Professional Documents
Culture Documents
Abstract - One aspect of assessing the harmonics point of common coupling (PCC) of transmission and
tolerated by a power system is the estimation of the distribution grids. Frequency converters are present in
aggregation or sum of harmonics arising from the various
the major of wind turbines of large wind farms and the
sources.
operation planning of the wind farms should give full
The estimation of harmonics is not exact or uniform,
since there will be unpredictable variations in either the
considerations on the harmonic currents present in the
non-linear sources and/or parameters of the system which PCC, especially in application of smart grid.
affect the summation. The combination of a number of The basis for harmonic combination is the
harmonic sources will generally lead to less than the superposition principle. To apply the superposition
arithmetic sum of the maximum values due to uncertainty principle properly, a phasorial composition should be
of magnitude and phase angle. Hence the resulting
used. However, because of the uncertainty of the
summation is difficult to estimate accurately.
amplitude and phases, mainly caused by load variation,
In this paper the harmonic summation caused by
large wind farms with harmonic sources is investigated.
alternative ways considering the impedances between
The work verifies, by computational simulations, the sources, are a simple and reasonable option. Hence, if
harmonic aggregation in the point of common coupling the harmonic currents are known for a certain condition,
(peC) of a typical wind farm under study by the Brazilian then the resultant harmonic voltages can be estimated by
Systems Operator. Results show that the harmonic alternative methods.
summation estimates for different conditions. The results
Reservations about the use of simplified methods to
are also compared with the lEe 61400-21 recommended
aggregation factors. The results indicate that aggregation
combine harmonics have been expressed. Several
of harmonics at the point of common coupling cannot be practical difficulties have been pointed out but the main
easily generalized. The topology of the wind farm, the type concern is the lack of practical measurements to back up
of electronic converter, the wind variations, the frequency the assumptions in contrast to highly sophisticated
range and the upstream supply system impedance play a techniques used in simulations.
very role in the determination of the aggregation
A number of methods and experiments have been
coefficients.
developed in the past to assess the harmonic summation.
However, no conclusive approach has been offered so
Key Words-Harmonic Aggregation, Harmonic
Summation, lEe 61400-21 Standard.
far. For example, Rowe's work at [1] was concerned
with the summation of random phasors. It was assumed
I. INTRODUCTION that each distorted load at a bus generated independent
harmonic currents with particular random properties.
REcently, an increase in the field of power electronics
There must be a sufficient number of vectors for the
has been occurring. This increase leads to more non
method to be applied. The advantage of Rowe's analysis
linear loads in power systems. Among these loads,
is that little information is needed.
electronic converters are the main responsible source of
R. de Vre [2] showed that harmonic currents produced
harmonic currents which causes harmonic voltages at the
by one TV receiver and one light dimmer never reach
Fabio Medeiros and Dalton C. Brazil are with the Brazilian
the arithmetic summation for the 3rd harmonic. For the
National Systems Operator (ONS), Rio de Janeiro, Brazil, 5th and higher harmonics the arithmetic summation may
docb@ons.org.br and finedeiros@ons.org.br. be reached but the probability of such occurrence would
Paulo F. Ribeiro is with Technische Universiteit Eindhoven, remain small.
Rolanda, pfribeiro@ieee.org.
Lagostena et al [3] use the arithmetic sum for the
Cristiano A. G. Marques and Carlos A. Duque are with Federal
University of Juiz de Fora, Minas Gerais, Brazil,
combination of lower order harmonics and the r.s.s. for
cristiano.marques@engenharia.ufjf.br and carlos.duque@ufjf.edu.br. higher orders. Lemoine [4] suggests a diversity factor
978-1-4673-1943-0/12/$31.00 ©2012 IEEE
364
2
associated with a probability not exceeding the simulated model. The harmonic currents are calculated
arithmetic sum. using the discrete Fourier transform.
The analysis of Sherman [5] was based on the
instantaneous value of a sum of sine waves. Corbyn [6]
used Sherman's result to make the point that for one III. RESULTS
particular harmonic the random variation of phase angles
of several loads would make the arithmetic sum a very Fig. 1 presents a typical power system wind farm
rare occurrence. configuration under study by the Brazilian Systems
As previously stated, reservations about alternative Operator. In this system, the symbol E represents a wind
methods for combining harmonics have been expressed. generator that is supplied by a 34,5/0,4 kV transformer.
The problem is that, technically speaking, only the The nominal currents of the wind generator is given in
vectorial composition is meaningful and that only table 1.
instantaneous spectra (waveshapes) should be used to
qualify the harmonic sources. Recently, some work In this paper we consider three basic cases: i) the phase
using probabilistic harmonic analysis also has been of the harmonic currents rp is considered constant and
developed by Ribeiro, Baghouz and authors [7-10]. In
the amplitudes vary randomly around its nominal values
these contributions, is considered that the harmonic
(case 1), ii) the phase rp vary as a random variable and
components are time-varying, and a statistical treatment
must be adopted. the amplitude is fixed (case 2), and iii) both amplitude
and phase vary as a random variable (case 3).
II. IEC RECOMMENDED SUMMATION COEFFICIENTS
In accordance with the IEC 61400-21 standard [11],
A. Case 1
the harmonic current magnitude, lhs , due the
contribution of several harmonic sources at the PCC, For the case 1 the amplitudes of each wind generator
with order h, is given by was varied +1- 20% around the nominal values. The
summation currents at the bus connected at the 138 kV
source is shown in Fig. 2. As expected the currents
(1) combine with an aggregation factor close to an
arithmetic summation.
365
3
Current (A)
Harmonic
16 4,62
17 7,80 Fig. 4 - Currents at the bus connected at PCC when the
18 3,18 phase angles of the harmonics vary between -90 degree
19 7,80
and 90 degree.
20 2,89
21 4,62
23 6,64
366
4
80
60
40
20
o
·0.5
Current (A)
Harmonic
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1920 21 23
Harmonics
B. Case 3
367
5
368
6
around 20% for the nominal 25A) and the phases As the rise of electronic loads increase, future
varying around +/-90 degrees. It becomes clear also customers could be requested to connect the electronic
from these example, that due to the wind farm topology, load via a transformer with a particular phase shift. This
supply system condition, and with high variability of would be particularly important at lower frequencies, as
magnitude and phases the aggregation factor does not the amplitudes are very high. Indeed, from the examples
seem to vary much and is higher than one, implying simulated, the current phase shift is seen to be very
some cancelation, but not as high as predicted by IEC effective at lower frequencies. This should be
standards. investigated in the light of site experiments. By the
results presented, we verify that the estimates of
harmonic summation using the IEC 61400-21
methodology may present significant errors in a real
power system. Thus, in this paper, we propose to adjust
the fJ values of this methodology in order to decrease
the errors in the estimates in the real power system
which is in study by the Brazilian Operator of the
<J)
Q)
u
c
National Electricity System. The simulated results
�
::J
reveal that the errors can be reduced with the
g adjustments, and provide a more reliable result if used in
(;
z a real power system.
V. REFERENCES
performed and these alternative values calculated and John Wiley & Sons, Ltd, 2009.
[11] IEC 61400-21 Wind turbines - Part 21: Measurement and assessment of
compared against the cumulative curves. power quality characteristics of grid connected wind turbines, Aug. 2008.
The examples simulated have shown that the [12] Fabio Medeiros, Dalton C. Brasil, Paulo F. Ribeiro, Cristiano A. G.
Marques and Carlos A. Duque, "A New Approach for Harmonic Summation
aggregation varies with frequency order, the system Using the Methodology of lEC 61400-21". 14th International Conference on
configuration, the current phase angles and the relative Harmonics and Quality of Power, TCHQP 2010, Bergamo, Italy, September
369