DATA SHEET

IMPULSE VALVE OPERATOR SUPERVISOR (IVOS)

DESCRIPTION

The Impulse Valve Operator Supervisor (IVOS) is used to monitor the presence of
the Impulse Valve Operator (IVO). When installed between the Impulse Valve on
the container and the IVO, this supervises the position of the actuation device;
when the IVO is removed from the container this will cause a “trouble” at the
system control panel.
This can also be used to monitor the position of the Impulse Valve Pneumatic
Operator (IVPO).

SPECIFCATIONS – IMPULSE VAVLE OPERATOR SUPERVISOR (IVOS)


Item Description
Part Number 02-14263
Switch Normally Closed (Black) / Normally Open Contacts (White) /
Common (Red)
Conduit 0.25”ID SST Flexible Conduit 34.75” lg. with 1/2” Knockout
Connector
Wire Leads 22 AWG, 44” lg.
Temperature Range 32°F to 130°F (0°C to 54.4°C)
Listings & Approvals UL / ULC Listed & FM Approved
Impulse Valve
Operator
Supervisor
Impulse Valve
INSTALLATION (IVOS)
Actuator Port
After the electrical / control system has been checked out and no trouble / ground faults
are present; proceed with the Actuation System installation.
NOTE: This should be the last items completed before the system is placed into
operation.

IMPORTANT NOTES: Check to ensure IVO is armed (Firing Pin retracted) and Safety Pin
is place before installing to the Impulse Valve on the container.
Install the wire leads from the IVOS to the control unit. (Refer to typical wiring diagrams
for details)
Install IVO; remove Retaining Clip and Plastic Plug from Impulse Valve Actuation Port. Impulse Valve
Operator (IVO)
Insert IVO into Impulse Valve Actuation Port and insert IVOS Retaining Clip.

The container is “NOW ARMED”.

Form No. C.1.79.01-1


704 SW 10th Street, P.O. Box 610, Blue Springs, Missouri 64013-0610 U.S.A.
Phone: (816) 229-3405 ● www.fike.com
TYPICAL WIRING DETAIL FOR SHP PRO TO IVOS
(See SHP Pro Control Unit manual for specific wiring requirements)

NOTE:
IVOS CONTACTS SHOWN
TRANSFER UNDER
PRESSURE

TYPICAL WIRING DETAIL FOR MONITOR MODULE TO IVOS


(See Cheetah Xi Control Unit manual for specific wiring requirements)

NOTE:
IVOS CONTACTS SHOWN
TRANSFER UNDER
PRESSURE

Copyright © Fike Corporation All Rights Reserved. 2 of 2


Form No. C.1.79.01-1, March, 2016. Specifications are subject changes without notice.