You are on page 1of 9

IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO.

5, SEPTEMBER 2004 1205

A Wireless Controller to Enhance Dynamic


Performance of Parallel Inverters in
Distributed Generation Systems
Josep M. Guerrero, Member, IEEE, Luis García de Vicuña, José Matas, Miguel Castilla, and
Jaume Miret, Member, IEEE

Abstract—This paper presents a novel control strategy for par- the droop method [8]–[11]. To achieve good power sharing, the
allel inverters of distributed generation units in an ac distribution control loop makes tight adjustments over the output voltage fre-
system. The proposed control technique, based on the droop con-
quency and amplitude of the inverter, in order to compensate the
trol method, uses only locally measurable feedback signals. This
method is usually applied to achieve good active and reactive power active and reactive power unbalances [12]. This concept steams
sharing when communication between the inverters is difficult due from the power system theory, in which a generator connected
to its physical location. However, the conventional voltage and fre- to the utility mains drops its frequency when the power required
quency droop methods of achieving load sharing have a slow and increases [13].
oscillating transient response. Moreover, there is no possibility to
modify the transient response without the loss of power sharing In the literature, there are many control schemes based on the
precision or output-voltage and frequency accuracy. In this work, a droop method to share linear loads [14]. Nevertheless, nowadays
great improvement in transient response is achieved by introducing the proliferation of nonlinear loads has become a problem, be-
power derivative-integral terms into a conventional droop scheme. cause the units must both share harmonic current and to balance
Hence, better controllability of the system is obtained and, conse- active and reactive power. In [15], a controller was proposed
quently, proper transient performance can be achieved. In addi-
tion, an instantaneous current control loop is also included in the to share nonlinear loads by adjusting the output voltage band-
novel controller to ensure proper sharing of harmonic components width with the delivered harmonic power. However, this tech-
when supplying nonlinear loads. Simulation and experimental re- nique has two main limitations: the controller uses an algorithm
sults are presented to prove the validity of this approach, which which is too complicated to calculate the harmonic current con-
shows excellent performance as opposed to the conventional one. tent, and the harmonic current sharing is achieved at the expense
Index Terms—Distributed generation (DG), droop control of reducing the stability of the system. Recently, novel control
method, nonlinear loads. loops that adjust the output impedance of the units by adding
virtual resistors [16] or reactors [17] have been included in the
I. INTRODUCTION droop method, with the purpose to share the harmonic current
content properly. In another approach [18], every single term of

D ISTRIBUTED generation (DG) systems are presented as a


suitable form to offer high reliable electrical power supply
[1]. The concept is particularly interesting when different kinds
the harmonic current is used to produce a proportional droop in
the corresponding harmonic voltage term, which is added to the
output-voltage reference. Nevertheless, the control approaches
of energy resources are available, such as photovoltaic panels, mentioned above have an inherent tradeoff between voltage reg-
fuel cells, or speed wind turbines [2], [3]. Most part of these ulation and power sharing. Besides, the droop method exhibits
resources need power electronic interfaces to make up local ac slow dynamic response, since it requires low-pass filters with a
grids [4], [5]. This way, inverters or ac-to-ac converters are con- reduced bandwidth to calculate the average value of the active
nected to an ac common bus with the aim to share properly the and reactive power [19]. Then, the stability and the dynamics of
disperse loads connected to the local grid [6]. In addition, every the whole system are strongly influenced by the characteristics
unit must be able to operate independently when communica- of these filters and by the value of the droop coefficients, which
tion is too difficult due to the long distance between its con- are bounded by the maximum allowed deviations of the output
nection points [7]. In this sense, several control techniques have voltage amplitude and frequency.
been proposed without control wire interconnections based on In this paper, we propose a novel control scheme that is able
to improve the transient response of parallel-connected inverters
without using communication signals. A wireless controller was
Manuscript received July 16, 2003; revised June 3, 2004. This paper was pre- developed, by adding a supplemental transient droop character-
sented in part at PESC’03, Acapulco, México, June 15–19, 2003. This work was
supported by the Spanish Ministry of Science and Technology under CICYT istic to the conventional static droop approach, which improves
DPI 2003-06508-C02-01. Recommended by Associate Editor I. Gadoura. the paralleled-system dynamics. The novel droop function en-
The authors are with the Departament d’Enginyeria de Sistemes, Automàtica sures both steady-state objectives and a good transient perfor-
i Informàtica Industrial, Departament d’Enginyeria Electrònica, Universidad
Politécnica de Cataluña, Barcelona, Spain (e-mail: josep.m.guerrero@upc.es). mance. Simulation and experimental results are reported, con-
Digital Object Identifier 10.1109/TPEL.2004.833451 firming the validity of this control technique.
0885-8993/04$20.00 © 2004 IEEE
1206 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004

Fig. 3. Static droop characteristics P 0 ! and Q 0 E .

Fig. 1. Distributed generation units connected in parallel to a common ac bus.

Fig. 2. Equivalent circuit of an inverter connected to a bus.

II. REVIEW OF THE CONVENTIONAL DROOP METHOD


Fig. 1 shows a DG system made up of different kind of re-
Fig. 4. Tradeoff between frequency deviation and active power sharing (droop
sources, such as solar panels, fuel cells, and speed wind tur- coefficient m > m).
bines. As mentioned previously, every resource needs an electric
power interface to transfer energy to the common bus. We can voltage regulation [15], which can be acceptable if, for instance,
model every unit as an inverter connected to the common bus the frequency and amplitude deviations are mostly at 2% and
through a decoupling impedance, as shown in Fig. 2. Usually the 5%, respectively (see Figs. 3 and 4). The inherent tradeoff of
inverter output impedance is highly inductive, this scheme restricts the mentioned coefficients, which can be a
and, hence, the active and reactive powers drawn to the bus can serious limitation in terms of transient response, power sharing
be expressed as [13] accuracy, and system stability [19].
On the other hand, to carry out the droop functions expressed
(1) by (3) and (4), it is necessary to calculate the average value over
one line-cycle of the output active and reactive instantaneous
(2) power. This can be implemented by means of low-pass filters
with a smaller bandwidth than that of the closed-loop inverter.
where is the output reactance of an inverter, is the phase Consequently, the power calculation filters and droop coeffi-
angle between the output voltage of the inverter and the voltage cients determine, to a large extent, the dynamics and the stability
of the common bus, and and are the amplitude of the output of the paralleled-inverters [19]. Damping and oscillatory phe-
voltage of the inverter and the load voltage, respectively. nomena of phase shift difference could cause instabilities and a
From the above equations, it can be derived that the large transient circulating current that can overload and damage
active power is predominately dependent on the power the units.
angle , while the reactive power mostly depends on In conclusion, the conventional droop method has several
the output-voltage amplitude. Consequently, most of the intrinsic problems related to its limited transient response,
wireless-control of paralleled-inverters uses the conventional since the system dynamics depends on the power-calculation
droop method, which introduces the following droops in the filter characteristics, the droop coefficients, and the output
amplitude and the frequency of the inverter output voltage impedance. These parameters are determined by the line-fre-
quency, the maximum allowed frequency and amplitude
(3) deviations, and the nominal output power. Thus, by using the
conventional droop method, the inverter dynamics cannot be
(4)
independently controlled.
being and the output voltage angular frequency and am-
III. PROPOSED CONTROL TECHNIQUE
plitude at no load, and and are the droop coefficients for
the frequency and amplitude, respectively. In this paper, we will try to overcome the above limitations
It is well known that if droop coefficients are increased, then and to synthesize a novel control strategy without communi-
good power sharing is achieved at the expense of degrading the cation wires that could be appropriate for a high-performance
GUERRERO et al.: WIRELESS CONTROLLER 1207

voltage proportionally to the time-derivative of the fundamental


output-current. On the other hand, in order to share harmonic
current content, without increasing output-voltage THD too
much, the resistive-impedance should be achieved. Hence, a
high pass filter can easily carry out both behaviors. Note that
the gain and the pole value of this filter must be carefully
chosen. The proper design of this output impedance can reduce,
to a large extent, the line-impedance impact over the power
sharing accuracy.

V. SMALL-SIGNAL MODELING
Fig. 5. Block diagram of the proposed controller. To analyze the stability and the transient response, a small-
signal model of the parallel-inverter system is proposed. An ob-
DG electrical ac interface system. To improve the dynamics of jective of the above controllers is to avoid the existence of a
the system, the following novel droop-based control scheme is circulating current among the inverters. Hence, this current can
proposed: be an interesting variable to investigate; however, it is a fast
and oscillating variable, which can complicate the analysis of
the system. To facilitate this analysis, from Fig. 2, the envelope
signal of the current drawn to the bus can be found
(5)

(7)
(6)
By taking the usual approximations , , and
where is the derivative coefficient of the reactive power ; , we can derive
, , and are the integral, proportional, and derivative co-
efficients of the active power . Note that if we take into account
(8)
that , the steady-state voltage and the frequency
droops coincide exactly with those obtained with the conven-
tional method, expressed by (3) and (4). where is a small variation of the phase difference. As it can
The proposed control scheme allows us to modify the tran- be seen, the envelope of is proportional to the power angle .
sient response, act on the control coefficients, and, at the same Consequently, a small-signal analysis is proposed to obtain the
time, keep the static droop characteristic. Also, it minimizes dynamics of taking into account the well-known infinite bus
the transient circulating current among the units and further im- approximation [13], [19].
proves the dynamic performance of the whole system. In fact, First, we must take into account the expression of the low-
the coefficients and fix the steady-state droop function pass filters, shown in Fig. 5, which averages the instantaneous
while , , and are selected to guarantee stability and active and reactive power values. By using (1) and (2), and mod-
good transient response. eling the low-pass filters as a first-order system, it yields to

IV. CONTROLLER IMPLEMENTATION


(9)
Fig. 5 depicts the block diagram of the proposed controller.
The average active power can be obtained by multiplying the (10)
inverter output voltage by the inverter output current , and
by filtering the product using a low-pass filter. In a similar way,
where denotes perturbed values, capital letters mean equilib-
the average reactive power is obtained, but in this case the output
rium point values, and is the cut-off angular frequency of
voltage must be delayed 90 .
the low-pass filters, which must be fixed over one decade below
In order to adjust the output voltage phase, (5) is imple-
from frequency mains.
mented, which corresponds to a PID controller applied over
Second, by perturbing (5)–(6) and using (9)–(10), we obtain
the average active power signal. The output-voltage amplitude
is regulated by using the conventional droop method with the
inclusion of the reactive power derivative term [see (6)].
Finally, the output impedance of the inverter can be emulated
by means of a high-pass filter to share linear and nonlinear (11)
loads [20]. In this case, an additional faster loop is added to
program the output impedance. On the one hand, inductive
output impedance can be implemented by dropping the output (12)
1208 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004

Finally, substituting (12) into (11), it can be found

(13)

where , , and are

Using (13), the stability of the closed-loop system can be eval-


uated, and a desired transient response can be selected following
a linear three-order dynamics. From the values of , , and
coefficients, it can be seen that the proposed controller endows
superior controllability of the dynamics as opposed to the con-
ventional approach, in which , , and .

Fig. 6. Root locus diagrams for (a) 0  m 10 , m = 5 1 10 and


m m

VI. DESIGN METHODOLOGY
(b) 0   10 , = 2 1 10 .
In order to properly select the coefficients of the load-
sharing controller, we propose a design methodology. First, TABLE I
PARAMETERS OF THE WIRELESS LOAD-SHARING CONTROL
the coefficients and can be chosen as in the conventional
droop method to ensure steady state control objectives [15] as
follows:

(14)

(15)

where and are the maximum active and reactive


powers that can be delivered by the inverter and and
are the maximum frequency and amplitude output-voltage devi-
ations allowed (see Fig. 3). Hence, these two parameters can be
fixed by the designer taking into account the tradeoff between
the power sharing accuracy and the frequency and amplitude
deviation.
Second, the coefficients , , and are chosen in order
to adjust the transient response, and ensuring system stability. In
this sense, the analysis of the eigenvalues of (13) through several
root locus plots as a function of these parameters is presented.
Fig. 6(a) and (b) show the root locus plots using the param-
eters listed in Table I, and considering a variation of the coef-
GUERRERO et al.: WIRELESS CONTROLLER 1209

Fig. 7. Family of root locus diagrams for n 1


= 0, 5 10 , and 10 . (a) 0 
m  10 and (b) 0 m  10 .
Fig. 8. n 1 m = 0, 5 1 10
Family of root locus diagrams ( = 5 10 ): (a) ,
1
10 10 , and 15 101 0
for 10 m  10 m = 010 1 10
and (b) ,
0 1
5 10 , 0, 5 101 1 1
, 10 10 , and 15 10 for 0  m  10 .
ficients and from zero to . Notice that this system
has three roots: two conjugated poles ( and ) and a real pole
stable and unstable behaviors. Note that, in this case, when
. The arrows indicate the evolution of the corresponding
and have positive values the system is stable. It can be seen
pole when the coefficient increases. As Fig. 6(a) shows, with
that there is a small range of negative values of in which the
the increasing of , the conjugated poles tend to go far away
system remains stable. Out of this range, the system becomes
from the imaginary axis splitting as two real poles, while the
unstable (see shadowed area).
single pole is attracted toward the origin, becoming the domi-
In a practical design, and coefficients should be
nant root. Thus, the system behavior can be approximated as a
chosen to obtain the desired transient response specifications,
first order system but it turns slower. Fig. 6(b) shows that when
taking into account the well-known tradeoff design between an
increasing , the complex poles become dominant, resulting
over-damping fast response or a slower first order dynamics.
in a near second order behavior. Since in both cases the poles
remain in the left half -plane, the system is stable in the range
of concern. VII. SIMULATION AND EXPERIMENTAL RESULTS
Fig. 7 illustrates the low sensibility of over the system The conventional droop method (3)–(4) and the proposed
dynamics, through three superimposed root locus plots consid- control scheme (5)–(6) were simulated with the parameters
ering the same variations as in Fig. 6. Due to the small variation listed in Table I and the scheme shown in Fig. 9 for a two-in-
in the root locus, this parameter can be previously fixed or fi- verter paralleled system in order to compare its outstanding
nally adjusted for fine tuning purposes. features. Coefficients and were chosen taking into account
Fig. 8 depicts two family of root locus considering a wider the tradeoff between the power sharing accuracy and the
variation of and coefficients, which allow us to identify voltage regulation, while , , and were selected to
1210 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004

Fig. 9. Parallel operation of two inverters.

Fig. 11. Dynamic response of the phase difference between inverters, at


m
variations of (a) and (b) m .

Fig. 11(a) depicts that the transient behavior turns slower and
less damped when increasing , due to the fact that the real
pole becomes dominant, as shown Fig. 6(a). Fig. 11(b) shows
the tendency to obtain a more oscillatory response when in-
creasing , since it attracts the conjugated poles toward the
imaginary axis, as can be seen in Fig. 6(b). Combining these two
degrees of freedom with the tight adjust of , we can obtain
Fig. 10. Transient response of circulating current and its approximated a better dynamic performance than in the conventional droop
envelope deduced from (8): (a) conventional droop method and (b) proposed
control method. method, since using the conventional one the transient response
can not be adjusted without change and values.
Two 1-kVA single-phase inverter units were built and tested
ensure stability and a good transient response as explained in in order to show the validity of the proposed approach. Each
the previous section. inverter consisted of a single-phase insulated gate bipolar tran-
Fig. 10 shows the startup circulating current and its approxi- sistor (IGBT) full-bridge with a switching frequency of 20 kHz
mated envelope deduced from (8), using the conventional droop and an output filter, with the following parameters:
method and the proposed control, respectively. These results mH, F, V, and V Hz.
confirm that the proposed controller achieves a better dynamic The controllers of these inverters were based on three loops: an
response than that of the classical droop method approach. Note inner current-loop, an outer PI controller that ensures voltage
that in spite of the initial current peak due to the initial phase- regulation [21], and the load-sharing controller, based on (5)
error between inverters, a faster transient response, better dy- and (6). The last controller was implemented by means of a
namic performance, and less circulating current are achieved TMS320LF2407A, fixed-point 40-MHz digital signal processor
with the proposed control solution. (DSP) from Texas Instruments (see Fig. 12), using the param-
Fig. 11 shows startup waveforms of the phase difference be- eters listed in Table I. The DSP-controller also includes a PLL
tween the inverters for different values of the coefficients of the block in order to synchronize the inverter with the common bus.
proposed controller, which proves that the transient response When this occurs, the static bypass switch is turned on, and the
of the system can be easily modified with these parameters. droop-based control is initiated.
GUERRERO et al.: WIRELESS CONTROLLER 1211

Fig. 12. Power stage and controller of a single unit.

(a) (a)

(b) (b)

Fig. 13. Transient response of the circulating current (X-axis: 5 A/div, Y-axis: Fig. 14. Transient response of the active power P (X-axis: 500 W/div, Y-axis:
100 ms/div): (a) conventional droop method and (b) proposed control method. 200 ms/div): (a) conventional droop method and (b) proposed control method.

The dynamic performance of the parallel system is Fig. 14 depicts the active power transient behavior for both con-
experimentally evaluated in case of connecting inverter #2 trol schemes. These results show an overall improvement in the
when the inverter #1 is supplying all the power required by dynamic response of the proposed control solution.
the load. Fig. 13 shows the circulating-current using The second experimental test consists in supplying a non-
the (a) conventional droop method and (b) the one proposed. linear load by means of the two parallel inverter systems. Fig. 15
1212 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 19, NO. 5, SEPTEMBER 2004

[2] K. Ro and S. Rahman, “Two-loop controller for maximizing perfor-


mance of a grid-connected photovoltaic-fuel cell hybrid power plant,”
IEEE Trans. Energy Conv., vol. EC-13, pp. 276–281, Sept. 1998.
[3] R. H. Lasseter and P. Piagi, “Providing premium power through dis-
tributed resources,” in Proc. IEEE 33rd Hawaii Int. Conf. System Sci-
ences (HICSS’00), 2000, pp. 1–9.
[4] S. R. Wall, “Performance of inverter interfaced distributed generation,”
in Proc. IEEE/PES-Transmission and Distribution Conf. Expo., 2001,
pp. 945–950.
[5] C. Wekesa and T. Ohnishi, “Utility interactive AC module photovoltaic
system with frequency tracking and active power filter capabilities,” in
Proc. IEEE-PCC’02 Conf., 2002, pp. 316–321.
[6] J. Liang, T. C. Green, G. Weiss, and Q.-C. Zhong, “Evaluation of repet-
itive control for power quality improvement of distributed generation,”
in Proc. IEEE-PESC’02 Conf., 2002, pp. 1803–1808.
[7] S. Barsi, M. Ceraolo, P. Pelachi, and D. Poli, “Control techniques of
(a) dispersed generators to improve the continuity of electricity supply,” in
Proc. IEEE PES’02 Winter Meeting, 2002, pp. 789–794.
[8] R. H. Lasseter, “Microgrids,” in Proc. IEEE PES’02 Winter Meeting,
2002, pp. 305–308.
[9] C.-C. Hua, K.-A. Liao, and J.-R. Lin, “Parallel operation of inverters for
distributed photovoltaic power supply system,” in Proc. IEEE PESC’02
Conf., 2002, pp. 1979–1983.
[10] J. Sachau and A. Engler, “Static and rotating grid formation for modu-
larly expandable island grids,” in Proc. EPE’99 Conf., Laussane, Frane,
1999, pp. 1–10.
[11] H. Matthias and S. Helmut, “Control of a three phase inverter feeding
an unbalanced load and operating in parallel with other power sources,”
in Proc. EPE-PEMC’02 Conf., 2002, pp. 1–10.
[12] T. Kawabata and S. Higashino, “Parallel operation of voltage source in-
verters,” IEEE Trans. Ind. Applicat., vol. IA-24, pp. 281–287, Mar./Apr.
1988.
[13] A. R. Bergen, Power Systems Analysis. Englewood Cliffs, NJ: Pren-
(b) tice-Hall, 1986.
[14] M. C. Chandorkar and D. M. Divan, “Control of parallel connected in-
Fig. 15. Steady-state waveforms supplying a nonlinear load: (a) load voltage verters in standalone AC supply system,” IEEE Trans. Ind. Applicat.,
and current (X-axis: 5 ms/div, Y-axis: 150 V/div, 10 A/div) and (b) output
vol. IA-29, pp. 136–143, Jan./Feb. 1993.
current of the two units (X-axis: 10 ms/div, Y-axis: 10 A/div). [15] A. Tuladhar, H. Jin, T. Unger, and K. Mauch, “Parallel operation of
single phase inverter modules with no control interconnections,” in Proc.
shows the load voltage and current, and the output current of the IEEE-APEC’97 Conf., 1997, pp. 94–100.
[16] S. J. Chiang, C. Y. Yen, and K. T. Chang, “A multimodule parallelable
two units. As it can be seen, the load sharing capability is very series-connected PWM voltage regulator,” IEEE Trans. Ind. Electron.,
good, even when supplying nonlinear loads. vol. 48, pp. 506–516, June 2001.
[17] A. Engler, “Control of parallel operating battery inverters,” PV Hybrid
Power Syst., 2000.
VIII. CONCLUSION [18] U. Borup, F. Blaabjerg, and P. N. Enjeti, “Sharing of nonlinear load in
parallel-connected three-phase converters,” IEEE Trans. Ind. Applicat.,
In this paper, a novel load-sharing controller for parallel in- vol. 37, pp. 1817–1823, Nov./Dec. 2001.
verters has been proposed. Based on the droop method, the con- [19] E. A. A. Coelho, P. Cabaleiro, and P. F. Donoso, “Small signal stability
troller avoids the use of control wire interconnections. In a sharp for single phase inverter connected to stiff AC system,” in Proc. IEEE-
IAS’99 Annu. Meeting, 1999, pp. 2180–2187.
contrast with the conventional droop method, the presented con- [20] J. M. Guerrero, L. García de Vicuña, J. Matas, and J. Miret, “Steady-state
troller is able to modify the dynamic response of the paralleled invariant-frequency control of parallel redundant uninterruptible power
system by correctly tuning control gain parameters. supplies,” in Proc. IEEE-IECON’02 Conf., 2002, pp. 274–277.
[21] H. Wu, D. Lin, D. Zhang, K. Yao, and J. Zhang, “A current-mode con-
Simulation and experimental results show that the dynamic trol technique with instantaneous inductor-current feedback for UPS in-
response is significantly improved, highlighting the possibili- verters,” in Proc. IEEE APEC’99 Conf., 1999, pp. 951–957.
ties of the proposed approach for inverters in DG systems, when
several units must be connected to a common ac bus with a
proper transient response. Linear and nonlinear loads can be cor-
rectly supplied by the parallel system using the proposed control Josep M. Guerrero (S’01–M’03) received the
B.S. degree in telecommunication engineering,
solution. the M.S. degree in electronic engineering, and
the Ph.D. degree from Polytechnic University of
ACKNOWLEDGMENT Catalunya, Barcelona, Spain, in 1997, 2000, and
2003, respectively.
The authors would like to thank J. Barri, R. Ciurans, D. Mon- Since 1998, he has been an Assistant Professor
tesinos, and A. Sabé, Salicrú Electronics, for their help with the in the Department of Automatic Control Systems
and Computer Engineering, Polytechnic University
experimental verification. of Catalunya, where he teaches digital signal
processing, control theory, and microprocessors. His
REFERENCES research interests include DSP-based control, uninterruptible power supplies,
and distributed power systems.
[1] R. H. Lasseter et al., “White paper on integration of distributed energy Dr. Guerrero is an Associate Editor with the IEEE TRANSACTIONS ON
resources. The CERTS microgrid concept,” in Consort. Electric Relia- INDUSTRIAL ELECTRONICS and is listed in the International Who’s Who in the
bility Technology Solutions, 2002, pp. 1–27. World and Who’s Who in Science and Engineering.
GUERRERO et al.: WIRELESS CONTROLLER 1213

Luis García de Vicuña received the Ingeniero de Miguel Castilla received the M.S. and Ph.D.
Telecomunicación and Dr.Ing. degrees from the Poly- degrees in telecommunication engineering from the
technic University of Catalunya, Barcelona, Spain, in Polytechnic University of Catalunya, Barcelona,
1980 and 1990, respectively, and the Dr.Sci. degree Spain, in 1995 and 1998, respectively.
from the Université Paul Sabatier, Toulouse, France, Since 2002, he has been an Associate Professor
in 1992. in the Department of Electronic Engineering,
From 1980 to 1982, he was an Engineer with Con- Polytechnic University of Catalunya, where he
trol Applications Company. He is currently an Asso- teaches analog circuits and power electronics. His
ciate Professor in the Department of Electronic Engi- research interests are in the areas of modeling,
neering, Polytechnic University of Catalunya, where simulation, and control of dc-to-dc power converters
he teaches power electronics. His research interests and high-power-factor rectifiers.
include power electronics modeling, simulation and control, active power fil-
tering, and high-power-factor ac/dc conversion.

José Matas received the B.S., M.S., and Ph.D. Jaume Miret (M’98) received the B.S. degree
degrees in telecommunication engineering from the in telecommunications and the M.S. degree in
Polytechnic University of Catalunya, Barcelona, electronics from the Polytechnic University of
Spain, in 1988, 1996, and 2003, respectively. Catalunya, Barcelona, Spain, in 1992 and 1999,
Since 1997, he has been an Associate Professor respectively, where he is currently pursuing the
in the Department of Electronic Engineering, Ph.D. degree.
Polytechnic University of Catalunya. His research Since 1993, he has been an Assistant Professor at
interests include power-factor-correction circuits, the Polytechnic University of Catalunya. His research
distributed power systems, and nonlinear control. interests include dc-to-ac converters, active power fil-
ters, and digital control.

You might also like