You are on page 1of 1

Sl No Description Detail Units Remark

FIRE PUMP SET


1 Fire pump Capacity 750 GPM
FIRE PUMP SET HEAD CALCULATION
1 Vertical Lift 84.80 Meter
2 Hence, Vertical Lift Pr.Drop 8.31 Bar
3 Pressure required at the farthest landing valve 6.90 Bar
4 Fittings Loss 2.28
Total Head 17.50 Bar
Proposed Fire Pump Head - bar - 750 GPM @ 17.5 bar head
Quantity- 1 No Electrical. 1 No. Diesel, 1 No Jockey
Basis of Design: UAE FLS / NFPA 14