PROJECT
ALEYNA AY
201721032
NAVAL ARCHITECTURE AND MARINE ENGINEERING
CONTENT
1. Abstract
2. Flat Plan
3. Wall Resistance Values
4. Heat Loss Calculation Tables
5. Saloon
6. Kitchen
7. Room 1
8. Room 2
9. Room 3
10.Bathroom
11.Pipe Diameter Calculation Table
12.Column Design
13.Radiator Selection
14.Conclusion
15.References
1. Abstract
In this project, the heat loss calculation of a 3+1 flat in Balıkesir has been
calculated. Pipe diameter calculation was made according to this heat loss
calculation.
2. Flat Plan
City: Balıkesir
Floor: 3
Design Temperature:
ROOM 1
KITCHEN
ROOM 2
BATHROOM
SALOON
ROOM 3
3. Wall Resistance Values
OUTER WALLS
INTERIOR WALLS
5. SALOON
Figure 5.2
Figure 5.3
Figure 5.4
Figure 5.5
Figure 5.6
Figure 5.7
Figure 5.8
6. KITCHEN
A0 A A k ΔT Q0 ZD ZW ZH Z QH=QI+QS
cm m m m2 ad m2 m2 Kcal/(m2h◦C) ◦C Kcal/h % % % 1+% W Kcal/h
KITCHEN / 18 °C
ÇCP3 W 1,2 1 1,2 1 1,2 2,2 21 55,44
DD3 W 28 3,2 3 9,6 1 1,2 8,4 0,55 21 97,02
ÇCP4 N 1,8 2,2 3,96 1 3,96 2,2 21 182,952
DD4 N 28 2,9 3 8,7 1 3,96 4,74 0,55 21 54,747
İD2 E 21 3,2 3 9,6 1 9,6 1,451722 4 55,74612
Figure 6.2
Figure 6.3
7. ROOM-1
A0 A A k ΔT Q0 ZD ZW ZH Z QH=QI+QS
cm m m m2 ad m2 m2 Kcal/(m2h◦C) ◦C Kcal/h % % % 1+% W Kcal/h
ROOM 1 / 20°C
ÇCP5 E 1,8 1,2 2,16 1 2,16 2,2 23 109,296
DD5 E 28 2,4 3 7,2 1 2,16 5,04 0,55 23 63,756
DD6 N 28 3,65 3 10,95 1 10,95 0,55 23 138,5175
İK1 S 0,8 2,1 1,68 1 3,528 2,5 2 17,64
İD3 S 21 2,85 3 8,55 1 1,68 6,87 1,45 2 19,923
Figure 7.2
Figure 7.3
8. ROOM-2
A0 A A k ΔT Q0 ZD ZW ZH Z QH=QI+QS
cm m m m2 ad m2 m2 Kcal/(m2h◦C) ◦C Kcal/h % % % 1+% W Kcal/h
ROOM 2 / 20°C
ÇCP6 E 1,8 1,2 2,16 1 2,16 2,2 23 109,296
DD7 E 28 2,85 3 8,55 1 2,16 6,39 1,55 23 227,8035
İK2 W 0,8 2,1 1,68 1 1,68 2,5 2 8,4
İD4 W 21 2,85 3 8,55 1 1,68 6,87 1,45 2 19,923
İD5 S 21 2,5 3 7,5 1 7,5 1,45 6 65,25
Figure 8.2
Figure 8.3
9. ROOM-3
A0 A A k ΔT Q0 ZD ZW ZH Z QH=QI+QS
cm m m m2 ad m2 m2 Kcal/(m2h◦C) ◦C Kcal/h % % % 1+% W Kcal/h
ROOM3 / 20°C
ÇCP7 S 1,8 1,2 2,16 1 2,16 2,2 23 109,296
DD6 S 28 3,65 3 10,95 1 2,16 8,79 0,55 23 111,1935
DD7 E 28 2,5 3 7,5 1 7,5 0,55 23 94,875
DD8 W 28 1,8 3 5,4 1 5,4 0,55 23 68,31
İK3 N 0,8 2,1 1,68 1 1,68 2,5 2 8,4
Figure 9.2
Figure 9.3
10. BATHROOM
A0 A A k ΔT Q0 ZD ZW ZH Z QH=QI+QS
cm m m m2 ad m2 m2 Kcal/(m2h◦C) ◦C Kcal/h % % % 1+% W Kcal/h
BATHROOM / 26°C
ÇCP8 E 0,7 0,7 0,49 1 0,49 2,2 29 31,262
DD9 E 28 1,5 3 4,5 1 0,49 4,01 0,55 29 63,9595
İK4 W 0,7 2,1 1,47 1 1,47 2,5 8 29,4
İD6 W 21 1,5 3 4,5 1 1,47 3,03 1,45 8 35,148
İD7 E 21 2,5 3 7,5 1 7,5 1,45 6 65,25
Figure 10.2
Figure 10.3
11. PIPE DIAMETER CALCULATION
Boru Parçası
Isı Miktarı
Uzunluğu
Sıcaklık farkı ...°C Yaklaşık boru çaplarına göre Değiştirilmiş boru çapına göre Fark
olduğuna göre ısı
miktarı
d W R LR ∑ξ Z D W R LR ∑ξ Z LR Z
No kcal/h kcal/h m m/s mmSS/m mmSS mmSS m/s mmSS mmSS mmSS mmSS mmSS
1 744 ------ 6 1/2" 0,13 2,2 13,2 12,2 10,18
2 1488 ------ 6,6 1/2" 0,13 2,2 14,52 5,5 4,65
3 2232 ------ 10 1/2" 0,2 4,5 45 8,8 17,4
4 2976 ------ 8 1/2" 0,26 7,5 60 5,8 13,92
Sum = 132,72 Sum = 46,15
Figure 11.2
Figure 11.3
Şiber Valve
Double Elbow (Narrow)
Double Elbow (Wide)
T Input (Departure)
Elbow
T Pass (Departure)
T Counter Current
Boiler or Radiator
Trouser Piece
T Departure
T Merger
Pipe Diameter
S Piece
Part Number
Total
During this project, the heat loss calculation of an apartment was made.
Afterwards, the critical path was determined and the column diagram was
drawn. Finally, the pipe diameter calculation was made and the project was
completed with the selection of the appropriate radiator for the flat.
15. References
i. http://deneysan.com/content/images/documents/isitma-2_65672174.pdf
ii. https://www.alarko-carrier.com.tr/Upload/Content/Documents/875532ee-85e9-491e-a5b0-
503539162cb5.pdf