GAS DEMAND CALCULATION
Project No. 3481 Date 08/05/23
Project Name SERENIA LIVING Prepared By MPT
Checked By DW
Issue IFC
1 Assumptions and Gas Properties Conversions
Product Composition Gross Heat Content Value From [unit] To [unit] Result
[%] Product [BTU/m3] [BTU/kg] [Unit] [Unit]
NG 37,633 N/A 47,608.00 BTU/hr kW 13.94
LPG 100% Propane 88,852 47,608 1.00 LPG [kg] LPG [litres] 1.96
SNG 60% Propane 53,311 28,565 2.00 LPG [litres] LPG [kg] 1.02
40% Air 39.70 MJ kW 11.03
10.00 kW MJ 36.00
4338 kcal/hr BTU/hr 17,203.08 1 kW= 3415.8
3 Load Calculation
Daily Gas
Unit Gas Load Hourly Gas Load Operation
Load
Description Quantity Unit Capacity Diversity Factor Hourly Capacity
SNG SNG SNG
[No.'s] [kW per capita] [BTU/hr] [m3/hr] [kW] [BTU/hr] [m3/hr] [hrs] [m3/day]
Tower 1 (2 Bedrooms) 96 7.1 24,252 0.45 0.500 340.8 1,164,105 21.84 1.0 44
Tower 1 (Presidential Penthouse) 1 11.8 40,306 0.76 0.500 5.9 20,153 0.38 1.0 1
Tower 2 (3&4 Bedrooms) 84 7.1 24,252 0.45 0.500 298.2 1,018,592 19.11 1.0 38
Tower 2 (Presidential Penthouse) 1 11.8 40,306 0.76 0.500 5.9 20,153 0.38 1.0 1
Tower 3 23 11.8 40,306 0.76 0.500 135.7 463,524 8.69 1.0 17
Tower 4 21 11.8 40,306 0.76 0.500 123.9 423,218 7.94 1.0 16
Main Swimming Pool Heating 1 1,291.0 4,409,798 82.72 1.000 1,291.0 4,409,798 82.72 12.0 993
Kids Pool Heating 1 58.0 198,116 3.72 1.000 58.0 198,116 3.72 12.0 45
TOTAL: 2,259.4 7,717,658.5 144.8 1,153.87
Note:Gas Demand for the residential kitchens assumptions to be finalized by the Gas specialist contractor
GAS DEMAND CALCULATION
Project No. 3481 Date 27.06.2022
Project Name SERENIA LIVING -TOWER-2 Prepared By MPT
Checked By SM
Issue SD
1 Assumptions and Gas Properties Conversions
Product Composition Gross Heat Content Value From [unit] To [unit] Result
[%] Product [BTU/m3] [BTU/kg] [Unit] [Unit]
NG 37,633 N/A 47,608.00 BTU/hr kW 13.94
LPG 100% Propane 88,852 47,608 1.00 LPG [kg] LPG [litres] 1.96
SNG 60% Propane 53,311 28,565 2.00 LPG [litres] LPG [kg] 1.02
40% Air 39.70 MJ kW 11.03
10.00 kW MJ 36.00
4338 kcal/hr BTU/hr 17,203.08 1 kW= 3415.8
3 Load Calculation
Daily Gas
Unit Gas Load Hourly Gas Load Operation
Load
Description Quantity Unit Capacity Diversity Factor Hourly Capacity
SNG SNG SNG
[No.'s] [kW per capita] [BTU/hr] [m3/hr] [kW] [BTU/hr] [m3/hr] [hrs] [m3/day]
Tower 2 85 19.0 64,900 1.22 0.500 807.5 2,758,259 51.74 1.0 103
TOTAL: 807.5 2,758,258.5 51.7 103.48
GAS DEMAND CALCULATION
Project No. 3481 Date 15.07.2022
Project Name SERENIA LIVING -TOWER-3 Prepared By MPT
Checked By SM
Issue SD
1 Assumptions and Gas Properties Conversions
Product Composition Gross Heat Content Value From [unit] To [unit] Result
[%] Product [BTU/m3] [BTU/kg] [Unit] [Unit]
NG 37,633 N/A 47,608.00 BTU/hr kW 13.94
LPG 100% Propane 88,852 47,608 1.00 LPG [kg] LPG [litres] 1.96
SNG 60% Propane 53,311 28,565 2.00 LPG [litres] LPG [kg] 1.02
40% Air 39.70 MJ kW 11.03
10.00 kW MJ 36.00
4338 kcal/hr BTU/hr 17,203.08 1 kW= 3415.8
3 Load Calculation
Daily Gas
Unit Gas Load Hourly Gas Load Operation
Load
Description Quantity Unit Capacity Diversity Factor Hourly Capacity
SNG SNG SNG
[No.'s] [kW per capita] [BTU/hr] [m3/hr] [kW] [BTU/hr] [m3/hr] [hrs] [m3/day]
Tower 3 23 19.0 64,900 1.22 0.500 218.5 746,352 14.00 1.0 28
TOTAL: 218.5 746,352.3 14.0 28.00
GAS DEMAND CALCULATION
Project No. 3481 Date 15.07.2022
Project Name SERENIA LIVING -TOWER-4 Prepared By MPT
Checked By SM
Issue SD
1 Assumptions and Gas Properties Conversions
Product Composition Gross Heat Content Value From [unit] To [unit] Result
[%] Product [BTU/m3] [BTU/kg] [Unit] [Unit]
NG 37,633 N/A 47,608.00 BTU/hr kW 13.94
LPG 100% Propane 88,852 47,608 1.00 LPG [kg] LPG [litres] 1.96
SNG 60% Propane 53,311 28,565 2.00 LPG [litres] LPG [kg] 1.02
40% Air 39.70 MJ kW 11.03
10.00 kW MJ 36.00
4338 kcal/hr BTU/hr 17,203.08 1 kW= 3415.8
3 Load Calculation
Daily Gas
Unit Gas Load Hourly Gas Load Operation
Load
Description Quantity Unit Capacity Diversity Factor Hourly Capacity
SNG SNG SNG
[No.'s] [kW per capita] [BTU/hr] [m3/hr] [kW] [BTU/hr] [m3/hr] [hrs] [m3/day]
Tower 3 22 19.0 64,900 1.22 0.500 209.0 713,902 13.39 1.0 27
TOTAL: 209.0 713,902.2 13.4 26.78
CIBSE Public health engineering Part 11 - Miscellaneous piped services: The Institute of Plumbing Design Guide Chapter 6 Gas:
NFPA 54 - 2006 National Fuel Gas Code 2006 Edition:
Number of Units Diversity Factor
1-5 1
5-10 0.9
10-20 0.7
20-50 0.6
50-100 0.5
100-150 0.4
150 and above 0.3