Calculation
A - Considering total run demand from DG (Refer 1.3 above)
A1 Total min. prime rating of DG set required = TRD / RLF = 2667 KW
A2 Prime Unlimited Time Rating of Cummins Model KTA50G3 = 1031 KW / 1289 KVA
(Ref.: Cummins Engine Type & Rating Chart - Annexure-II)
A3 No. of DG set required = A1 / A2 = 2.587
SAY 3 nos DG working
D CONCLUSION
Considering above calculations, 3 nos of Cummins Model KTA50-G3 DG set is
selected as working