Scale parameters and functions

6.8 DR 7 interface parameters

6.8 DR 7 interface parameters

6.8.1 Overview
Data record DR 7 contains the parameters for defining the properties of the available I/O
(digital inputs, digital outputs, serial interfaces).
If a port is not used, the default values can be retained.

Procedure
● Change the parameters if necessary
● Transfer the data record to the scales

Table 6- 5 Assignment of data record 7

Variable Note Type Length Read De- Min. Max. Modbus


(bytes) write fault Register
Data record Contains no. of data record USHORT 2 r 7 - - 1300
number
Length Data record length information USHORT 2 r 48 - - 1301
Application Information about which application USHORT 2 r 141 - - 1302
the DR belongs to
Version ID Information about the current data USHORT 2 r 1 1 65635 1303
record version
Assignment for Assignment for input 0: USHORT 2 rw 0 0 0x7FFF 1304
digital input 0, Code 0: No command assigned
1, 2 (Page 88) 1 … 32767: Command triggered by
a rising edge (0→1 transition)
32769…65535 (command code +
32768): Command triggered by a
falling edge (1→0 transition)
Assignment for input 1: USHORT 2 rw 0 0 0x7FFF 1305
Encoding like input 0
Assignment for input 2: USHORT 2 rw 0 0 0x7FFF 1306
Encoding like input 0
Reserve USHORT 2 rw 0 0 1999 1307
Input filtering 0: No filtering USHORT 2 rw 2 0 8 1308
(hardware 1: 5 ms
setting) 2: 10 ms
(Page 88) 3: 15 ms
4: 20 ms
5: 25 ms
6: 30 ms
7: 40 ms