.MODEL Q. m3/h. H.
5.SUCTION PRESSURE BARG 2.COUPLING ( ü ) NORMAL ( ) NOT
6.MOTOR FEED.PUMP CURRENT ________ KW. _____ / ______ / ______ A. 3.VIBRATION ( RANGE ≤ 3.5 mm/s ) ( ) NORMAL ( ) NOT
BURNER 4.DISCHARGE PRESSURE 2 BARG
1.FUEL TYPE ( ) OIL ( ) GAS - 5.SUCTION PRESSURE 0.5
BARG
2.FUEL TEMPERATURE ( ) OIL ( ) GAS - 0
C 6.MOTOR CIR.PUMP CURREN 4 KW. 7.5 / 7.3 / 7.2 A.

3.FUEL PRESSURE ( ) OIL ( ) GAS - BARG BURNER

4.IGNITION ELECTRODE ( ) NORMAL ( ) NOT 10. CONTROL PANEL ( ü ) NORMAL ( ) NOT


5.FLAME SENSOR ( ) NORMAL ( ) NOT 11. O2 ( 2.5-4.5 % ) - %
6.FLAME TUBE ( ) NORMAL ( ) NOT 12 . CO ( < 200 ppm ) - ppm
7.DIFFUSER ( ) NORMAL ( ) NOT 13. CO2 –~ ( 11-13 % ) - %
8.NOZZLE NO. ( ) NORMAL ( ) NOT 14. SOOT NUMBER ( ≤ No.3 ) -
9.FUEL SYSTEM ( ) OIL ( ) GAS ( ) NORMAL ( ) NOT 15. MOTOR BURNER CURRENT - KW. - / - / - A.
REMARK ทำการเปลี่ยนแหวนทองแดงใหม่ พร้อมเสริ มความหนาด้วยประเก็นกราไฟท์ ทั้งหมด5ตัว
ตรวจสอบพบ HEATER A1ขดคอยล์ OVER HEAT ขาด1คอยล์ ทำการถอดสายไฟออกไม่ให้อุปกรณ์ท ำงาน
ทดสอบการใช้งานให้ท ำอุณหภูมิถึง 200 C ตามที่ลูกค้าใช้งาน
ตรวจสอบการรั่วซึ ม ไม่พบการรั่วซึ มที่อุณหภูมิ 200 C
INSPECTION BY APPROVED BY

SIGNATURE : วรากานต์ ขาวผิว SIGNATURE : วุฒิชยั สาระธรรม


NAME : คุณวรากานต์ ขาวผิว NAME : คุณวุฒิชยั สาระธรรม
POSITION : JOB HEAD POSITION : HEAD OFFICE
DATE : 18 / 08/ 66 DATE : 18 / 08/ 66 FR-IS-02-04 -22-02-65
1. บันทึกการตรวจสอบ ถังสำรองน้ำมัน
(DRAIN TANK)
(DRAIN TANK)

ข้อมูลถังสำรองน้ำมัน (Drain Tank)

Model
Serial No.
Mfg. Date
บริษทั ไทยสตีมเซอร์ วสิ แอนด์ ซัพพลาย จำกัด JOB NO. 66-090-099

THAI STEAM SERVICE & SUPPLY CO., LTD. SHEET 4 OF 4

Description : BOILER Checking

งานตรวจสอบ
HEATER
ตำแหน่ง A1

งานตรวจสอบ
HEATER
ตำแหน่ง A1
ชำรุ ด

งานตรวจสอบ
HEATER วัดค่าขึ้นปกติ 2 คอยล์ วัดค่าไม่ขขึ้น 1 คอยล์
ตำแหน่ง A1

REMARK ตรวจสอบพบ HEATER ตำแหน่ง A1 มีการ OVER HEAT ขาด1คอยล์


ทำการถอดสายไฟออกไม่ให้อุปกรณ์ท ำงาน

INSPECTION BY APPROVED BY

SIGNATURE : วรากานต์ ขาวผิว SIGNATURE : วุฒิชยั สาระธรรม


NAME : คุณวรากานต์ ขาวผิว NAME : คุณวุฒิชยั สาระธรรม
POSITION : JOB HEAD POSITION : HEAD OFFICE
DATE : 18 / 8 / 66 DATE : 18 / 8 / 66