Professional Documents
Culture Documents
org
Published in IET Generation, Transmission & Distribution
Received on 9th October 2013
Accepted on 23rd August 2014
doi: 10.1049/iet-gtd.2014.0313
ISSN 1751-8687
Abstract: For high-voltage direct current (HVDC) transmission systems, the transient fault current characteristics are that: if the
fault point is over the line, the fault component current measured at both converter stations would be increased and they have the
same changing direction. If the fault point is beyond the line, the fault component current measured at one converter station is
increasing and the fault component current measured at the other converter station is decreasing, so they have the opposite
changing direction. According to this characteristic, a novel pilot protection principle for HVDC transmission line based on
fault component current is proposed here. The principle proposed has no limitation to the sampling frequency. A fault,
whether it occurs in the line or beyond the line, can be effectively identified only using the fault component current at both
converter stations. At the same time, the setting criterion of the fault component current is also given. The simulation results
show that the new method can identify the faults reliably and rapidly. The study is promising to have significant theoretical
and practical value.
468 IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474
& The Institution of Engineering and Technology 2015 doi: 10.1049/iet-gtd.2014.0313
17518695, 2015, 5, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2014.0313 by Readcube (Labtiva Inc.), Wiley Online Library on [28/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
2 Analysis of fault current characteristics for one is a normal network and the other is fault component
HVDC transmission lines network. Therefore, the voltage that decreases is equal to
superposing a negative voltage source at the fault point,
At present, the HVDC projects in operation are mostly which is given in Fig. 3.
two-end HVDC transmission systems, which consist of In Fig. 3, Uf is the superposition voltage source, If is
rectifier station M, inverter station N and DC transmission current of the failure branch, RSM and RSN are equivalent
lines. The schematic diagram of a bipolar HVDC resistances of the systems at both ends and Rf is
transmission line is shown in Fig. 1. ground-resistance at the fault branch.
As shown in Fig. 1, uMp and uMn are voltages measured According to the designated direction in Fig. 3, it is easily
(positive and negative poles) at terminal M; iMp and iMn are inferred that the current components of ΔIM and ΔIN at both
currents measured (positive and negative poles) at terminal sides are positive when the fault voltage source is
M; uNp and uNn are voltages measured (positive and negative superposed, and there is
poles) at terminal N; iNp and iNn are currents measured
(positive and negative poles) at terminal N. The points from ⎧
f1 to f5 are positions at which fault occurs. E1, E2 are pole ⎨ If = DIM + DIN
voltages at both converter stations when fault occurs. DI = k I (2)
Different from AC transmission system, a short-circuit ⎩ DIM = k MI f
N N f
current is controlled when a fault occurs in HVDC
transmission line. In this paper, a fault, whether it occurs
over the line or beyond the line, can be effectively
where ΔIM and ΔIN are the fault component currents at the
identified using only the fault component current at both
rectifier station and the inverter station, respectively. kM, kN
converter stations in the transient process after the fault
are positive coefficients, and there exists
occurs. The fault identification is during the process of the
fault occurring. That is to say, the control angles of α and β
remain unchanged, or the control angles of α and β have
changed but they have not arrived at the steady state. kM + kN = 1 (3)
Subsequently, the characteristics of fault current at both
ends are analysed.
It is well known that the voltages in HVDC transmission
line would decline when fault occurs. Thus, when fault
occurs, according to the superposition theory, the circuit
networks can be divided into two parts. One is a normal
network and the other is fault component network.
To facilitate analysing the current features, a normal
positive pole network of HVDC system is given in Fig. 2.
UM, UN are pole voltages at both converter stations when
the HVDC system has no fault. Generally, UM is larger than
Fig. 2 Positive HVDC system with no fault
UN. IM, IN are pole currents at both converter stations. In a
general way, IM equals the load current Ih. At both ends,
supposing the current positive direction flows into the line,
then there is
IM = Ih
(1)
IN = −Ih
IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474 469
doi: 10.1049/iet-gtd.2014.0313 & The Institution of Engineering and Technology 2015
17518695, 2015, 5, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2014.0313 by Readcube (Labtiva Inc.), Wiley Online Library on [28/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
the line and at the inverter station), the fault component
current of ΔIM at the rectifier station is positive and the fault
component current of ΔIN at the inverter station is negative.
In other words, the changing direction of ΔIM and ΔIN at
both sides are reverse.
Fig. 4 Positive fault component network with fault at the point f2 The influence on DC system exerted by faults in AC system is
by changing the voltage at the converter side. When a fault
occurs at the point f4 in AC system of the rectifier side, it
Moreover, ΔIM and ΔIN can be calculated according to (4). will lead to the voltage of bus line in AC system
decreasing. Moreover, the decreasing voltage of bus line in
AC system will further result in the decline of the voltage
DIM = IM − Ih
(4) of bus line in DC system. Thus, for DC system, the fault
DIN = IN + Ih
characteristic of the decreasing voltage is the same as the
fault feature when fault occurs at f2 point at the rectifier side.
From (4), we know that ΔIM and ΔIN are increasing when fault
In the same way, when a fault occurs at the point f5 in AC
occurs in the line. In other words, the changing trends of ΔIM
system of the inverter side, it will lead to the voltage of bus
and ΔIN are positive.
line in AC system of the inverter side decreasing. Similarly,
the decreasing voltage of the inverter side will further
2.2 Current fault characteristic with fault at the decrease the voltage of bus line in DC system at the
point f2 inverter side. For DC system, the fault characteristic of the
decreasing voltage at the inverter side is similar to the fault
Similarly, when fault occurs at the point f2, the fault feature when a fault occurs at the point f3 at the inverter side.
component network is given in Fig. 4, where IfR is the Therefore, when a fault occurs at the point f4 or f5, the
shunt current of the fault branch in the right side. analysis method is the same as the analysis when a fault
From Fig. 4, according to the circuit theory, we can obtain occurs at the point f2 or f3, respectively. That is to say, a
similar conclusion can be drawn that the current changing
DIM = −I fR trends are reverse.
(5)
DIN = I fR
Namely, when fault occurs at the point f2 (fault occurs beyond 2.5 Conclusion of fault current characteristics
the line and at the rectifier station), the fault component analysis
current of ΔIM at the rectifier station is negative and the In summary, from the above analysis, it can be concluded that
fault component current of ΔIN at the inverter station is the current changing trends are reverse when a fault occurs
positive. In other words, the changing direction of ΔIM and beyond the line, and the current changing trends are the
ΔIN at both sides are reverse. same when a fault occurs over the line. Thus, these
differences in current changing characteristics at both ends
2.3 Fault current characteristics with fault at the can be used to identify the faults of HVDC transmission line.
point f3 We need to explain that the equivalent of the system at both
sides is a complex question as the parameters of line are
In the same way, when fault occurs at the point f3, the fault changing with time after a fault occurs, and are dependent
component network is given in Fig. 5. IfL is the shunt on the characteristic of the controller at both ends. That is
current of the fault branch in the left side. to say, RSM and RSN in Figs. 3–5 will be a time-dependant
From Fig. 5, we know that impedance. Although it is inconsistent with the practical
condition, the correction of conclusion to analyse the fault
DIM = I fL characteristics at both ends is not affected.
(6)
DIN = −I fL
3 Identification principle of the fault direction
Namely, when fault occurs at the point f3 (fault occurs beyond
From the analysis of Section 2, a fault occurring over the line
or beyond the line can be identified by using the differences of
current changing trend at both ends in HVDC transmission
lines. To use the characteristics, the current changing value
can be extracted by using the integration of a period of data
in time domain. Then, by comparing the integration value
with the setting threshold value, the direction of the fault
current changing can be identified.
To identify the direction of the fault component current,
two questions should be considered first. One is how to
choose the length of data-window and the other is how to
set the threshold value. On the whole, the longer the length
Fig. 5 Positive fault component network with fault at the point f3 of the data-window selected, the stronger the ability of
470 IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474
& The Institution of Engineering and Technology 2015 doi: 10.1049/iet-gtd.2014.0313
17518695, 2015, 5, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2014.0313 by Readcube (Labtiva Inc.), Wiley Online Library on [28/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
anti-disturbance; the higher the setting threshold value, the
better the selectivity. For the question of choosing the
data-window, the adjustment process of the controller is
generally about 30 ms. Thereby, the data-window should
not exceed the length of 30 ms. In addition, considering the
disturbance of lightning, the length of data-window should
not be less than 3 ms. To sum up the above two factors, a
10 ms data-window is chosen to carry out the integration.
For the question of setting the threshold value, because the
fault current in steady state is 0.1 times of the load current,
the integration value in 10 ms can be taken as the threshold
value according to 0.1 times of the load current. Thus, the
criterion can be constructed as follows
N
Di . kr∗N∗Iset (7)
k=1
IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474 471
doi: 10.1049/iet-gtd.2014.0313 & The Institution of Engineering and Technology 2015
17518695, 2015, 5, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2014.0313 by Readcube (Labtiva Inc.), Wiley Online Library on [28/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
fault occurs beyond the line at the rectifier side, the current
pilot component at the inverter side can operate correctly
because of the positive current changing trend. On the other
hand, the current pilot component at the rectifier side
cannot start because of the negative current changing trend.
Considering the two factors, it is ensured that the pilot
protection at the rectifier side will not operate when metallic
ground fault occurs beyond the line at the rectifier side.
472 IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474
& The Institution of Engineering and Technology 2015 doi: 10.1049/iet-gtd.2014.0313
17518695, 2015, 5, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2014.0313 by Readcube (Labtiva Inc.), Wiley Online Library on [28/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
when metallic ground fault occurs beyond the line at the
inverter side.
From the simulation results, within 10 ms, the relay
protection can operate reliably when fault occurs over the
line, and the relay protection will not operate when fault
occurs beyond the line.
Fig. 11 Negative pole fault component currents and relay Fig. 13 Negative pole fault component currents and relay
protection operation when metallic ground fault occurs at 500 km protection when metallic ground fault occurs at a distance of
from the M-side in positive pole 170.89 km from Zhao Qing in positive pole
IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474 473
doi: 10.1049/iet-gtd.2014.0313 & The Institution of Engineering and Technology 2015
17518695, 2015, 5, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/iet-gtd.2014.0313 by Readcube (Labtiva Inc.), Wiley Online Library on [28/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License
www.ietdl.org
Gao Po–Zhao Qing HVDC system is 3000 MW. The voltage 5 Yang, B.-M., Kim, C.-K., Jung, G.-J., Moon, Y.-H.: ‘Verification of
and current signals are input to the protection device with a hybrid real time HVDC simulator in Cheju-Haenam HVDC systems’,
J. Electr. Eng. Technol., 2006, 1, (1), pp. 23–27
sampling frequency of 6.4 kHz. A single phase-to-earth 6 Lee, B., Kang, S.-G., Seo, S., Ajjarapu, V., Song, H.: ‘Generation
fault occurred at a point 170.89 km from substation Zhao re-dispatch algorithm against voltage collapse in Jeju island system
Qing on August 14, 2005 (2:40:18 Beijing time). with a frequency control by high-voltage direct current’, IET Gener.
From Figs. 12 and 13, we can see that the directional Transm. Distrib., 2010, 4, (5), pp. 1751–8695
elements in both sides of the positive pole can correctly 7 Zhou, Y., Zhuojiang, D., Fenwang, Y.: ‘The development of HVDC
transmission system’. Proc. Third Int. Conf. Digital Manufacturing
distinguish the right direction, determining an inside fault , and Automation, GuiLin, China, August 2012, pp. 907–910
while the directional elements in both sides of the negative 8 Hongzhi, L., Xia, W.N., Junru, G.: ‘The research on the affection of the
pole cannot distinguish the right direction at the same time, Qinghai-Tibet HVDC transmission system upon operating characteristic
determining an outside fault or no fault. Thus, it can be of the line protection in Qing-Hai AC electrical power system’. Proc. Int.
concluded that the proposed pilot protection principle can Conf. Electricity Distribution, Shanghai, China, September 2012,
pp. 1–8
act correctly and has a good applicability in practical 9 ‘ABB solves 100-year-old electrical puzzle – new technology to enable
engineering project. future DC grid’, http://www.abb.com/cawp/seitp202/
65df338284e41b3dc1257aae0045b7de.aspx
10 Naidoo, D., Ijumba, N.M.: ‘A protection system for long HVDC
8 Conclusions transmission lines’. Published in Power Engineering Society Inaugural
Conference and Exposition, Durbani, Africa, July 2005, pp. 150–155
By analysing the fault features of HVDC transmission systems, 11 Takeda, H., Ayakawa, H., Tsumenaga, M., Sanpei, M.: ‘New protection
a novel pilot protection principle for HVDC transmission line method for HVDC lines including cables’, IEEE Trans. Power Deliv.,
based on fault component current is proposed in this paper. 1995, 10, (4), pp. 2035–2039
A fault, whether it occurs in the line or beyond the line, can 12 Suonan, J., Gao, S., Song, G., et al.: ‘A novel fault-location method for
HVDC transmission lines’, IEEE Trans. Power Deliv., 2010, 25, (2),
be effectively identified using only the fault component pp. 1203–1209
current at both converter stations. The method is simple and 13 Shang, L., Herold, G., Jaeger, J., Krebs, R., Kumar, A.: ‘High-speed
does not need the seriously synchronous data. Moreover, it fault identification and protection for HVDC line using wavelet
has no limitation to the sampling frequency and it needs the technique’. Proc. IEEE Porto Power Tech Conf., Porto, Portugal,
September 2001, pp. 1–5
lower communication speed.
14 Rajesh, K., Yadaiah, N.: ‘Fault identification using wavelet transform’.
The simulation results in different conditions show that the Proc. IEEE/Power Eng. Soc. Transmission Distribution Conf. Exhibit.,
principle can operate rapidly and identify the fault with high Asia Pacific Dalian, China, 2005, pp. 1–6
sensitivity and reliability. The study is promising and shows 15 Liu, X., Osman, A.H., Malik, O.P.: ‘Hybrid traveling wave boundary
significant theoretical and practical value. protection for HVDC line’. Presented at the Int. Conf. Power System,
Bangalore, India, December 2007
16 Bo, Z.Q.: ‘A new non-communication protection technique for
9 Acknowledgment transmission lines’, IEEE Trans. Power Deliv., 1998, 13, (4),
pp. 1073–1078
This work was supported by the National Natural Science 17 Wang, G., Wu, M., Li, H., Hong, C.: ‘Transient based protection for
Foundation of China (No. 51177128 and 51477131). HVDC lines using wavelet-multi resolution signal decomposition’.
Proc. IEEE/Power Eng. Soc. Transmission Distribution Conf. Exhibit.,
Asia Pacific, Dalian, China, 2005, pp. 1–4
10 References 18 Long, C.S., Chun, S.H., Zhi, W.Y., Fang, Z.: ‘Distance protection
scheme with travelling wave for UHVDC transmission line based on
1 Ying, Z., Nengling, T., Bin, X.: ‘Fault analysis and traveling-wave wavelet transform’. Proc. Third Int. Conf. Electric Utility Deregulation
protection scheme for bipolar HVDC lines’, IEEE Trans. Power and Restructuring and Power Technologies, Nanjing, China, 2008,
Deliv., 2012, 27, (3), pp. 1583–1591 pp. 2162–2164
2 Andersen, B.R., Lie, X.: ‘Hybrid HVDC system for power trans-mission 19 Suonan, J., Zhang, J., Jiao, Z., Yang, L., Song, G.: ‘Distance protection
to island networks’, IEEE Trans. Power Deliv., 2004, 19, (4), for HVDC transmission lines considering frequency-dependent
pp. 1884–1890 parameters’, IEEE Trans. Power Deliv., 2013, 28, (2), pp. 723–732
3 Liu, X.l., Osman, A.H., Malik, O.P.: ‘Hybrid traveling wave/boundary 20 Zheng, X., Tai, N., Thorp, J.S., Yang, G.: ‘A transient harmonic current
protection for monopolar HVDC line’, IEEE Trans. Power Deliv., protection scheme for HVDC transmission line’, IEEE Trans. Power
2009, 24, (2), pp. 569–578 Deliv., 2013, 27, (4), pp. 723–732
4 O’Reilly, J., Wood, A.R., Osauskas, C.M.: ‘Frequency domain based 21 Gao, S., Suonan, J., Song, G., et al.: ‘A new current differential
control design for an HVDC converter connected to a weak AC protection principle for HVDC transmission lines’, Autom. Electr.
network’, IEEE Trans. Power Deliv., 2003, 18, (3), pp. 1028–1033 Power Syst., 2010, 34, (17), pp. 45–49 (in Chinese)
474 IET Gener. Transm. Distrib., 2015, Vol. 9, Iss. 5, pp. 468–474
& The Institution of Engineering and Technology 2015 doi: 10.1049/iet-gtd.2014.0313