1. Introduction
3. Simulation Parameters
The simulations presented in this paper were carried out
in Matlab-Simulink. The important parameter setups
during the simulations are shown in table I.
VISMA-Method 1 VISMA-Method 2
voltage-to-current current-to-voltage
VISMA-Model
model model
Control
mechanism
Hysteresis controller PWM controller
Control variable Phase currents Phase voltages
Fig. 12. Output voltage of the VISMA-Method 1 by changing to Measurement Phase voltages am Phase currents in
island mode (filter capacators C = 5µF, left: VISMA without variable PCC output inductors
Switching 2,8kHz ~ 15kHz in 15kHz in simulation
load; right: VISMA with a load). frequency
simulation (depends (depends on the
(assumed: max.
fs=15kHz for on the setting of setting of PWM
It is obviously to see that the VISMA has built the voltage IGBT) hysteresis controller) controller)
continuously after switching off the public grid. Without a
The same as the real
load the voltages have a large distortion, because the Synchronizing VISMA currents
synchronous
switching frequency of the hysteresis controller is varying with the grid almost equal to zero
generator
and the LC-filter could not filter out all frequency parts; Parameter for Virtual excitation Ep Virtual excitation Ep
whereas the VISMA under island mode with a resistive power setting Virtual torque Mmech Virtual torque Mmech
load, the harmonics could be damped almost completely Virtual rotating mass Virtual rotating mass
Dynamic
(virtual inertial JVISMA) (virtual inertial JVISMA)
and rapidly. Another way to reduce the harmonics is to properties
Virtual damping kd Virtual damping kd
choose larger capacitors and make sure that the corner Necessary for the
frequency of the LC-filter is under the minimal switching Low-pass filter Not necessary measurement of the
frequency of the hysteresis controller. phase currents
Possible with Possible without
extending filter hardware
B. Island mode of the VISMA-Method 2 capacitors reconfiguration
Island mode
For VISMA-Method 2 a modification of the hardware Frequency and voltage Frequency and
configuration is not necessary. The VISMA operates here controller are voltage controller are
necessary for a stable necessary for a stable
as a voltage source. Under the same simulation conditions long-term island grid long-term island grid
the VISMA-Method 2 provided following results
illustrated in Fig.13.
7. Conclusions
This paper presents a new method to implemente the
VISMA on the PWM controlled inverter by using a
current-to-votage model. A comparison of this new
method with VISMA-Method 1 by using a voltage-to-
current model on the hysteresis controlled inverter has
been performed by simulation results. It has been proved
that the VISMA-Method 2 is able to behave almost the
same static and dynamic properties such as flexible
Fig. 13. Output voltage of the VISMA-Method 2 by changing to power setting, energetic reproducing the virtual rotating
island mode (filter capacators C = 5µF, left: VISMA without mass and virtual damping in a parallel operation with the
load; right: VISMA with a load). public grid as the VISMA-Method 1.
Firstly, the VISMA-Method 2 could build the three phase Both VISMA-Methods can be operated under an island
voltages immediately after switching off the public grid. mode. The VISMA-Method 2 can achieve a better
Secondly, the voltages of the VISMA have almost no voltage quality compared to the VISMA-Method 1,
harmonics compared to the VISMA-Method 1 because of which needs larger capacitors in order to having the same
the constant switching frequency of the PWM controller voltage quality. For building a stable island grid the
and the proper output filter. In the case of VISMA with a frequency and voltage controller should be applied in
load into island mode, the voltages dropped in short period both VISMA-Methods.
and then rose quickly to a stabile value. Because of the
virtual inertial of the VISMA the voltages cannot collapse Considering the widely applied PWM controlled invertes
suddenly. In order to keep a stable long-term voltage under in the current market, the VISMA-Method 2 is tended to
island mode, the voltage and frequency controller must be be more easily utilized.
applied.