Model CSTPA-ASD054-1S

Power supply 1 phase, 220-240V, 50/60Hz


kW 16.0
Capacity
Cooling1 kBtu/h 54.5
Power input W 170
kW 18.0
Capacity
Heating2 kBtu/h 61.3
Power input W 170
Type DC motor
Fan motor
Number 1
Number of rows 3
Tube pitch × row pitch mm 21×13.37
Fin spacing mm 1.5
Indoor coil Fin type Hydrophilic aluminum
Tube OD and type mm Ф7 Inner-groove
Dimensions (L×H×W) mm 2200×252×40.11
Number of circuits 12
Air flow rate3 m3/h 2100/1950/1800/1750/1600/1450/1350
Sound pressure level4 dB(A) 46/44/42/41/39/38/37
Net dimensions5 (W×H×D) mm 950×300×950
Main body Packed dimensions (W×H×D) mm 1050×335×1050
Net/Gross weight kg 35.3/41.2
Net dimensions (W×H×D) mm 1050×55×1050
Panel Packed dimensions (W×H×D) mm 1115×100×1115
Net/Gross weight kg 7.4/9.7
Refrigerant type R410A
Design pressure (H/L) MPa 4.4/2.6

Pipe Liquid/Gas pipe mm Ф9.53/Ф15.9


connections Drain pipe mm OD Φ32
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with
zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with
zero level difference.
3. Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is
measured 1.4m below the unit in a semi-anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.

1
Dimensions (mm)
Model names
A B

CSTPA-ASD054-1S 300 200