ELECTRICAL AUDIT REPORT


SUBJECT: Testing of Transformer, H.T. , L.T. Panel and Lighting Load; Testing and Assessment of all
Electrical equipment's, wiring, earthing at ground floor and Lightning Arrester Installation at
above
address.

Dear Sir,

As advised we have tested and checked the electrical installation on 04/05/2022. The report is as
under:

 FLOOR-WISE CONNECTED LOAD -


- GROUND FLOOR :
Red Phase : 10 Amps
Yellow Phase : 15 Amps
Blue Phase : 38 Amps
(Total Load not properly connected phase-wise)
Resistivity : < 0.7 Ω
- FIRST FLOOR :
Red Phase : 22 Amps
Yellow Phase : 18 Amps
Blue Phase : 48 Amps
(Total Load not properly connected phase-wise)
Resistivity : < 0.85 Ω
- SECOND FLOOR :
Red Phase : 15 Amps
Yellow Phase : 11 Amps
Blue Phase : 7.5 Amps
(Total Load not properly connected phase-wise because of some obstruction)
Resistivity : < 0.7 Ω

 ELECTRICAL INSTALLATION TESTING REPORT -


At Main between : Phase I & Neutral=100Megh
Phase II & Neutral=100Megh
Phase III & Neutral=100Megh
Conted........
RABI ENTERPRISE
ALL KIND FIRE & SAFETY INSTALLATION & ELECTRICAL WORKS
GOVT. LICENCE HOLDER
PALTA, P.O. - BENGAL ENAMEL, NORTH 24 PGS.
CONTACT : 9007328684
E-mail : rabisankarduttapalta@gmail.com
GST : 19BMNPD6903M1ZL

Ref. Date .......................20


EARTHING FITNESS CERTIFICATE FOR WHOLE BUILDING

SUB: TESTING & CHECKING YOUR GROUND EARHTING & LIGHTNING ARRESTER

Dear Sir,

As your order on us we have tested and checked the Ground Earthing & Lightning Arrester on
09/11/2021.

The Reports are as under:

Testing result for Lightning Arrester :

Between Lighting Arrester I & Ground Earth II 0.2 Ohms


Between Lighting Arrester II & Ground Earth I 0.2 Ohms

Specification of Lightning earthing :

Electrode: 40mm dia X 3.2 Mtrs long perforated galvanized pipe electrode 2nos.
Connection: 40mm X 6mm G.I. strip between electrode & earth bar 2nos.

Testing result for ground earth :

1. Earth testing result -


Between E1 & E2 =0.5 Ohms
Ground Earthing Between E1 & Neutral =0.1 Volts
Ground Earthing Between E2 & Neutral =0.1 Volts

2. Specification of ground earthing -


Electrode: 40mm dia 3.2 mtrs long perforated galvanized pipe electrode 2nos.
Connection: 40mm X 6mm G.I. Strip between electrode & earth bar 2nos.

REMARKS :

The all electrical wiring are in good order and safe condition. There are no leakages & electrical
equipments are
well connected with the Earthing & it is safe for usage.