Professional Documents
Culture Documents
TABLE OF CONTENTS
PART 1 - GENERAL
A. The design drawings are diagrammatic and they may not show all physical
arrangements, offsets, bends, or elbows which may be required for installation of various
materials, equipment, piping, and ductwork systems in allotted spaces. The Contractor
shall examine these and other available drawings to determine space limitations and
interferences. The Contractor shall be responsible for making any minor changes in
location of equipment, pipe and ductwork from that shown on drawings and for all
physical details required for installation. Cost for adapting Contractor's work to jobsite
conditions shall not be considered as basis of an extra cost to contract. The Contractor
shall get approval before proceeding with any change.
B. Information pertaining to new and existing conditions that are described in the
specifications or appear on drawings are based on available records. While such data has
been collected with reasonable care, there is no expressed or implied guarantee that
conditions so indicated are entirely representative of those actually existing or that
unlooked for developments may not occur. Such information is merely provided to assist
the Contractor in his investigation of conditions.
C. The Contractor must carefully examine the drawings, specifications and project site,
and verify all measurements, distances, levels, materials, equipment, etc. before starting
work.
D. Drawings shall not be scaled for determining exact dimensions or location of equipment.
E. All works not shown on drawings in complete detail shall be installed in conformance
with accepted standard practice and manufacturer’s recommendations.
F. All items shall be installed in a manner and in locations avoiding all obstructions,
preserving headroom and keeping openings and passageways clear. Changes shall be
made to the location of equipment and materials as may be necessary in order to meet
this requirement.
G. Work indicated on drawings, but not mentioned in Specifications, or vice versa, shall
be performed as if specifically mentioned or indicated by both.
1.3 DEFINITIONS
A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms,
furred spaces, pipe and duct chases, unheated spaces immediately below roof, spaces
above ceilings, unexcavated spaces, crawlspaces, and tunnels.
D. Concealed, Interior Installations: Concealed from view and protected from physical
contact by building occupants. Examples include above ceilings and chases.
A. All systems, materials, equipment and procedures associated with Fire Protection Systems
shall be in accordance with NFPA requirements as well as the local civil defense code
and requirements
B. Unless indicated otherwise, sprinkler protection shall be provided in all areas except
where omission is allowed by NFPA 13
1.5 SUBMITTALS
A. Welding certificates.
C. Shop Drawings:
a. Drawings shall be overlaid with shop drawings of other trades and checked
for conflicts.
b. Shop drawings shall identify the related contract drawing number or related
reference drawing.
c. Shop drawings shall be fully dimensioned, including both plan and elevation
dimensions from building reference points.
d. Shop drawings shall show schedules and description of equipment, valves,
piping and fittings
e. Shop drawings shall show complete system layout of equipment,
components, plumbing fixtures, piping, indicating service clearances, and
pipe sizes, fitting types and sizes and hanger support locations.
f. Planned piping layout, including valve and specialty locations and valve-stem
movement.
g. Clearances for installing and maintaining insulation.
h. Clearances for servicing and maintaining equipment, accessories, and
specialties, including space for disassembly required for periodic
maintenance.
4. Submit shop drawings for review as required by the contract documents. Additional
shop drawings may be requested when it appears that coordination issues are
not clearly resolved, when there is a question as to whether contract documents are
being complied with or the design intent is not being met.
D. Product Data:
E. Calculations:
1. Submit full hydraulic calculations prepared as per NFPA requirements for all the
Fire Fighting systems and covering all the different critical scenarios. The
calculations shall be used to verify the duty of the fire pumps or utility connection
requirements, pipe sizing and requirements of PRVs. All changes resulting from the
approved hydraulic calculations shall be under the scope of the contractor.
2. Submit detailed calculation for the clean agent system
3. Submit detailed calculation for the foam systems and any special pre-engineered
system shown on the plans
A. Steel Support Welding: Qualify processes and operators according to AWS D1.1,
"Structural Welding Code--Steel."
B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and
Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."
1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping."
2. Certify that each welder has passed AWS qualification tests for welding
processes involved and that certification is current.
F. All Material and equipment shall be new, unless stated otherwise and approved by
the employer.
H. All electrical work related to Fire Fighting items shall be as specified under Division
26, Electrical.
J. Equipment and materials to be installed outdoors shall be of the type that is designed,
manufactured and listed or approved for outdoor installation by being resistant to the
adverse effects of weather prevailing at the project location. The additional protective
measures against outdoor weather required by the manufacturers’ installation
instructions and prevalent practice shall be provided.
K. Where two or more equipment or components are of the same class, the same
manufacturer shall be used for selecting the equipment; component parts of the entire
system need not be products of the same manufacturer.
O. All equipment with moving parts shall be protected against personal injury
A. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through
shipping, storage, and handling to prevent pipe end damage and to prevent entrance of
dirt, debris, and moisture.
B. The equipment supplied shall be packed for protection against damage during handling,
transport, warehousing and installation. The efficiency of the packing shall be the
responsibility of the Contractor. The Contractor shall repair or replace any damaged
items, at no additional cost, as instructed by the Engineer even after delivery of the
equipment, if it is proven that the damage was caused by packing, storage, or handling
deficiencies.
C. Protect stored sprinklers, pipes, tubes, flanges, fittings, and piping specialties from
moisture and dirt. Elevate above grade.
D. Hose reels/racks, fire extinguishers and fire blankets shall be covered in protective
packaging and stored on well compartmented racks or shelving. Fire extinguishers, shall
be secured to prevent damage resulting from falling and in no instance shall they be
subject to temperatures in excess of 52 ºC or to direct sunlight.
1.8 COORDINATION
A. Coordinate mechanical equipment installation with other trades and building components.
B. Arrange for pipe spaces, chases, slots, and openings in building structure during progress
of construction, to allow for Fire Fighting installations.
C. For large equipment make provisions for the necessary openings in the building to allow
for admittance of all equipment before closing in.
E. Coordinate requirements for access panels and doors for Fire Fighting items requiring
access for operation, service or maintenance that are concealed behind finished
surfaces whether indicated on plans or not . Access panels and doors are specified in
Division 08 Section "Access Doors and Frames."
A. The entire firefighting system including all materials, components, equipment and
accessories and their installation shall conform to the requirements of the Authority
having jurisdiction and / or the Civil Defense Requirements.
B. AHJ requirements for permit approval shall be considered mandatory to the construction
C. All local codes and regulations shall become part of this specification and must be
adhered to where they exceed requirements as shown on the drawings or stated in the
specifications, without additional cost to the Contract. Contract documents may contain
more stringent requirements than the code.
A. The Contractor shall provide operating and maintenance instruction manuals covering
each and every item of equipment and devices furnished or erected by the Contractor
prior to "Substantial Completion" as required by Division 1.
C. Prior to final inspection or acceptance, fully instruct designated facility operating and
maintenance personnel on operation, adjustment and maintenance of products,
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
equipment and systems. Review contents of operating and maintenance manual with
personnel in full detail to explain all aspects of operations and maintenance.
A. Contractors are cautioned that they must exercise extreme care in any activity
involving contact with any installed roof membrane.
B. Construct protective plywood (3/4 in. thick) runways across the roof for moving, setting,
and installing equipment and piping systems. No activity on the roof will be
permitted without this protection. Start runways at the point of origin of any equipment
placed on roof and terminate at the point of installation on curb or base. Any and all
repairs necessary to bring the roofing system to its original condition shall be made by
an approved Roofing Contractor and paid for by the Contractor responsible for the
damage
A. All Trades shall work in cooperation with each other, and fit their work into the structure
as job conditions may demand. In general, priority shall be arranged as follows: (in
order of preference)
1.14 INSPECTION
A. The Contractor shall verify the location of underground service, utilities, structures,
etc., which may be encountered or be affected by his work and shall be responsible
for any damage caused by neglect to provide proper precautions or protection.
1.16 WELDING
B. The Contractor is entirely responsible for the quality of the welding and shall:
C. Rules of procedure for qualification of all welders and general requirements for fusion
welding shall conform with the applicable portions of ASME B31.1, Welding: Qualify
processes and operators according to ASME Boiler and Pressure Vessel Code: Section
IX, "Welding and Brazing Qualifications, and AWS B2.1 /B2.1M, and / or, as approved
by the Qualifications."
D. Examine each welder at job site, in the presence of the Engineer, to determine the ability
of the welder to meet the qualifications required. Test welders for piping for all
positions, including welds with the axis horizontal (not rolled) and with the axis vertical.
Each welder shall be allowed to weld only in the position in which he has qualified and
shall be required to identify his welds with his specific code marking signifying his name
and number as signed.
E. Provide the Engineer with a list of names and corresponding code markings. Retest
welders who fail to meet the prescribed welding qualifications. Disqualify welders,
who fail the second test, for work on the project.
F. Field bevels and shop bevels shall be done by mechanical means or by flame cutting.
Where beveling is done by flame cutting, surfaces shall be thoroughly cleaned of scale
and oxidation just prior to welding. Conform to specified standards.
G. Utilize split welding rings or approved alternate method for joints on all pipes above 50
mm to assure proper alignment, complete weld penetration, and prevention of weld spatter
reaching the interior of the pipe.
H. Piping shall not be split, bent, flattened, or otherwise damaged either before, during or
after installation.
I. Replace and re-inspect defective welds. Repairing defective welds by adding weld
material over the defect or by peening will not be permitted. Welders responsible for
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
J. Electrodes shall be stored in a dry heated area, and be kept free of moisture and
dampness during the fabrication operations. Discard electrodes that have lost part of their
coating.
A. Refer to Division 23, Vibration and Seismic Controls for HVAC Piping and
Equipment section, for sound and vibration requirements.
1.18 WARRANTY
A. Comply with Division 01 for all components and with special warranties listed in
individual section of Division 21
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where subparagraph titles below introduce lists, the following
requirements apply for product selection:
PART 3 - EXECUTION
A. All items shall be installed in the locations shown on the Drawings and strictly in
accordance with the manufacturer's instructions as well as the local civil defense
requirements.
B. The installation shall comply fully with all applicable standards and codes listed in
individual sections of Division 21.
C. Landing valves, Hose reels and fire extinguishers shall be securely fixed with
approved fixings in a position offering unobstructed access.
C. Fill holes which are cut oversize so that a tight fit is obtained around the objects
passing through.
D. Do not pierce beams or columns without written permission from the structural engineer
and then only as directed.
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of
piping systems. Indicated locations and arrangements were used to size pipe and calculate
friction loss, expansion, pump sizing, and other design considerations. Install piping
as indicated unless deviations to layout are approved on Coordination Drawings.
C. Comply with requirements of NFPA 13 and NFPA 14 for installation of fire protection
piping materials.
G. Install test connection where indicated, and at most remote point from risers.
H. Make sprinkler piping connections to the top of cross mains and feed mains.
I. Provide flush and test connections at ends of cross and feed mains.
J. Provide dedicated supports for the firefighting piping. Common supports with other
building services shall not be utilized.
L. Install piping indicated to be exposed and piping in equipment rooms and service areas
at right angles or parallel to building walls. Diagonal runs are prohibited unless
specifically indicated otherwise.
M. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
R. Select system components with pressure rating equal to or greater than system
operating pressure.
S. Size reduction shall be made using reducing fittings; bushings are not acceptable.
T. Independently support piping so that its weight shall not be supported by the equipment
to which it is connected.
U. Mitered ells, notched tees, and orange peel reducers are not acceptable. On threaded
piping, bushings are not acceptable.
W. Piping shall not be routed through electrical rooms or transformer vaults, or above
transformers, panelboards, or switchboards, including the required service space for this
equipment, unless the piping is serving this equipment.
X. Use only wrenches having square flat jaws, or non-metallic strap wrenches on brass
specialties; wrench marks not permitted.
Y. Select system components with pressure rating equal to or greater than system
operating pressure.
Z. Install escutcheons for penetrations of walls, ceilings, and floors in finished spaces.
AA. Install sleeves for pipes passing through concrete and masonry walls,
gypsum-board partitions, and concrete floor and roof slabs.
GG. Conveniently locate control panels, hardware and devices, valves, gauges,
cleanout fittings, and other equipment or specialties requiring frequent reading,
adjustments, inspection, repairs, or removal and replacement.
HH. Install gauges to be easily read from floors, platforms, and walkways.
II. Locate groups of pipes parallel to each other, spaced to permit valve servicing.
B. Install equipment level and plumb, parallel and perpendicular to other building systems
and components in exposed interior spaces, unless otherwise indicated.
D. Install equipment to allow right of way for piping installed at required slope.
A. Handle, transport and store sprinklers with care to prevent damage. Use only
wrenches supplied by manufacturer to tighten sprinklers in fittings.
C. Do not alter or apply ornamentation, coatings or paint to sprinklers. Exercise care when
painting sprinkler piping to avoid touching sprinklers with paint.
A. Refer to Division 21 specification section "Identification for Fire Suppression Piping and
Equipment."
B. Relocate devices Identifying the items for unobstructed view in finished construction
3.7 PAINTING
B. Damage and Touchup: Repair marred and damaged factory-painted finishes with
materials and procedures to match original factory finish.
B. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and
elevation to support and anchor Fire Fighting materials and equipment.
1. Construct concrete bases of dimensions indicated, but not less than 4 inches larger
in both directions than supported unit.
2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise
indicated, install dowel rods on 18-inch centers around the full perimeter of the
base.
3. Install epoxy-coated anchor bolts for supported equipment that extend through
concrete base, and anchor into structural concrete floor.
4. Place and secure anchorage devices. Use supported equipment manufacturer's
setting drawings, templates, diagrams, instructions, and directions furnished with
items to be embedded.
5. Install anchor bolts to elevations required for proper attachment to supported
equipment.
6. Install anchor bolts according to anchor-bolt manufacturer's written instructions.
7. Use 3000-psi, 28-day compressive-strength concrete and reinforcement as
specified in Division 03 Section "Cast-in-Place Concrete."
A. Cut, fit, and place wood grounds, nailers, blocking, and anchorages to support, and
anchor Fire Fighting
B. Select fastener sizes that will not penetrate members if opposite side will be exposed to
view or will receive finish materials. Tighten connections between members. Install
fasteners without splitting wood members.
3.11 GROUTING
A. Mix and install grout for Fire Fighting equipment base bearing surfaces, pump and other
equipment base plates, and anchors.
F. Place grout on concrete bases and provide smooth bearing surface for equipment.
A. Complete all phases of work so the system, equipment, and components can be checked
out, started, calibrated, operationally tested, adjusted, balanced, functionally tested, and
otherwise commissioned. Complete systems, including all subsystems, so they are
fully functional.
C. Additional tests may be required in the case of products, materials, and equipment if:
1. Provide for the safety and good condition of materials and equipment until
Substantial Completion. Protect materials and equipment from damage.
2. Protect installed Work.
3. In case of damage, immediately provide repairs and/or replacements as required.
4. Protect covering for bearings, open connections to tanks, pumps, compressors
and similar equipment.
5. Interior of piping shall be maintained free of dirt, grit, dust, and other foreign
materials.
6. Fixtures, piping, finished brass or bronze, and equipment shall have grease,
adhesive, labels, and foreign materials removed. Chromium, nickel plate,
polished bronze or brass Work shall be polished. Glass shall be cleaned inside and
out.
7. Prior to connecting sprinkler risers for flushing, flush water feed mains, lead-in
connections and control portions of sprinkler piping.
8. After fire sprinkler piping installation has been completed and before piping is
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
SECTION 210513
COMMON MOTOR REQUIREMENTS FOR FIRE SUPPRESSION EQUIPMENT
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including Conditions of Contract
and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes basic requirements for factory-installed and field-installed
motors.
1.3 SUBMITTALS
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
D. Rugged-Duty Motors: Where indicated, motors are totally enclosed with 1.25
minimum service factor, greased bearings, integral condensate drains, and capped
relief vents. Windings are insulated with non-hygroscopic material. External finish
is chemical-resistant paint over corrosion-resistant primer.
E. Source Quality Control: Perform the following routine tests according to IEC:
1. Measurement of winding resistance.
2. No-load readings of current and speed at rated voltage and frequency.
3. Locked rotor current at rated frequency.
4. High-potential test.
5. Alignment.
2.3 SINGLE-PHASE MOTORS
A. Type: As indicated or selected by manufacturer from one of the following, to suit
starting torque and other requirements of specific motor application.
1. Permanent-split capacitor.
2. Split-phase start, capacitor run.
3. Capacitor start, capacitor run.
4. Insulation: Unless otherwise indicated, Class B for motors located in air-
conditioned spaces and Class F for motors located outside or in non-air-
conditioned spaces.
5. Energy-Efficient Design: Premium efficiency – Class “eff1”, unless otherwise
indicated. Classification in accordance with the definition set by the
“European Commission of Electric Machinery and Power Electronics
Manufacturers”.
B. Shaded-Pole Motors: Do not use, unless motors are smaller than 0.037 kW (1/20
hp).
C. Thermal Protection: Where indicated or required, internal protection automatically
opens power supply circuit to motor when winding temperature exceeds a safe value
calibrated to temperature rating of motor insulation. Thermal protection device
3.2 COMMISSIONING
A. Check operating motors for unusual conditions during normal operation. Coordinate
with the commissioning of the equipment for which the motor is a part.
B. Take measurements and prepare a log of voltage, current, frequency, and power.
C. Report unusual conditions.
D. Report current deficiencies of field-installed units.
SECTION 210517
SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to this
Section.
1.2 SUMMARY
A. Section Includes:
1. Sleeves.
2. Stack-sleeve fittings.
3. Sleeve-seal systems.
4. Sleeve-seal fittings.
5. Grout.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
PART 2 - PRODUCTS
2.1 SLEEVES
A. Cast-Iron Wall Pipes: Cast or fabricated of cast or ductile iron and equivalent to
ductile-iron pressure pipe, with plain ends and integral water stop unless otherwise
indicated.
B. Galvanized-Steel Wall Pipes: ASTM A 53/A 53M, Schedule 40, with plain ends and
welded steel collar; zinc coated.
C. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40,
zinc coated, with plain ends.
1. Permanent sleeves are not required for holes in slabs formed by molded-PE or
-PP sleeves.
2. Cut sleeves to length for mounting flush with both surfaces.
a. Exception: Extend sleeves installed in floors of mechanical equipment
areas or other wet areas 2 inches (50 mm) above finished floor level.
3. Using grout, seal the space outside of sleeves in slabs and walls without
sleeve-seal system.
D. Install sleeves for pipes passing through interior partitions.
1. Cut sleeves to length for mounting flush with both surfaces.
2. Install sleeves that are large enough to provide 1/4-inch (6.4-mm) annular
clear space between sleeve and pipe or pipe insulation.
3. Seal annular space between sleeve and piping or piping insulation; use joint
sealants appropriate for size, depth, and location of joint. Comply with
requirements for sealants specified in Division 07 Section "Joint Sealants."
E. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings,
and floors at pipe penetrations. Seal pipe penetrations with firestop materials.
Comply with requirements for firestopping specified in Division 07 Section
"Penetration Firestopping."
3.2 STACK-SLEEVE-FITTING INSTALLATION
A. Install stack-sleeve fittings in new slabs as slabs are constructed.
1. Install fittings that are large enough to provide 1/4-inch (6.4-mm) annular
clear space between sleeve and pipe or pipe insulation.
2. Secure flashing between clamping flanges for pipes penetrating floors with
membrane waterproofing. Comply with requirements for flashing specified in
Division 07 Section "Sheet Metal Flashing and Trim."
3. Install section of cast-iron soil pipe to extend sleeve to 2 inches (50 mm)
above finished floor level.
4. Extend cast-iron sleeve fittings below floor slab as required to secure
clamping ring if ring is specified.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space
between piping and sleeve for installing sleeve-seal system.
b. Piping NPS 6 (DN 150) and Larger: Galvanized-steel wall sleeves with
sleeve-seal system
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space
between piping and sleeve for installing sleeve-seal system.
3. Concrete Slabs-on-Grade:
a. Piping Smaller Than NPS 6 (DN 150): Galvanized-steel wall sleeves
with sleeve-seal system
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space
between piping and sleeve for installing sleeve-seal system.
b. Piping NPS 6 (DN 150) and Larger: Galvanized-steel wall sleeves with
sleeve-seal system
1) Select sleeve size to allow for 1-inch (25-mm) annular clear space
between piping and sleeve for installing sleeve-seal system.
4. Concrete Slabs above Grade:
a. Piping Smaller Than NPS 6 (DN 150): Galvanized-steel-pipe sleeves.
b. Piping NPS 6 (DN 150) and Larger: Galvanized-steel-pipe sleeves.
5. Interior Partitions:
a. Piping Smaller Than NPS 6 (DN 150): Galvanized-steel-pipe sleeves.
b. Piping NPS 6 (DN 150) and Larger: Galvanized-steel-sheet sleeves.
PART 1 - GENERAL
1.2 SUMMARY
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
A. Section Includes:
1. Escutcheons.
2. Floor plates.
2.1 ESCUTCHEONS
D. Split-Casting Brass Type: With polished, chrome-plated finish and with concealed
hinge and setscrew.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install escutcheons for piping penetrations of walls, ceilings, and finished floors.
B. Install escutcheons with ID to closely fit around pipe, tube, and insulation of
piping and with OD that completely covers opening.
D. Install floor plates with ID to closely fit around pipe, tube, and insulation of piping
and with OD that completely covers opening.
A. Replace broken and damaged escutcheons and floor plates using new materials.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
PART 1 - GENERAL
1.2 SUMMARY
A. Section Includes:
B. Related Requirements:
1. Section 220548 "Vibration and Seismic Controls for Plumbing Piping and
Equipment" for devices for plumbing equipment and systems.
2. Section 230548 "Vibration and Seismic Controls for HVAC" for devices for
HVAC equipment and systems.
1.3 DEFINITIONS
1. Include rated load, rated deflection, and overload capacity for each vibration
isolation device.
C. Welding certificates.
D. Seismic-restraint devices shall have horizontal and vertical load testing and
analysis and shall bear anchorage preapproval by ICC-ES or preapproval by
another agency acceptable to authorities having jurisdiction, showing maximum
seismic-restraint ratings. Ratings based on independent testing are preferred to
ratings based on calculations. If preapproved ratings are unavailable, submittals
based on independent testing are preferred. Calculations (including combining
shear and tensile loads) to support seismic-restraint designs must be signed and
sealed by a qualified professional engineer.
PART 2 - PRODUCTS
A. Seismic restraints shall be selected, designed and installed for the non-structural
components in accordance with “EPC 201-2012: Egyptian code to calculate loads
and forces in structural and buildings works" for buildings included under the
project to sustain the following loads:
2. Wind Loading:
1. Mounting Plates:
a. Top Plate: Encapsulated steel load transfer top plates, factory drilled
and threaded with threaded studs or bolts.
b. Baseplate: Encapsulated steel bottom plates with holes provided for
anchoring to support structure.
1. Factory-Set Height Guide with Shear Pin: Shear pin shall be removable and
reinsertable to allow for selection of pipe movement. Guides shall be
capable of motion to meet location requirements.
A. Elastomeric Mount in a Steel Frame with Upper and Lower Steel Hanger Rods:.
2.8 SNUBBERS
E. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-
resistant neoprene, with a flat washer face.
A. Adhesive Anchor Bolts: Drilled-in and capsule anchor system containing PVC or
urethane methacrylate-based resin and accelerator, or injected polymer or hybrid
mortar adhesive. Provide anchor bolts and hardware with zinc-coated steel for
interior applications and stainless steel for exterior applications. Select anchor
bolts with strength required for anchor and as tested according to ASTM E 488.
PART 3 - EXECUTION
3.1 EXAMINATION
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 APPLICATIONS
A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for
application by an agency acceptable to authorities having jurisdiction.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
D. Equipment Restraints:
E. Piping Restraints:
G. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged
to provide resilient media between anchor bolt and mounting hole in concrete base.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
J. Drilled-in Anchors:
A. Install flexible connections in piping where they cross seismic joints, where
adjacent sections or branches are supported by different structural elements, and
where the connections terminate with connection to equipment that is anchored to
a different structural element from the one supporting the connections as they
approach equipment. Comply with requirements in Section 211200 "Fire-
Suppression Standpipes," Section 211313 "Wet-Pipe Sprinkler Systems," and
Section 211316 "Dry-Pipe Sprinkler Systems" for piping flexible connections.
EQUIPMENT
PART 1 - GENERAL
1.2 SUMMARY
A. Section Includes:
1. Equipment labels.
2. Warning signs and labels.
3. Pipe labels.
4. Stencils.
5. Valve tags.
6. Warning tags.
B. Samples: For color, letter style, and graphic representation required for each
identification material and device.
1. Material and Thickness: Polished brass or aluminum, 0.032 inch (0.8 mm)
thick, with predrilled holes for attachment hardware.
2. Letter Color: Black.
3. Background Color: White.
4. Minimum Label Size: Length and width vary for required label content,
but not less than 2-1/2 by 3/4 inch (64 by 19 mm).
5. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing
distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing
distances up to 72 inches (1830 mm), and proportionately larger lettering
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
E. Minimum Label Size: Length and width vary for required label content, but not
less than 2- 1/2 by 3/4 inch (64 by 19 mm).
F. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is
less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances up to 72
inches (1830 mm), and proportionately larger lettering for greater viewing
distances. Include secondary lettering two-thirds to three-fourths the size of
principal lettering.
E. Pipe-Label Colors:
2.4 STENCILS
1. Tag Material: polished Brass or aluminum, 0.032 inch (0.8 mm) thick, with
predrilled holes for attachment hardware.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
B. Valve Schedules: For each piping system, on 8-1/2-by-11-inch (A4) bond paper.
Tabulate valve number, piping system, system abbreviation (as shown on valve
tag), location of valve (room or space), normal-operating position (open, closed, or
modulating), and variations for identification. Mark valves for emergency shutoff
and similar special uses.
PART 3 - EXECUTION
3.1 PREPARATION
B. Valve-Tag Application Schedule: Tag valves according to size, shape, and with
captions similar to those indicated in "Valve-Tag Size and Shape" Subparagraph
below:
A. Write required message on, and attach warning tags to, equipment and other
items where required.
SECTION 211100
FACILITY FIRE-SUPPRESSION WATER SERVICE PIPING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including Conditions of Contract
and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes fire-suppression piping and equipment for the following
building systems:
1. Automatic wet-type, Class I, fire-suppression standpipes and branches for
sprinklers.
2. fire-suppression sprinklers, including piping, valves, specialties, and
automatic sprinklers operated by fire-detection system.
1.3 DEFINITIONS
A. CPVC: Chlorinated polyvinyl chloride plastic.
B. Hose Connection: Valve with threaded outlet matching fire hose coupling thread for
attaching fire hose.
C. Hose Station: Hose connection, fire hose rack, and fire hose.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
1.5 SUBMITTALS
A. Product Data: For the following:
1. Pipe and fitting materials and methods of joining for standpipe piping.
2. Pipe and fitting materials and methods of joining for sprinkler piping.
3. Pipe hangers and supports.
4. Piping seismic restraints.
5. Valves, including specialty valves, accessories, and devices.
6. Alarm devices. Include electrical data.
7. Air compressors. Include electrical data.
8. Fire department connections. Include type; number, size, and arrangement of
inlets; caps and chains; size and direction of outlet; escutcheon and marking;
and finish.
9. Hose connections. Include size, type, and finish.
10. Sprinklers, escutcheons, and guards. Include sprinkler flow characteristics,
mounting, finish, and other pertinent data.
B. Fire-Hydrant Flow Test Report: As specified in "Preparation" Article.
C. Approved Sprinkler Piping Drawings: Working plans, prepared according to NFPA
13, that have been approved by Engineer and authorities having jurisdiction. Include
hydraulic calculations.
D. Field Test Reports and Certificates: As specified in "Field Quality Control" and
"Commissioning" Articles in Part 3 of this Section. Indicate and interpret test results
for compliance with performance requirements and as described in NFPA 13 and
NFPA 14. Include "Contractor's Material and Test Certificate for Aboveground
Piping" and "Contractor's Material and Test Certificate for Underground Piping."
E. Maintenance Data: For each type of standpipe and sprinkler specialty to include in
maintenance manuals specified in Division 1.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
1. Sprinkler Cabinets: Finished, wall-mounting steel cabinet and hinged cover,
with space for a minimum of six spare sprinklers plus sprinkler wrench.
Include the number of sprinklers required by NFPA 13 and wrench for
sprinklers. Include separate cabinet with sprinklers and wrench for each type
of sprinkler on Project.
PART 2 - PRODUCTS
2.1 PIPING MATERIALS
A. Refer to Part 3 "Piping Applications" Article for applications of pipe, tube, fitting,
and joining materials.
2.2 PIPES
A. Standard-Weight Seamless Black Steel Pipe: ASTM A 53, ASTM A 135, or ASTM
A 795; Schedule 40 in DN150 (NPS 6) and smaller, and Schedule 30 in DN200
(NPS 8) and larger.
2.3 PIPE FITTINGS
A. Malleable-Iron Threaded Fittings: ASME B16.3.
B. Steel, Threaded Couplings: ASTM A 865.
C. Steel Welding Fittings: ASTM A 234/A 234M, ASME B16.9, or ASME B16.11.
D. Steel Flanges and Flanged Fittings: ASME B16.5.
E. Steel, Grooved-End Fittings: UL-listed and FM-approved, ASTM A 47M (ASTM A
47), malleable iron or ASTM A 536, ductile iron; with dimensions matching steel
pipe and ends factory grooved according to AWWA C606.
sets for bypass, drain, electric sprinkler alarm switch, pressure gages, retarding
chamber, and fill-line attachment with strainer.
1. Option: Grooved-end connections for use with keyed couplings.
2. Drip Cup Assembly: Pipe drain without valves, and separate from main drain
piping.
B. Pressure-Regulating Valves: UL 1468, 2760-kPa (400-psig) minimum rating, brass.
Include DN40 or DN65 (NPS 1-1/2 or NPS 2-1/2), female NPS inlet and outlet;
adjustable setting feature; and straight or 90-degree angle pattern design as
indicated.
1. Finish: Rough chrome-plated.
C. Zone / Floor control valve assembly (ZV): UL listed and FM approved, rated for
1200-kpa (175-psig) working pressure, designed for horizontal or vertical
installation. Assembly include OS & Y gate valve, supervisory switch, flow switch
and alarm check valve. Details of alarm check valve are as above. For more
guidance on arrangement of zone / floor control valves refer to NFPA 13 - Appendix
A.
D. Automatic Air Vents (AAV): Float type with brass base and connection rail. Body
cover, float and vacuum breaker of high quality temperature resisting synthetic
material, suitable for working pressure 1200kpa (175 psig)
E. Ball Drip Valves: UL 1726, automatic drain valve, DN20 (NPS 3/4), ball check
device with threaded ends.
2.9 SPRINKLERS
A. Automatic Sprinklers: With heat-responsive element complying with the following:
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
sizes and threads, and bottom outlet with pipe threads. Include brass, lugged caps,
gaskets, and brass chains; brass, lugged swivel connection and drop clapper for each
hose-connection inlet; 450-mm high brass sleeve; and round, floor, brass,
escutcheon plate with marking "AUTO SPKR & STANDPIPE."
1. Finish Including Sleeve: Polished brass.
A. Pressure Gages: UL 393, 90- to 115-mm diameter dial with dial range of 0 to 1725
kPa (0 to 250 psig).
PART 3 - EXECUTION
3.1 PREPARATION
A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results for
system design calculations required in "Quality Assurance" Article in Part 1 of this
Section.
B. Report test results promptly and in writing.
3.2 EARTHWORK
A. Refer to Section "Earthwork" for excavating, trenching, and backfilling.
3.3 EXAMINATION
A. Examine roughing-in for hose connections and stations to verify actual locations of
piping connections before installation.
B. Examine walls and partitions for suitable thickness, fire- and smoke-rated
construction, framing for hose-station cabinets, and other conditions where hose
connections and stations are to be installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
C. Piping between Fire Department Connections and Check Valves: Use galvanized,
standard-weight steel pipe with threaded ends; cast- or malleable-iron threaded
fittings; and threaded joints, or,
D. Piping between Fire Department Connections and Check Valves: Use galvanized,
standard-weight steel pipe with grooved ends; steel, grooved-end fittings; steel,
keyed couplings; and grooved joints.
E. Underground Service-Entrance Piping: Use UPVC Class 5 pipes, provide UPVC
coupling of the same class of that of pipes. For each coupling provide 2 rubber rings.
Rubber rings to comply with ASTM D 1869
F. Standpipes: Use the following:
1. DN65 (NPS 2.5) and Smaller: Standard-weight seamless steel pipe with
threaded ends, cast- or malleable-iron threaded fittings, and threaded joints.
2. DN65 (NPS 2.5) and Larger: Standard-weight seamless steel pipe with
grooved ends; steel, grooved-end fittings; steel, keyed couplings; and grooved
joints.
G. Wet-Pipe Sprinklers: Use the following:
1. Sprinkler-Piping Option: Mechanical-T bolted-branch-outlet fittings may be
used downstream from sprinkler zone valves.
2. DN65 (NPS 2.5) and Smaller: Standard-weight seamless steel pipe with
threaded ends, cast- or malleable-iron threaded fittings, and threaded joints, or,
3. DN65 (NPS 2-1/2) and Larger: Standard-weight seamless steel pipe with
grooved ends; steel, grooved-end fittings; steel, keyed couplings; and grooved
joints.
A. Drawings indicate valve types to be used. Where specific valve types are not
indicated, the following requirements apply:
1. Fire-Protection-Service Valves: UL listed and FM approved for applications
where required by NFPA 13 and NFPA 14.
a. Shutoff Duty: Use gate valves.
2. General-Duty Valves: For applications where UL-listed and FM-approved
valves are not required by NFPA 13 and NFPA 14.
a. Shutoff Duty: Use gate, ball, or butterfly valves.
b. Throttling Duty: Use globe, ball, or butterfly valves.
H. Install sprinkler zone control valves, test assemblies, and drain risers adjacent to
standpipes when sprinkler piping is connected to standpipes.
I. Install drain valves on standpipes.
J. Install ball drip valves to drain piping between fire department connections and
check valves. Drain to floor drain or outside building.
K. Install alarm devices in piping systems.
L. Hangers and Supports: Comply with NFPA 13 for hanger materials. Install
according to NFPA 13 for sprinkler piping and to NFPA 14 for standpipes.
M. Earthquake Protection: Install piping according to NFPA 13 to protect from
earthquake damage.
N. Install piping with grooved joints according to manufacturer's written instructions.
Construct rigid piping joints, unless otherwise indicated.
O. Install pressure gages on riser or feed main, at each sprinkler test connection, and at
top of each standpipe. Include pressure gages with connection not less than DN8
(NPS 1/4) and with soft metal seated globe valve, arranged for draining pipe
between gage and valve. Install gages to permit removal, and install where they will
not be subject to freezing.
E. Alarm Check Valves: Install valves in vertical position for proper direction of flow,
including bypass check valve and retard chamber drain-line connection.
F. Dry-Pipe Valves: Install trim sets for air supply, drain, priming level, alarm
connections, ball drip valves, pressure gages, priming chamber attachment, and fill-
line attachment.
1. Air-Pressure Maintenance Devices for Dry-Pipe Systems: Install shutoff
valves to permit servicing without shutting down sprinkler system; bypass
valve for quick system filling; pressure regulator or switch to maintain system
pressure; strainer; pressure ratings with 95- to 410-kPa (14- to 60- psig)
adjustable range; and 1200-kPa (175-psig) maximum inlet pressure.
2. Install air compressor and compressed-air supply piping.
3.14 CONNECTIONS
A. Connect water-supply piping and standpipes and sprinklers to fire pumps. Include
backflow preventers.
B. Install ball drip valves at each check valve for fire department connection. Drain to
floor drain or outside building.
3.17 CLEANING
A. Clean dirt and debris from sprinklers.
B. Remove and replace sprinklers having paint other than factory finish.
3.18 PROTECTION
3.19 COMMISSIONING
A. Verify that specialty valves, trim, fittings, controls, and accessories are installed and
operate correctly.
B. Verify that air compressors and their accessories are installed and operate correctly.
C. Verify that specified tests of piping are complete.
D. Verify that damaged sprinklers and sprinklers with paint or coating not specified are
replaced with new, correct type.
E. Verify that sprinklers are correct types, have correct finishes and temperature
ratings, and have guards as required for each application.
F. Verify that potable-water supplies have correct types of backflow preventers.
G. Drain dry-pipe sprinkler piping.
H. Pressurize and check dry-pipe sprinkler piping air-pressure maintenance devices and
air compressors.
I. Verify that hose connections and fire department connections have threads
compatible with local fire department equipment.
J. Fill wet-pipe sprinkler piping with water.
K. Fill standpipes with water.
L. Verify that hose connections are correct type and size.
M. Verify that hose stations are correct type and size.
N. Energize circuits to electrical equipment and devices.
O. Start and run excess-pressure pumps.
P. Start and run air compressors.
Q. Adjust operating controls and pressure settings.
R. Coordinate with fire alarm tests. Operate as required.
S. Coordinate with fire-pump tests. Operate as required.
3.20 DEMONSTRATION
PART 1 - GENERAL
1.2 SUMMARY
A. This Section includes piping and equipment for the following building systems:
1.3 DEFINITIONS
A. Hose Connection: The cabinet is not fire-rated, whilst the specified fire rating of
walls shall be maintained..
B. Hose Station: Hose connection, fire hose reel, and fire hose.
A. Verify the design of standpipes for compliance with NFPA, and obtain approval
from Engineer and authorities having jurisdiction. Include minimum residual
pressures at hydraulically remote outlets according to the following:
1.5 SUBMITTALS
1. Pipe and fitting materials and methods of joining for standpipe piping.
2. Pipe hangers and supports.
3. Piping seismic restraints.
4. Valves, including specialty valves, accessories, and devices.
C. Welding certificates.
D. Field Test Reports and Certificates: As specified in "Field Quality Control" and
"Commissioning" Articles in Part 3 of this Section. Indicate and interpret test
results for compliance with performance requirements and as described in NFPA
14. Include "Contractor's Material and Test Certificate for Aboveground Piping"
and "Contractor's Material and Test Certificate for Underground Piping."
E. Operation and Maintenance Data: For each type of standpipe specialty to include
in operation and maintenance manuals specified in Division 1.
PART 2 - PRODUCTS
A. Automatic Wet-Type LV-1 and LV-2, Class I Standpipe System: Includes NPS
2-1/2 (DN 65) hose connections. Has open water-supply valve with pressure
maintained and is capable of supplying water demand.
B. Automatic Wet-Type, Class II Standpipe System: Includes NPS 1-1/2 (DN 40)
hose stations. Has open water-supply valve with pressure maintained and is
capable of supplying water demand.
C. Automatic Wet-Type, Class III Standpipe System: Includes NPS 1-1/2 (DN 40)
hose stations and NPS 2-1/2 (DN 65) hose connections. Has open water-supply
valve with pressure maintained and is capable of supplying water demand
provided with 40mm/65mmx30m fire hose.
2.3 PIPES
B. Schedule 30 Steel Pipe: ASTM A 135/A 135M or ASTM A 795/A 795M, with
wall thickness less than Schedule 40 and equal to or greater than Schedule 30 or
ASTM A 795/A 795M and ASME B36.10M, Schedule 30 wrought-steel pipe.
B. Steel Welding Fittings: ASTM A 234/A 234M, ASME B16.9, or ASME B16.11.
A. Steel, Keyed Couplings: UL 213 and AWWA C606, for steel-pipe dimensions.
Include ASTM A 536, ductile-iron housing, rubber gaskets, and steel bolts and
nuts. Include listing for dry-pipe service for couplings for dry piping.
B. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch (3.2 mm)
thick.
1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges:
Full-face gaskets.
2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges:
Ring-type gaskets.
C. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise
indicated.
B. Gate Valves, DN50 (NPS 2) and Smaller: UL 262; cast-bronze, threaded ends;
solid wedge; OS&Y; and rising stem.
C. Gate Valves, DN65 (NPS 2-1/2) and Larger: UL 262, iron body, bronze mounted,
taper wedge, OS&Y, and rising stem. Include replaceable, bronze, wedge facing
rings and flanged ends.
D. Swing Check Valves, DN50 (NPS 2) and Smaller: UL 312 or MSS SP-80, Class
150; bronze body with bronze disc and threaded ends.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
E. Swing Check Valves, DN65 (NPS 2-1/2) and Larger: UL 312, cast-iron body and
bolted cap, with bronze disc or cast-iron disc with bronze-disc ring and flanged
ends.
F. Split-Clapper Check Valves, DN100 (NPS 4) and Larger: UL 312, cast-iron body
with rubber seal, bronze-alloy discs, and stainless-steel spring and hinge pin.
B. Ball Drip Valves: UL 1726, automatic drain valve, DN20 (NPS 3/4), ball check
device with threaded ends.
C. ALTITUDE VALVE
2. The pilot system shall be furnished complete and installed on the main
valve. It shall include the altitude pilot, a needle valve, Y-strainer and
isolation ball valves. The one-way altitude valve shall be operationally and
hydrostatically tested prior to shipment.
3. The main valve body and bonnet shall be ductile iron per ASTM A536;
grade 65-45- 12.end connections shall be flanged. All ferrous surfaces shall
be coated with a minimum of 4 MILS epoxy. The main valve seat ring shall
be bronze per ASTM B61. Elastomers (diaphragms, resilient seats and O-
rings) shall be BUNA-N. The pilot shall be bronze per ASTM B61. The
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
needle valve and isolation ball valves shall be brass and control line tubing
shall be copper.
4. The one-way altitude valve shall be suitable for a flow of at least 1450
l/sec and a maximum pressure of 16 bars.
A. Manual Control Stations: Hydraulic operation, with union, DN15 (NPS 1/2) pipe
nipple, and bronze ball valve. Include metal enclosure labeled "MANUAL
CONTROL STATION" with operating instructions and cover held closed by
breakable strut to prevent accidental opening.
2. Threads and Gaskets: NFPA 1963 and matching local fire department
threads.
3. Flow-Restricting Devices: DN40 (NPS 1-1/2) brass, adjustable for DN40
(NPS 1- 1/2) fire hose inlet.
4. Fire Hose: NFPA 1961 and UL 219 or LPCB, lined fire hose with
couplings, gaskets, and nozzle. Include the following fire hose materials:
a. Jacket: Combination of natural and synthetic threads.
b. Lining: Combination of rubber and plastic compounds.
c. Cover: Rubber, plastic, or combination of compounds.
5. Nozzles: UL 401.
6. Drain Valves: UL 1726.
7. Mountings: Pipe clamp or wall bracket for freestanding units.
8. Mountings: Pipe escutcheon for cabinet-mounted units.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
B. DN65 and DN40 (NPS 2-1/2 and NPS 1-1/2) Hose Stations: DN65 (NPS 2-1/2)
hose valve with male threaded outlet, cap, and chain and DN40 (NPS 1-1/2) hose
valve; hose reel with water-retention device and pins for folded, DN40 (NPS 1-
1/2) lined hose; and DN40 (NPS 1-1/2) lined hose with swivel inlet coupling
and nozzle.
C. DN40 (NPS 1-1/2) Hose-Reel Hose Stations: DN40 (NPS 1-1/2) hose valve
standard UL 668; semiautomatic hose reel standard UL 47 or LPCB with water-
retention device and pins for DN40 (NPS 1-1/2) lined hose; and DN40 (NPS 1-
1/2) lined hose standard NFPA 1961 and UL 219 with swivel inlet coupling and
nozzle (standard UL 401).
A. Wall, Fire Department Connections: UL 405; cast-brass body with brass, wall,
escutcheon plate; brass, lugged caps with gaskets and brass chains; and brass,
lugged swivel connections. Include inlets with threads according to NFPA 1963
and matching local fire department sizes and threads, outlet with pipe threads,
extension pipe nipples, check devices or clappers for inlets, and escutcheon plate
with marking "STANDPIPE."
1. Type: Exposed, projecting mounting.
2. Escutcheon Plate: Round.
3. Finish: Rough chrome-plated.
A. Pressure Gages: UL 393, 90- to 115-mm diameter dial with dial range of 0 to
1725 kPa (0 to 250 psig).
PART 3 - EXECUTION
3.1 PREPARATION
A. Perform fire-hydrant flow test according to NFPA 291. Use results for system
design calculations required in "Quality Assurance" Article in Part 1 of this
Section.
3.2 EARTHWORK
3.3 EXAMINATION
A. Examine roughing-in for hose connections and stations to verify actual locations
of piping connections before installation.
B. Examine walls and partitions for suitable thickness, fire- and smoke-rated
construction, framing for hose-station cabinets, and other conditions where hose
connections and stations are to be installed.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
B. Flanges, unions, and transition and special fittings with pressure ratings the
same as or higher than system's pressure rating may be used in aboveground
applications, unless otherwise indicated.
C. Piping between Fire Department Connections and Check Valves, and other dry-
type fire- suppression standpipe piping: Use galvanized, standard-weight steel
pipe with threaded ends; cast- or malleable-iron threaded fittings; and threaded
joints.
D. Piping between Fire Department Connections and Check Valves, and other dry-
type fire- suppression standpipe piping: Use galvanized, standard-weight steel
pipe with grooved ends; steel, grooved-end fittings; steel, keyed couplings; and
grooved joints.
8. DN200 (NPS 8) and Larger: Standard-weight steel pipe with plain ends,
steel welding fittings, and welded joints.
A. Drawings indicate valve types to be used. Where specific valve types are not
indicated, the following requirements apply:
A. Steel-Piping, Grooved Joints: Use Schedule 40 steel pipe with cut or roll-grooved
ends and Schedule 30 or thinner steel pipe with roll-grooved ends; steel,
grooved-end fittings; and steel, keyed couplings. Assemble joints with couplings,
gaskets, lubricant, and bolts according to coupling manufacturer's written
instructions. Use gaskets listed for dry-pipe service for dry piping.
B. Install shutoff valve, backflow preventer, pressure gage, drain, and other
accessories indicated at connection to water-service piping. Refer to Division 22
Section "Domestic Water Piping Specialties" for backflow preventers.
B. Install shutoff valve, backflow preventer, pressure gage, drain, and other
accessories indicated at connection to water distribution piping. Refer to Division
22 Section "Domestic Water Piping Specialties" for backflow preventers.
C. Use approved fittings to make changes in direction, branch takeoffs from mains,
and reductions in pipe sizes.
D. Install unions adjacent to each valve in pipes DN50 (NPS 2) and smaller.
Unions are not required on flanged devices or in piping installations using
grooved joints.
G. Install ball drip valves to drain piping between fire department connections and
check valves. Drain to floor drain or outside building.
I. Hangers and Supports: Comply with NFPA 13 for hanger materials. Install
according to NFPA 14.
L. Install pressure gages on riser or feed main, at each sprinkler test connection, and
at top of each standpipe. Include pressure gages with connection not less than
DN8 (NPS 1/4) and with soft metal seated globe valve, arranged for draining pipe
between gage and valve. Install gages to permit removal, and install where they
will not be subject to freezing.
B. Install freestanding hose connections for access and minimum passage restriction.
A. Install freestanding hose stations for access and minimum passage restriction.
B. Install DN40 (NPS 1-1/2) hose-station valves with flow-restricting device, unless
otherwise indicated.
C. Install DN65 (NPS 2-1/2) hose connections with quick-disconnect DN65 by DN40
(NPS 2- 1/2 by NPS 1-1/2) reducer adapter and flow-restricting device, unless
otherwise indicated.
3.14 CONNECTIONS
B. Install ball drip valves at each check valve for fire department connection.
Drain to floor drain or outside building.
A. Flush, test, and inspect standpipes according to NFPA 14, "System Acceptance"
Chapter.
B. Replace piping system components that do not pass test procedures and retest
to demonstrate compliance. Repeat procedure until satisfactory results are
obtained.
C. Report test results promptly and in writing to Engineer and authorities having
jurisdiction.
3.17 COMMISSIONING
A. Verify that specialty valves, trim, fittings, controls, and accessories are installed
and operate correctly.
B. Verify that air compressors and their accessories are installed and operate
correctly.
E. Verify that hose connections and fire department connections have threads
compatible with local fire department equipment.
G. Pressurize and check dry-pipe valve air-pressure maintenance devices and air
compressors.
3.18 DEMONSTRATION
PART 1 - GENERAL
1.2 SUMMARY
A. This Section includes fire-suppression sprinklers, piping, and equipment for the
following building systems:
1.3 DEFINITIONS
operate at working pressure higher than standard 175 psig (1200 kPa), but not
higher than 350 psig (2410 kPa).
A. Verify the design of sprinklers for conformance with NFPA 13, and obtain
approval from Engineer and authorities having jurisdiction.
B. Verify the design of sprinkler piping according to the following and obtain
approval from Engineer and authorities having jurisdiction:
1. Include 10 percent margin of safety for available water flow and pressure.
2. Include losses through water-service piping, valves, and backflow
preventers.
3. Sprinkler Occupancy Hazard Classifications: As per NFPA 13
requirements.
4. Minimum Density for Automatic-Sprinkler Piping Design: As follows:
1.6 SUBMITTALS
1. Pipe and fitting materials and methods of joining for sprinkler piping.
2. Pipe hangers and supports.
3. Piping seismic restraints.
4. Valves, including specialty valves, accessories, and devices.
5. Alarm devices. Include electrical data.
6. Fire department connections. Include type; number, size, and
arrangement of inlets; caps and chains; size and direction of outlet;
escutcheon and marking; and finish.
7. Excess-pressure pumps. Include electrical data.
8. Sprinklers, escutcheons, and guards. Include sprinkler flow
characteristics, mounting, finish, and other pertinent data.
a. Lighting fixtures.
b. Air outlets and inlets.
H. Welding certificates.
I. Field Test Reports and Certificates: As specified in "Field Quality Control" and
"Commissioning" Articles in Part 3 of this Section. Indicate and interpret test
results for compliance with performance requirements and as described in NFPA
13. Include "Contractor's Material and Test Certificate for Aboveground Piping"
and "Contractor's Material and Test Certificate for Underground Piping."
J. Operation and Maintenance Data: For each type of sprinkler specialty to include
in operation and maintenance manuals specified in Division 1.
A. Furnish extra materials described below that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
PART 2 - PRODUCTS
2.2 PIPES
B. Schedule 30 Steel Pipe: ASTM A 135/A 135M or ASTM A 795/A 795M black-
steel pipe where indicated, with wall thickness less than Schedule 40 and equal to
or greater than Schedule 30 or ASTM A 795/A 795M and ASME B36.10M,
Schedule 30 wrought- steel pipe.
B. Steel Welding Fittings: ASTM A 234/A 234M, ASME B16.9, or ASME B16.11.
A. Steel, Keyed Couplings: UL 213 and AWWA C606, for steel-pipe dimensions.
Include ASTM A 536, ductile-iron housing, rubber gaskets, and steel bolts and
nuts.
B. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch (3.2 mm)
thick.
1. Class 125, Cast-Iron Flanges and Class 150, Bronze Flat-Face Flanges:
Full-face gaskets.
2. Class 250, Cast-Iron Flanges and Class 300, Steel Raised-Face Flanges:
Ring-type gaskets.
C. Metal, Pipe-Flange Bolts and Nuts: ASME B18.2.1, carbon steel unless otherwise
indicated.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
B. Gate Valves, DN50 (NPS 2) and Smaller: UL 262; cast-bronze, threaded ends;
solid wedge; OS&Y; and rising stem.
C. Indicating Valves, DN65 (NPS 2-1/2) and Smaller: UL 1091; butterfly or ball-
type, bronze body with threaded ends; and integral indicating device.
D. Indicating Valves, larger than DN65 (NPS 2-1/2): UL 1091; butterfly, iron body.
Include replaceable, bronze, wedge facing rings and flanged ends; and integral
indicating device.
E. Gate Valves, DN65 (NPS 2-1/2) and Larger: UL 262, iron body, bronze mounted,
taper wedge, OS&Y, and rising stem. Include replaceable, bronze, wedge facing
rings and flanged ends; and integral indicating device.
G. Swing Check Valves, DN50 (NPS 2) and Smaller: UL 312 or MSS SP-80, Class
150; bronze body with bronze disc and threaded ends.
H. Swing Check Valves, DN65 (NPS 2-1/2) and Larger: UL 312, cast-iron body and
bolted cap, with bronze disc or cast-iron disc with bronze-disc ring and flanged
ends.
I. Split-Clapper Check Valves, DN100 (NPS 4) and Larger: UL 312, cast-iron body
with rubber seal, bronze-alloy discs, and stainless-steel spring and hinge pin.
between flanges.
A. General Requirements:
B. Alarm Check Valves: UL 193, should be capable to withstand the pump churn
pressure, designed for horizontal or vertical installation, with cast-iron flanged
inlet and outlet, bronze grooved seat with O-ring seals, and single-hinge pin and
latch design. Include trim sets for bypass, drain, electric sprinkler alarm switch,
pressure gages, retarding chamber, and fill- line attachment with strainer.
F. Ball Drip Valves: UL 1726, automatic drain valve, DN20 (NPS 3/4), ball check
device with threaded ends.
2.7 SPRINKLERS
A. General Requirements:
For Sauna rooms use high temperature rating sprinklers, for steam rooms
use intermediate temperature rating sprinklers
2. Extended-coverage sprinklers.
3. Flush ceiling sprinklers, including escutcheon.
4. Pendent sprinklers.
5. Quick-response sprinklers.
6. Recessed sprinklers, including escutcheon.
7. Sidewall sprinklers, including escutcheon.
8. Upright sprinklers.
9. Upright; pendent, or sidewall dry-type sprinklers connected to wet pipe
consists of a sprinkler permanently attached to the outlet of an extension
pipe nipple.
10. The sprinkler contains a required "weep" hole (or annular clearance) at
the seat as a means of identifying water leakage past the inlet seal. The
pipe nipple is sealed at the inlet to prevent water from entering the nipple
until the sprinkler operates. The inlet end of the dry type sprinkler is
installed into a threaded tee fitting, typically above a ceiling or
enclosure.
G. Sprinkler Escutcheons: Materials, types, and finishes for the following sprinkler
mounting applications. Escutcheons for concealed, flush, and recessed-type
sprinklers are specified with sprinklers.
D. Drop-Nipple Fittings: UL 1474, with threaded inlet, threaded outlet, and seals;
adjustable.
F. Sprinkler, Branch-Line Test Fittings: UL-listed, brass body; with threaded inlet
and capped drain outlet and threaded outlet for sprinkler.
1. Standard: UL 1474.
2. Type: Flexible hose for connection to sprinkler, and with bracket for
connection to ceiling grid.
3. Pressure Rating: [175-psig (1200-kPa) minimum] [350 psig (2410 kPa)].
4. Size: Same as connected piping, for sprinkler.
A. Wall, Fire Department Connections: UL 405; cast-brass body with brass, wall,
escutcheon plate; brass, lugged caps with gaskets and brass chains; and brass,
lugged swivel connections. Include inlets with threads according to NFPA 1963
and matching local fire department sizes and threads, outlet with pipe threads,
extension pipe nipples, check devices or clappers for inlets, and escutcheon plate
with marking "AUTO SPKR."
1. Type: Exposed, projecting mounting.
2. Escutcheon Plate: Round.
3. Finish: Rough chrome-plated.
caps, gaskets, and brass chains; brass, lugged swivel connection and drop
clapper for each hose-connection inlet; 450-mm high brass sleeve; and round,
floor, brass, escutcheon plate with marking "AUTO SPKR."
A. Pressure Gauges: UL 393, 90- to 115-mm diameter dial with dial range of 0 to
2410 kPa (0 to 350 psig).
1. Panels: UL listed and FM approved when used with thermal detectors and
Class A detector circuit wiring. Electrical characteristics are 220-V ac,
50 Hz, with 24-V dc rechargeable batteries.
2. Manual Control Stations: Electric operation, metal enclosure, labeled
"MANUAL CONTROL STATION" with operating instructions and a
cover held closed by breakable strut.
3. Manual Control Stations: Hydraulic operation, with union, DN15 (NPS
1/2) pipe nipple, and bronze ball valve. Include metal enclosure labeled
"MANUAL CONTROL STATION" with operating instructions and a
cover held closed by breakable strut.
PART 3 - EXECUTION
3.1 PREPARATION
A. Perform fire-hydrant flow test according to NFPA 13 and NFPA 291. Use results
for system design calculations required in "Quality Assurance" Article in Part 1 of
this Section.
B. Flanges, unions, and transition and special fittings with pressure ratings the
same as or higher than system's pressure rating may be used in aboveground
applications, unless otherwise indicated.
C. Piping between Fire Department Connections and Check Valves: Use galvanized,
standard- weight steel pipe with threaded ends; cast- or malleable-iron threaded
fittings; and threaded joints.
D. Piping between Fire Department Connections and Check Valves: Use galvanized,
standard- weight steel pipe with grooved ends; steel, grooved-end fittings; steel,
keyed couplings; and grooved joints.
joints.
2. DN100 (NPS 4) and Smaller: Standard-weight steel pipe with plain
ends, steel welding fittings, and welded joints.
3. DN100 (NPS 4) and Smaller: Schedule 30 steel pipe with roll-grooved
ends; steel, grooved-end fittings; steel, keyed couplings; and grooved
joints.
4. DN100 (NPS 4) and Smaller: Schedule 30 steel pipe with plain ends,
steel welding fittings, and welded joints.
5. DN125 and DN150 (NPS 5 and NPS 6): Standard-weight steel pipe with
grooved ends; steel, grooved-end fittings; steel, keyed couplings; and
grooved joints.
6. DN125 and DN150 (NPS 5 and NPS 6): Standard-weight steel pipe
with plain ends, steel welding fittings, and welded joints.
16. DN100 (NPS 4): Schedule 30 steel pipe with plain ends, steel welding
fittings, and welded joints.
A. Drawings indicate valve types to be used. Where specific valve types are not
indicated, the following requirements apply:
B. Steel-Piping, Grooved Joints: Use Schedule 40 steel pipe with cut or roll-grooved
ends and Schedule 30 or thinner steel pipe with roll-grooved ends; steel,
grooved-end fittings; and steel, keyed couplings. Assemble joints with couplings,
gaskets, lubricant, and bolts according to coupling manufacturer's written
instructions. Install couplings, flanges, flanged fittings, unions, nipples, and
transition and special fittings that have finish and pressure ratings same as or
higher than system's pressure rating for aboveground applications unless otherwise
indicated.
C. Install unions adjacent to each valve in pipes NPS 2 (DN 50) and smaller.
E. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
F. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and
fittings before assembly.
G. Flanged Joints: Select appropriate gasket material in size, type, and thickness
suitable for water service. Join flanges with gasket and bolts according to ASME
B31.9.
H. Threaded Joints: Thread pipe with tapered pipe threads according to ASME
B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to
remove burrs and restore full ID. Join pipe fittings and valves as follows:
1. Shop weld pipe joints where welded piping is indicated. Do not use
welded joints for galvanized-steel pipe.
B. Install shutoff valve, backflow preventer, pressure gage, drain, and other
accessories indicated at connection to water-service piping. Refer to Division 22
Section "Domestic Water Piping Specialties" for backflow preventers.
B. Install shutoff valve, backflow preventer, pressure gage, drain, and other
accessories indicated at connection to water distribution piping. Refer to Division
22 Section "Domestic Water Piping Specialties" for backflow preventers.
C. Use approved fittings to make changes in direction, branch takeoffs from mains,
and reductions in pipe sizes.
D. Install unions adjacent to each valve in pipes DN50 (NPS 2) and smaller.
Unions are not required on flanged devices or in piping installations using
grooved joints.
H. Install sprinkler zone control valves, test assemblies, and drain risers adjacent to
sprinkler risers when sprinkler branch piping is connected to sprinkler risers.
I. Install ball drip valves to drain piping between fire department connections and
check valves. Drain to floor drain or outside building.
K. Hangers and Supports: Comply with NFPA 13 for hanger materials and
installation.
N. Install pressure gages on riser or feed main and at each sprinkler test connection.
Include pressure gages with connection not less than DN8 (NPS 1/4) and with
soft metal seated globe valve, arranged for draining pipe between gage and
valve. Install gages to permit removal, and install where they will not be subject
to freezing.
A. Install listed fire-protection specialty valves, trim, fittings, controls, and specialties
according to NFPA 13, manufacturer's written instructions, and authorities having
jurisdiction.
D. Specialty Valves:
3.12 CONNECTIONS
B. Install ball drip valves at each check valve for fire department connection.
Drain to floor drain or outside building.
A. Flush, test, and inspect sprinkler piping according to NFPA 13, "Systems
Acceptance" Chapter.
B. Replace piping system components that do not pass test procedures and retest
to demonstrate compliance. Repeat procedure until satisfactory results are
obtained.
C. Report test results promptly and in writing to Engineer and authorities having
jurisdiction.
3.15 CLEANING
B. Remove and replace sprinklers having paint other than factory finish.
3.16 PROTECTION
3.17 COMMISSIONING
A. Verify that specialty valves, trim, fittings, controls, and accessories are installed
and operate correctly.
B. Verify that excess-pressure pumps and accessories are installed and operate
correctly.
C. Verify that air compressors and their accessories are installed and operate
correctly.
E. Verify that damaged sprinklers and sprinklers with paint or coating not specified
are replaced with new, correct type.
F. Verify that sprinklers are correct types, have correct finishes and temperature
ratings, and have guards as required for each application.
H. Verify that fire department connections have threads compatible with local fire
department equipment.
3.18 DEMONSTRATION
SECTION 212100
CARBON DIOXIDE EXTINGUISHING SYSTEM
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
PART 1 - GENERAL
1.1 SECTION INCLUDES
A. Fire detection system.
B. Control and supervision systems.
C. CO2 storage and distribution suppression system.
1.3 SUBMITTALS
A. Shop Drawings: To bear stamp of approval of authority having jurisdiction, Fire
Marshall, Owner's fire insurance underwriter. Indicate detailed layout of system,
including piping and location of each component. Include control diagrams, wiring
diagrams, and written sequence of operation.
B. Product Data: To bear stamp of approval of authority having jurisdiction, Fire
Marshall, Owner's fire insurance underwriter. Furnish each piece of equipment
comprising the system including cylinders, manifolds, control panel, nozzles,
detectors, alarm bells or horns, switches, and annunciators.
C. Samples: Submit one sample of each detector, manual pull station, and nozzle.
D. Design Data: Submit design calculations bearing stamp of approval of authority
having jurisdiction, Fire Marshall, Owner's fire insurance underwriter. Results shall
include calculations that verify system pressures, nozzle flow rate, orifice code
numbers, piping pressure losses, component flow data, and pipe sizes.
E. Test Reports: Indicate successful completion of tests.
F. Manufacturer's Installation Instructions: Indicate installation of equipment and
system components.
G. Manufacturer's Certificate: Certify that system meets or exceeds specified
requirements and ANSI/NFPA 12.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
1.5 WARRANTY
A. Provide one year warranty.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
Refer To The Attached Manufacturers List.
2.2 PIPE AND PIPING SPECIALTIES
A. Steel Pipe: ASTM A53 or A106, Schedule 40, for diameters up to 20 mm and
schedule 80 for diameters 25 mm & up to 50 mm.
1. Fittings: ANSI/ASME B16.3 malleable iron class 600 for sizes 2 inch (50
mm) and smaller, or ASTM A234, forged steel welding type fittings.
2. Joints: Screwed, ANSI/AWS D1.1 welded, or grooved and shouldered pipe
end couplings.
B. Pipe Hangers: ANSI/ASME B31.1, UL or FM approved for piping systemss, split
clamp up to 2-1/2 inch (60 mm) size, riser clamps over 2-1/2 inch (60 mm) size,
adequate to offset discharge thrust.
C. Escutcheons: Chrome plated pressed or stamped brass, one- piece or split pattern,
minimum 2 inches (50 mm) larger than opening.
D. Gages: ASME B40.1, UL 393, UL 404, [FS GG-G-76] [3-1/2 inch (90 mm)]
diameter cast aluminum case, phosphor bronze bourdon tube, rotary brass
movement, brass socket, front re- calibration adjustment, black figures on white
background, 1 percent mid-scale accuracy, scale calibrated in both psi and kPa.
D. Adjustment: Manual for normal or high sensitivity, with sensitivity setting visible
and requiring no special tools.
F. Cylinder Valves: Heavy duty forged brass, incorporating safety release pressure
operated manual control, solenoid discharge valve, and pressure gage. Provide
solenoid pilot valves for each cylinder or bank of cylinders.
G. Manifold: Provide for systems with more than one cylinder, with rack to secure
each cylinder and check valves between each cylinder discharge and manifold.
11. 1Relay contactor activated by detector zone board in alarm or trouble mode.
D. Provide cealed led – Acid batteries and charger for continuous operation of
detection, alarm, actuation and supervision functions for 48 hours. Provide
automatic battery switch-over upon failure of primary power supply.
E. Conceal control switches and indicators, with exception of Power On, Master
Trouble, Supervisory Trouble, Circuit 1 Alarm, Circuit 2 Alarm and Release
Indicators. Provide the following annunciation.
1. Power On : Green.
2. System Trouble : Amber.
3. Battery Trouble : Amber.
4. Circuit 1 Trouble : Amber.
5. Circuit 2 Trouble : Amber.
6. Ground Fault : Amber.
7. Release trouble : Amber.
8. Alarm Circuit 1 : Red.
9. Alarm Circuit 2 : Red.
10. Agent Release : Red.
11. Alarm Silence : Amber.
12. Battery Polarity : Amber.
13. Abort Trouble : Amber.
14. Alarm Output Trouble : Amber.
15. Supervisory Trouble : Amber.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify that spaces are ready to receive work.
B. Verify that enclosing walls are continuous above ceilings and below raised floors to
enable required concentration to be built up and maintained for required time to
ensure effective fire extinction.
3.2 INSTALLATION
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
escutcheons where exposed piping passes through walls, floors, and ceilings. Seal
pipe penetrations of fire separations.
O. Locate discharge nozzle approximately 6 inches (150 mm) above or below ceiling
and 6 inches (150 mm) below raised floors. Avoid interference with other piping
and equipment.
P. Locate remote manual releases at one or more doors to protect area where indicated.
Locate deadman abort switch adjacent.
Q. Provide signal to building fire alarm system. Refer to Section 16721.
R. Provide interlock with automatic closing door releases.
S. Provide interlock with motorized dampers. Refer to Section 15952.
3.3 TESTING
A. Provide systems testing and analysis.
B. Test distribution piping and valving, prior to nozzle installation, to 600 psig (4140
kPa) air pressure test. Inspect joints using soap water solution or halide torch or
lamp. Repair leaks and retest. Maintain test pressure for four hours.
C. Upon completion of installation provide final checkout inspection by factory trained
representative of manufacturer to ascertain proper system operation. Leave system
in a fully commissioned and automatic readiness state with circuitry energized and
supervised.
D. Test circuits including automatic discharge, manual discharge, equipment shut-
down, alarm devices, and storage container pressure. Test supervision of each
circuit.
E. Check each ionization detector with a sensitivity meter, adjust. Record sensitivity,
and include record in test report.
F. Submit original copies of tests, indicating that factory trained technical
representatives of the manufacturer have inspected and tested systems and are
satisfied with methods of installation, connections and operation.
3.5 DEMONSTRATION
A. Provide systems demonstration.
B. Demonstrate that components except cylinder discharge assembly, are functioning
properly and in conjunction with controls system.
C. Submit integrated step-by-step test procedure for approval 30 days prior to start of
demonstration.
1. Arrange meeting prior to demonstration with representatives of the Owner, the
Owner's Underwriter, and the installer.
2. Perform visual inspection and overall review of system installed.
3. Place minimum of three UL listed recording analyzers in space. Provide
certification that testing devices have been checked by recognized testing
authority within two weeks of date of demonstration.
4. Certify that replacement charge can be provided within 24 hours of
demonstration.
SECTION 212200
CLEAN AGENT EXTINGUISHING SYSTEM
PART 1 - GENERAL
PART 2 - PRODUCTS
2.1 MANUFACTURERS
Refer To The Attached Manufacturers List.
2.2 PIPE AND PIPING SPECIALTIES
A. Steel Pipe: ASTM A53 or A106, Schedule 40, black.
1. Fittings: ANSI/ASME B16.3 malleable iron class 300 for sizes 2 inch (50
mm) and smaller, or ASTM A234, forged steel welding type fittings.
E. Conceal control switches and indicators, with exception of Power On, Master
Trouble, Supervisory Trouble, Circuit 1 Alarm, Circuit 2 Alarm and Release
Indicators. Provide the following annunciation.
1. Power On : Green.
2. System Trouble : Amber.
3. Battery Trouble : Amber.
4. Circuit 1 Trouble : Amber.
5. Circuit 2 Trouble : Amber.
6. Ground Fault : Amber.
7. Release trouble : Amber.
8. Alarm Circuit 1 : Red.
9. Alarm Circuit 2 : Red.
10. Agent Release : Red.
11. Alarm Silence : Amber.
12. Battery Polarity : Amber.
13. Abort Trouble : Amber.
14. Alarm Output Trouble : Amber.
15. Supervisory Trouble : Amber.
2.9 MISCELLANEOUS EQUIPMENT
A. Alarm Bells: Low voltage to allow supervision of circuit wiring, of modular design,
with minimum sound level of 88 db at 10 ft (3 meters).
B. Alarm Horns: Low voltage to allow supervision of circuit wiring, with minimum
sound level of 90 db at 10 feet (3 meters)
2.10 OPERATING SEQUENCE
A. Actuation of one detector in either zone circuit:
1. Illuminate zone indicator.
2. Energize alarm horn.
3. Shut down air-conditioning system and close dampers.
4. Close doors to area.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
C. Route piping in orderly manner, concealed, plumb and parallel to building structure,
and maintain gradient. Install piping to conserve building space, and not interfere
with use of space and other work.
D. Securely support piping in accordance with ANSI/ASME B31.1 with allowance for
FM –200 thrust forces, and thermal expansion and contraction.
E. Use grooved mechanical couplings and fasteners only in accessible locations. Roll
groove piping only.
F. Install unions downstream of valves and at equipment or apparatus connections.
G. Prepare pipe, fittings, supports, and accessories for finish painting, in accordance
with Section 15055.
H. Identify in accordance with ANSI/NFPA 2001 requirements. Place directional
arrows and system labels wherever piping changes direction and minimum 20 feet (6
meters) on straight runs.
I. Secure cylinders as indicated on Drawings. [Where manifolded, mount and support
by rack as indicated. For each system provide same size cylinders containing equal
amounts of liquid.]
J. In rooms with suspended ceiling tiles, clip or retain tiles within 4 foot (1.2 m) radius
of the nozzles to prevent lifting during discharge.
K. Install wiring in accordance with Section [16120] & [16180] requirements.
L. Make final connections between equipment and system wiring under direct
supervision of factory trained representative of manufacturer.
M. Install engraved plastic instruction plate, detailing emergency procedures, at control
panel and at each manual discharge and abort switch location. At control panel
identify control logic units, contacts, and major circuits with permanent nameplates.
N. At hazard area walls pack space between pipe, pipe sleeve or surface penetration
with mineral fiber with elastomer calk to depth of 1/2 inch (13 mm). Provide
escutcheons where exposed piping passes through walls, floors, and ceilings. Seal
pipe penetrations of fire separations.
O. Locate discharge nozzle approximately 6 inches (150 mm) above or below ceiling
and 6 inches (150 mm) below raised floors. Avoid interference with other piping
and equipment.
P. Locate remote manual releases at one or more doors to protect area where indicated.
Locate deadman abort switch adjacent.
Q. Provide signal to building fire alarm system. Refer to Section 16721.
R. Provide interlock with automatic closing door releases.
S. Provide interlock with motorized dampers. Refer to Section 15952.
3.3 TESTING
A. Provide testing and analysis.
B. Test distribution piping and valving, prior to nozzle installation, to 50 psig (340
kPa) air pressure test. Inspect joints using soap water solution or halide torch or
lamp. Repair leaks and retest. Maintain test pressure for four hours.
C. Upon completion of installation provide final checkout inspection by factory trained
representative of manufacturer to ascertain proper system operation. Leave system
in a fully commissioned and automatic readiness state with circuitry energized and
supervised.
D. Test circuits including automatic discharge, manual discharge, equipment shut-
down, alarm devices, and storage container pressure. Test supervision of each
circuit.
E. Check each ionization detector with a sensitivity meter, adjust. Record sensitivity,
and include record in test report.
F. Submit original copies of tests, indicating that factory trained technical
representatives of the manufacturer have inspected and tested systems and are
satisfied with methods of installation, connections and operation.
3.4 MANUFACTURER'S FIELD SERVICES
A. Prepare and start systems.
B. Provide experienced manufacturer's field engineer to supervise installation and
performance testing of the system.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
3.5 DEMONSTRATION
A. Provide systems demonstration.
B. Demonstrate that components except cylinder discharge assembly, are functioning
properly and in conjunction with controls system.
C. Submit integrated step-by-step test procedure for approval 30 days prior to start of
demonstration.
1. Arrange meeting prior to demonstration with representatives of the Owner, the
Owner's Underwriter, and the installer.
2. Perform visual inspection and overall review of system installed.
3. Place minimum of three UL listed recording analyzers in space. Provide
certification that testing devices have been checked by recognized testing
authority within two weeks of date of demonstration.
4. Certify that replacement charge can be provided within 24 hours of
demonstration.
D. Discharge system using manual-release switch mounted on control panel. Run
discharge test with compressed nitrogen at 360 psig (2500 kPa) FM –200 after
discharge, check cylinders for complete pressure release.
E. After satisfactory completion of discharge test, fill cylinders with amount of FM –
200 specified in design calculations.
SECTION 213000
FIRE PUMPS
PART 1 - GENERAL
E. Tests
1. Prior to shipment, the pump and engine shall be thoroughly shop-tested as a
unit by the pump manufacturer. A characteristic curve showing the pump
performance based upon the results of the shop test shall be submitted to the
Engineer prior to shipment, and shall include the performance pump and
engine at the set-governor's speed. Absence of these test reports, indicating
that the complete unit has been tested in the factory by the driver, will be
ample grounds for the equipment rejection.
2. Each control panel shall be fully assembled and factory tested by the control
manufacturer prior to their shipment, and evidence of this test shall be
furnished with the controller.
3. Field Acceptance tests
a. The field acceptance test results shall be as good as the manufacturer's
certified shop test characteristic curve for the pump being tested within
the accuracy limits of the test equipment, the field acceptance test for
fire pumps should be forwarded to Site Engineer for review once the
pumps installed.
b. Overheating: The pump shall operate at peak load conditions without
objectionable heating of the bearings or of the prime mover. The
operating pump speed shall be the speed at which the pumping unit
would be expected to operate during a fire.
c. The engine shall not show signs of overload or stress and its governor
shall properly regulate the speed.
d. Controllers
4. The automatic controller shall be put through not less than ten automatic and
ten manual operations.
5. A running interval of at least five minutes at full speed shall be allowed before
repeating the starting cycle.
6. Automatic operation of the controller shall start the pump from all the
provided starting features, such as pressure switches, valves, etc.
7. Length of Test. The pump shall be in operation not less than one hour (total
time) during the foregoing tests.
2.3 ELETRIC DRIVEN FIRE-PUMP CONTROLLERS
A. Fire-Pump Controllers, General: UL 218 and NFPA 20; listed for electric-drive,
fire-pump service and service entrance; combined automatic and manual operation;
factory assembled and wired; and factory tested for capacities and electrical
characteristics.
1. Rate controllers for scheduled fire-pump horsepower and short-circuit
withstand rating at least equal to short-circuit current available at controller
location. Take into account cable size and distance from substation or supply
transformers.
2. Enclosure: UL 50, Type 2, drip proof, indoor, unless special-purpose
enclosure is indicated. Include manufacturer's standard red paint applied to
factory-assembled and -tested unit before shipping.
3. Controls, devices, alarms, functions, and operations listed in NFPA 20 as
required for drivers and controller types used, and specific items listed.
a. Isolating means and circuit breaker.
b. "Power on" pilot lamp.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
e. The engine shall be an open type self-contained power unit including the
following accessories: -
f. Stub shaft.
g. Fuel pumps and filters.
h. Air Cleaner.
i. Adjustable governor capable of regulating engine speed within a range
of 10 percent between shut-off and maximum load conditions. The
governor shall be set to maintain rated pump speed at maximum pump
load.
j. Lube oil pump.
k. Lube oil filter.
l. Over speed shut down device arranged to shut down engine at a speed
approximately 20 percent above rated engine speed and with manual
reset. The over speed shut down device shall be so supervised that the
automatic engine controller will continue to show an overspeed trouble
signal until the device is manually reset to normal operating position.
m. Electric Starter, generator or alternator and voltage regulator.
n. Dual storage battery units. Each unit shall have capacity to maintain
cranking speed through a 6-minute cycle (15 seconds cranking and 15
seconds rest, in 12 consecutive cycles). Provide certification that the
battery unit complies with this requirement. Batteries shall be furnished
in a dry charge condition, with electrolyte liquid in a separate container.
Electrolyte shall be added at the time the engine is put in service, and
the battery is given a conditioning charge.
o. Dual battery chargers, automatically controlled.
p. Chargers shall be specifically designed for fire pump service.
q. The rectifier shall be a semiconductor type.
r. The charger for a lead acid battery shall be a type which automatically
reduces the charging rate to less than 500 milli-amperes when the
battery reaches a full charge condition.
s. The control equipment incorporated in an "off-on" type of charger for a
load acid battery shall start the rectifier hourly. It shall shut off
automatically when the battery has been fully charged.
t. The battery charger at its rated voltage shall be capable of so delivering
energy into a full discharged battery in such a manner that it will not
damage the battery. It shall restore to the battery 100 percent of the
battery's ampere hour rating within 24 hours.
u. An ammeter with an accuracy of five percent of the normal charging
rate shall be furnished to indicate the operation of the charger.
v. The charger shall be designed so that it will not be damaged or blow
fuses during the cranking cycle of the engine when operated by an
automatic or manual controller.
w. A manual charge switch with indicator light shall be provided or, in lieu
thereof, the charger shall automatically charge at the maximum rate
whenever required by the state of charge of the battery.
x. When not connected through a control panel it shall be arranged to
indicate loss of current output on the load side of the d-c over-current
protective device.
y. Storage batteries shall be substantially supported, secured against
displacement, and located where they shall be readily accessible for
servicing.
z. Engine mounted radiator cooling system (For High Power Engines).
aa. Cooling water shall be from the discharge of the pump, taken off prior to
the pump discharge valve.
bb. Threaded rigid pipe shall be used for this connection. The pipe shall
include a manual shut-off valve, flushing type strainer, pressure
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
2. Separate pilot lamps and a common bell shall be provided to indicate trouble
caused by:-
a. Low oil pressure in the lubrication system. The controller shall provide
means for testing the position of the pressure switch contacts without
causing trouble alarms.
b. Failure of engine to start automatically.
c. Shutdown from over-speed.
d. Battery failure. Each battery shall be provided with separate lamps
which shall be lighted or extinguished on battery failure on attempt to
start.
e. High engine jacket water temperature.
3. Water Pressure Control: A pressure actuated switch having high and low
calibrated adjustments and responsive to water pressure in the fire system
shall be provided in the controller circuit. Suitable provision shall be made for
relieving pressure to the pressure switch to test the operation of the controller
and the pump.
4. Enclosure: The structure or panel shall be securely mounted in an
enclosure(s) which will protect the equipment against mechanical injury and
falling drops of water striking the enclosure from the downward vertical. All
switches required to keep the controller in the "automatic" position shall be
within the locked cabinets having to break glass panels.
5. A wiring diagram shall be provided and permanently attached to the inside of
the enclosure showing exact wiring for the controller, including a legend of
identifying numbers of individual components. All wiring terminals shall be
plainly marked to correspond with the wiring diagram furnished.
6. Wiring Elements: Wiring elements of the controller shall be designed on a
continuous-duty basis.
7. Field Wiring: All wiring leading from the panel to the engine and to the
batteries shall have adequate carrying capacity. Such wiring shall be protected
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
1. Spare parts and tools necessary for two years operation, as recommended by
the manufacturer, shall be provided as a part of the contract for the engine. A
list of these spares shall be included in the offer.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas, concrete bases, and conditions, with Installer present, for
compliance with requirements and other conditions affecting performance of fire
pumps.
B. Examine roughing-in for fire-suppression piping to verify actual locations of piping
connections before fire-pump installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.3 INSTALLATION
A. Install and align fire pump, pressure-maintenance pump, and controller according to
fire protection pumps NFPA 20.
B. Install pumps and controllers to provide access for periodic maintenance including
removal of motors, impellers, couplings, and accessories.
C. Set base-mounting-type pumps on concrete bases. Disconnect coupling halves
before setting. Do not reconnect couplings until alignment operations have been
completed.
1. Support pump baseplate on rectangular metal blocks and shims or on metal
wedges having small taper, at points near anchor bolts, to provide 3/4- to 1-
1/2-inch (19- to 38-mm) gap between pump base and concrete base for
grouting.
2. Adjust metal supports or wedges until pump and driver shafts are level.
Verify that coupling faces and pump suction and discharge flanges are level
and plumb.
D. Install suction and discharge piping equal to or greater than diameter of fire-pump
nozzles.
E. Install valves that are same size as piping connecting fire pumps, bypasses, test
headers, and other piping systems.
F. Install pressure gauges on fire-pump suction and discharge at pressure-gauge
tappings.
G. Support pumps and piping separately so weight of piping does not rest on pumps.
H. Refer to Division 21 Section "Common Work Results for Fire Suppression" for
basic piping installation and joint construction.
I. Install piping accessories, hangers and supports, anchors, valves, meters and gauges,
and equipment supports.
J. Install flowmeters and sensors where indicated. Install flowmeter-system
components and make connections according to manufacturer's written instructions.
2. Flexibility should be provided on the suction and discharge piping on the same
basis as for sprinkler system piping. Flexible couplings are not needed for pipe
penetrations that feed hose headers or relief valve discharge outlets on an
outside wall.
3. Engine Fuel Line Connections. Provide flexibility on fuel line connections to
both the fire pump drivers and the fuel tanks that supply fire pump drivers.
P. Anchorage
1. Provide anchorage for various components as follows: Fire Pump and Driver.
Anchor the base plates for the pump and driver to the pump house floor.
2. Controller. Anchor the controller to the floor and or/wall to prevent damage
due to differential movement. The contractor should make sure that any piping
(such as to a pressure switch) or electrical connections between the controller
and other equipment are not exposed to breakage or separation.
3. Fuel Tanks (Internal Combustion Engines). Anchor a fuel tank to its frame or
directly to the floor and/or wall if floor mounted. The frame should also be
adequately braced to prevent buckling of the legs and also anchored directly to
the floor. Piping connections between the fuel tank and engine should not be
exposed to breakage or separation.
4. Starter Batteries (Internal Combustion Engines). Restrain the battery set and
anchor the battery racks to prevent sliding and/or overturning which could
damage the connection from the battery set to the engine. Battery racks should
be adequately braced to prevent buckling of the legs.
3.4 ALIGNMENT
A. Align fire-pump and driver shafts after complete unit has been leveled on concrete
base, grout has set, and anchor bolts have been tightened.
B. After alignment is correct, tighten anchor bolts evenly. Fill baseplate completely
with grout, with metal blocks and shims or wedges in place. Tighten anchor bolts
after grout has hardened. Check alignment and make required corrections.
C. Align piping connections.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
D. Align pump and driver shafts for angular and parallel alignment according to HI 1.4
and to tolerances specified by manufacturer.
E. Align vertically mounted, split-case pump and driver shafts after complete unit has
been made plumb on concrete base, grout has set, and anchor bolts have been
tightened.
3.5 CONNECTIONS
A. Piping installation requirements are specified in Division 21 Section "Water-Based
Fire-Suppression Systems." Drawings indicate general arrangement of piping,
fittings, and specialties.
B. Install piping adjacent to pumps and equipment to allow service and maintenance.
C. Connect water supply and discharge piping to fire pumps with flexible connectors.
Connect water supply and discharge piping to pressure-maintenance pumps with
flexible connectors. Refer to Division 21 Section "Water-Based Fire-Suppression
Systems" for flexible connectors.
D. Connect relief-valve discharge to point of disposal.
E. Connect flowmeter-system sensors and meters according to manufacturer's written
instructions.
F. Connect controllers to pumps.
G. Connect fire-pump controllers to building fire-alarm system. Refer to Division 28
Section "Fire Detection and Alarm."
H. Ground equipment according to Division 26 Section "Grounding and Bonding for
Electrical Systems."
I. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power
Conductors and Cables."
3.6 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: Engage a factory-authorized service representative to
inspect, test, and adjust field-assembled components and equipment installation,
including connections, and to assist in field testing. Report results in writing.
B. Perform field tests for each fire pump when installation is complete. Comply with
operating instructions and procedures in NFPA 20 to demonstrate compliance with
requirements. Where possible, field correct malfunctioning equipment, and then
retest to demonstrate compliance. Replace equipment that cannot be satisfactorily
corrected or that does not perform as indicated, and then retest to demonstrate
compliance. Verify that each fire pump performs as indicated.
C. Perform the following field tests and inspections and prepare test reports:
1. Leak Test: After installation, charge system and test for leaks. Repair leaks
and retest until no leaks exist.
2. Final Checks before Start-up: Perform the following preventive-maintenance
operations and checks:
a. Lubricate oil-lubrication-type bearings.
b. Remove grease-lubrication-type bearing covers, flush bearings with
kerosene, and clean thoroughly. Fill with new lubricant according to
manufacturer's written instructions.
c. Disconnect coupling and check electric motor for proper rotation.
Rotation shall match direction of rotation marked on pump casing.
d. Verify that pump is free to rotate by hand. If pump is bound or if it
drags even slightly, do not operate until cause of trouble is determined
and corrected.
3. Starting procedure for pumps is as follows:
a. Prime pump by opening suction valve and closing drains, and prepare
pump for operation.
b. Open sealing-liquid supply valves if pump is so fitted.
c. Start motor.
d. Open discharge valve slowly.
e. Observe leakage from stuffing boxes and adjust sealing-liquid valve for
proper flow to ensure lubrication of packing. Do not tighten gland
SECTION 213113
ELECTRICAL DRIVE CENTRIFUGAL FIRE PUMPS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to this
Section.
1.1 SECTION INCLUDES
A. This Section includes electric split-case centrifugal fire pumps
C. Product Certificates: For each type of fire pump and fire-pump controller, signed by
product manufacturer.
D. Source quality-control test reports.
E. Field quality-control test reports.
F. Operation and Maintenance Data: For fire pumps and drivers, pressure-maintenance
pumps, controllers, accessories and specialties, alarm panels, and flowmeter systems
to include in emergency, operation, and maintenance manuals.
1.4 QUALITY ASSURANCE
A. Source Limitations: Obtain fire pumps, pressure-maintenance pumps, and
controllers through one source from a single manufacturer for each type of
equipment.
B. Product Options: Drawings indicate size, profiles, and dimensional requirements of
fire pumps, pressure-maintenance pumps, and controllers and are based on specific
systems indicated. Refer to Division 01 Section "Product Requirements."
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in
NFPA 70, Article 100, by testing agency acceptable to authorities having
jurisdiction, and marked for intended use.
D. Comply with standards of authorities having jurisdiction pertaining to materials,
hose threads, and installation.
E. Comply with NFPA 20, "Stationary Pumps for Fire Protection," for fire pumps,
drivers, controllers, accessories, and their installation.
1.5 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements
apply to product selection:
1. test reports, indicating that the complete unit has been tested in the factory by
the driver, will be ample grounds for the equipment rejection.
2. Each control panel shall be fully assembled and factory tested by the control
manufacturer prior to their shipment, and evidence of this test shall be
furnished with the controller.
3. Field Acceptance tests
2.3 PUMP DRIVERS
A. Description: UL 1004A, NEMA MG 1, totally enclosed, fan cooled, squirrel-cage,
induction - motor. Motor shall comply with Division 21 Section “Common Motor
Requirements for Fire Suppression Equipment”. Include construction complying with
NFPA 20 and NFPA 70, and include wiring compatible with controller used.
1. Finish: Manufacturer's standard red paint applied to factory-assembled and -tested
unit before shipping.
2. Nameplate: Complete with motor horsepower, characteristics, and other pertinent
data.
A. Description: UL 218 and NFPA 20; listed for electric-drive, fire-pump service.
C. Fire pump controller shall be provided with surge arresters in compliance with
IEEE C62.1 or IEEE C62.11 and shall be installed in common mode to
eliminate overvoltage between each phase and earth. As an alternative, the
controller shall withstand without any damage 10 kV impulse in accordance
with IEEE C62.41 or ANSI/UL 1449.
F. Optional Features:
1. Motor-operating condition.
2. Loss-of-line power.
3. Phase reversal.
4. Low-water alarm.
K. Factory Tests: Hydrostatically test and test run fire pumps before shipping
according to UL 448 requirements for "Operation Test" and "Manufacturing and
Production Tests." Test at 150 percent of shutoff head plus suction head, but not
less than 1725 kPa (250 psig). Produce certified test curves and inspection reports
showing head capacity and brake horsepower of each pump.
L. Fire pumps will be considered defective if they do not pass tests and inspections.
2.2 GROUT
compressive strength.
E. PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas, equipment foundations, and conditions, with Installer present, for
compliance with requirements for installation and other conditions affecting fire-
pump performance.
3.3 INSTALLATION
completed.
D. Comply with requirements for vibration isolation and seismic control devices
specified in Section 210548 "Vibration and Seismic Controls for Fire-
Suppression Piping and Equipment."
E. Install suction and discharge piping equal to or greater than diameter of fire-
pump nozzles, and as required by NFPA 20.
F. Install valves that are the same size as piping connecting fire pumps, bypasses,
test headers, and other piping systems.
H. Support pumps and piping separately so weight of piping does not rest on pumps.
3.4 ALIGNMENT
A. Align fire-pump and driver shafts after complete unit has been leveled on
foundation, grout has set, and foundation bolts have been tightened.
B. After alignment is correct, tighten foundation bolts evenly but not too firmly. Fill
baseplate completely with grout, with metal blocks and shims or wedges in place.
Tighten foundation bolts after grout has hardened. Check alignment and make
required corrections.
1. Align pump and driver shafts for angular and parallel alignment according
to HI 1.4.
2. Alignment Tolerances: Comply with manufacturer's written instructions.
D. Align vertically mounted, split-case pump and driver shafts after complete
unit has been made plumb on foundation, grout has set, and foundation bolts
have been tightened. Follow pump manufacturer's written instructions.
3.5 CONNECTIONS
1. Install piping adjacent to fire pumps and equipment to allow service and
maintenance.
2. Connect fire-pump discharge piping to building fire-suppression piping.
3. Connect relief-valve discharge to point of disposal.
F. Ground equipment.
3.6 IDENTIFICATION
1. Leak Test: After installation, charge system and test for leaks. Repair
leaks and retest until no leaks exist.
2. Check suction line connections for tightness so no air gets into pumps.
3. Operational Test: After electrical circuitry has been energized, start units
to confirm proper motor rotation and unit operation. Remove
malfunctioning units, replace with new units, and retest.
4. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
5. Furnish fire hoses in number, size, and length required to reach storm
drain or other acceptable location to dispose of fire-pump test water. Fire
hoses are for field- acceptance tests only and are not property of Employer.
6. Final Checks before Startup: Perform the following preventive-
maintenance operations and checks:
B. Perform field tests for each fire-pump unit and system piping when installation is
complete. Comply with operating instructions and procedures in NFPA 20 to
demonstrate compliance with requirements. Where possible, field correct
malfunctioning equipment, then retest to demonstrate compliance. Replace
equipment that cannot be satisfactorily corrected or that does not perform as
indicated, then retest to demonstrate compliance. Verify that each fire- pump unit
performs as indicated. Report test results in writing.
3.8 DEMONSTRATION
of END OF
SECTION 213113
SECTION 213116
DIESEL DRIVE CENTRIFUGAL FIRE PUMPS
PART 1 - GENERAL
Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to this
Section.
1.1 SECTION INCLUDES
A. This Section includes Diesel centrifugal fire pumps
A. Product Data: For each type of product indicated. Include rated capacities, certified
pump performance curves with each selection point indicated, operating
characteristics, and furnished accessories and specialties for each fire pump and
pressure-maintenance pump.
B. Shop Drawings: For fire pumps and drivers, fire-pump controllers, fire-pump
accessories and specialties, pressure-maintenance pumps, pressure-maintenance-
pump controllers, and pressure-maintenance-pump accessories and specialties.
Include plans, elevations, sections, details, and attachments to other work.
1. For installed products indicated to comply with design loads, include structural
analysis data signed and sealed by the qualified professional engineer responsible for
their preparation.
C. Product Certificates: For each type of fire pump and fire-pump controller, signed by
product manufacturer.
D. Source quality-control test reports.
E. Field quality-control test reports.
F. Operation and Maintenance Data: For fire pumps and drivers, pressure-maintenance
pumps, controllers, accessories and specialties, alarm panels, and flowmeter systems
to include in emergency, operation, and maintenance manuals.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. In other Part 2 articles where titles below introduce lists, the following requirements
apply to product selection:
1. Available Manufacturers: Subject to compliance with requirements, manufacturers
offering products that may be incorporated into the Work include, but are not limited
to, manufacturers specified.
2. Manufacturers: Subject to compliance with requirements, provide products by one of
the manufacturers specified.
2.2 SPLIT – CASE FIRE PUMPS
A. Single-Stage, Horizontally Mounted, Split-Case Fire Pumps: UL 448, factory-
assembled and –tested, as a one package in country of origin (UL listed & FM
approved), diesel-drive, double-suction, horizontal type. Include pump, driver,
controller, etc… mounted on same base and connected with
C. Characteristics: Capable of furnishing not less than 150 percent of rated capacity at
not less than 65 percent of total rated head. Shutoff head is limited to 140 percent of
total rated head.
D. Casing: Axially split cast iron with suction and discharge flanges machined to
ASME B16.1, Class 125 dimensions, unless Class 250 flanges are indicated.
E. Impeller: Cast bronze of construction to match fire pump, statically and dynamically
balanced, and keyed to shaft
F. Wear Rings: Replaceable, bronze.
G. Shaft and Sleeve: Steel shaft with bronze sleeve.
H. Driver: Diesel engine.
I. Coupling: Flexible and capable of absorbing torsional vibration and shaft
misalignment. Include metal coupling guard.
J. Finish: Manufacturer's standard red paint applied to factory-assembled and -tested
units before shipping
K. Nameplates: Complete with capacities, characteristics, and other pertinent data.
floor legs, direct-reading level gage, and secondary containment tank with capacity at
least equal to fuel storage tank.
11. Exhaust System: ASTM A 53, Type E or S, Schedule 40, black steel pipe;
ASME B16.9, weld-type pipe fittings; ASME B16.5, steel flanges; and
ASME B16.21, nonmetallic gaskets. Fabricate double-wall, ventilated thimble from
steel pipe.
A. Description: UL 218 and NFPA 20; listed for diesel-drive, fire-pump service.
Include the following:
NFPA 1963 hose thread that complies with local fire department standards and finish
same as for test-header-manifold escutcheon plate.
8. Ball Drip Valve: UL 1726.
9. Main Relief Valve: UL 1478, pilot operated.
10. Main Relief Valve: UL 1478, spring loaded.
11. Discharge Cone: Closed.
12. Discharge Cone: Open.
13. Finish: Manufacturer's standard factory-applied red paint, unless brass or other finish
is specified.
14. Pressure Sensing Line:
a. A completely separate pressure sensing line shall be provided for each fire
pump and for the jockey pump. The sensing line shall be arranged in accordance with
Figure A-7-5.2.1. of NFPA 20. The sensing line shall be 15mm H58 brass tubing
complying with ASTM B 135M.
b. The sensing line shall be equipped with 2 restrictive orifice unions each. Restricted
orifice unions shall be ground-face unions with brass restricted diaphragms drilled for
2.4 mm. Restricted orifice unions shall be mounted in the horizontal position, not less
than 1.5 m apart on the sensing line.
c. 2 test connections shall be provided for each sensing line. Test connections
shall consist of 2 brass 15 mm globe valves and 8 mm gage connection tee
arranged per NFPA 20. One of the test connections shall be equipped with a 0
to 1380 kPa water oil-filled gage.
d. Sensing line shall be connected to the pump discharge piping between the
discharge piping control valve and the check valve.
2.9 PRESSURE-MAINTENANCE-PUMP SPECIALTIES AND ACCESSORIES
A. Match pressure-maintenance-pump suction and discharge ratings as required for
pump
capacity rating. Include the following:
1. Engine running.
2. Main switch off or in manual position.
3. Engine trouble.
4. Low-water alarm.
5. Low fuel.
2.14 GROUT
A. Description: ASTM C 1107, Grade B, factory-mixed and -packaged, nonshrink and
nonmetallic grout; suitable for interior and exterior applications.
B. Characteristics: Post-hardening, volume-adjusting, dry, hydraulic-cement grout.
C. Properties: Nonstaining, noncorrosive, and nongaseous.
D. Design Mix: 34.5 MPa, 28 day compressive strength
PART 3 - EXECUTION
3.1 EXAMINATION
A- Examine areas, equipment foundations, and conditions, with the Installer present, for
compliance with requirements for installation and other conditions affecting fire-
pump
performance.
1. Proceed with installation only after unsatisfactory conditions have been corrected.
3.3 INSTALLATION
A- Comply with fire-pump, pressure-maintenance-pump, and controller manufacturers'
written installation and alignment instructions, and with NFPA 20.
B- Install pumps and controllers to provide access for periodic maintenance, including
removal of drivers, impellers, couplings, and accessories.
C- Set base-mounting-type pumps on concrete bases. Disconnect coupling halves before
setting. Do not reconnect couplings until alignment operations have been completed.
1. Support pump baseplate on rectangular metal blocks and shims or on metal wedges
having small taper, at points near foundation bolts to provide 19 to 38 mm gap
between pump base and foundation for grouting.
2. Adjust metal supports or wedges until pump and driver shafts are level. Check
coupling faces and pump suction and discharge flanges to verify that they are level
and plumb.
D- Install suction and discharge piping equal to or greater than diameter of fire-pump
nozzles.
E- Install valves that are the same size as piping connecting fire pumps, bypasses, test
headers, and other piping systems.
F- Install pressure gages on fire-pump suction and discharge at pressure-gage tappings.
G- Support pumps and piping separately so weight of piping does not rest on pumps.
H- Install piping accessories, hangers and supports, anchors, valves, meters and gages, and
equipment supports.
I- Refer to Division 15 Section "Basic Mechanical Materials and Methods" for basic piping
installation and joint construction.
J- Install water supply and drain piping for diesel-engine heat exchangers. Extend drain
piping from heat exchangers to point of disposition.
K- Install exhaust system piping for diesel engines. Extend to point of termination outside
structure. Install pipe and fittings with welded joints, and components having flanged
connections with gasketed joints.
L- Install condensate drain piping for diesel-engine exhaust system. Extend drain piping
from low points of exhaust system to condensate traps and to point of disposition.
M- Install flow meters and sensors where indicated. Install flow-measuring system
components and make connections according to manufacturer's written instructions.
N- Electrical Wiring: Install electrical devices furnished by equipment manufacturers but
not
specified to be factory mounted. Furnish copies of manufacturers' wiring diagram
Submittals to the electrical Installer.
3.4 ALIGNMENT
A- Align fire-pump and driver shafts after complete unit has been leveled on foundation,
grout has set, and foundation bolts have been tightened.
B- After alignment is correct, tighten foundation bolts evenly but not too firmly. Fill
baseplate completely with grout, with metal blocks and shims or wedges in place.
Tighten foundation bolts after grout has hardened. Check alignment and make
required corrections.
C- Make piping connections, check alignment, and make required corrections.
1. Adjust alignment of pump and driver shafts for angular and parallel alignment by one
method in HI 1.1-1.5, Section 1.4, "Installation, Operation and Maintenance."
2. Alignment Tolerances: Comply with manufacturer's written instructions.
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
3.5 CONNECTIONS
A- Piping installation requirements are specified in other Division 13 Sections. Drawings
indicate general arrangement of piping and specialties. The following are specific
connection requirements:
1. Install piping adjacent to fire and pressure-maintenance pumps to allow service and
maintenance.
2. Connect water supply to fire and pressure-maintenance pumps.
3. Connect fire-pump and pressure-maintenance-pump discharge piping to building fire
suppression piping.
4. Connect relief-valve discharge to point of disposal.
5. Connect cooling-system water supply and drain piping to diesel-engine heat
exchangers.
6. Connect exhaust system piping to diesel engines.
B- Perform field tests for each fire-pump unit and system piping when installation is
complete. Comply with operating instructions and procedures in NFPA 20 to
demonstrate compliance with requirements. Where possible, field correct
malfunctioning equipment, then retest to demonstrate compliance. Replace
equipment that cannot be satisfactorily corrected or that does not perform as
indicated, then retest to demonstrate compliance. Verify that each fire pump unit
performs as indicated. Report test results in writing
3.7 DEMONSTRATION
A- Engage a factory-authorized service representative to train the Employer's
maintenance
personnel to adjust, operate, and maintain fire pumps. Refer to Division 1 Section
"[Demonstration and Training] [Closeout Procedures]."
SECTION 213400
PRESSURE-MAINTENANCE PUMPS
PART 1 - GENERAL
DIVISION 21 – FIRE SUPPRESSION
EVER PROJECT,
CLUB HOUSE BUILDING
1.2 SUMMARY
A. Section Includes:
1.3 DEFINITIONS
B. Pump Equipment, Accessory, and Specialty Pressure Rating: 175 psig (1200
kPa) minimum unless higher pressure rating is indicated.
A. Product Data: For each type of product indicated. Include rated capacities,
operating characteristics, performance curves, electrical characteristics, and
furnished specialties and accessories.
A. Operation and Maintenance Data: For each pressure maintenance pump unit to
include in operation and maintenance manuals specified in Division 1.
G. Comply with NFPA 20, "Installation of Stationary Pumps for Fire Protection," for
pressure maintenance pumps, drivers, controllers, accessories, and installation.
1.9 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
B. Retain shipping flange protective covers and protective coatings during storage.
C. Protect bearings and couplings against damage from sand, grit, or other foreign
matter.
1.11 WARRANTY
7. Making good and installation and finishing all items that are disturbed and that
may be required due to repair or replacement of defective items. Coordinate with
Employer, manufacturer, and installer of adjacent disturbed items to ensure that
their warranty is not cancelled due to the repair work.
A. Furnish extra materials described below, that match products installed and that are
packaged with protective covering for storage and identified with labels describing
contents.
B. Pump Construction:
stationary seat.
7. Intermediate Chamber Bearings: Aluminum-oxide ceramic or bronze.
8. Chamber-Base Bearing: Tungsten carbide.
9. O-Rings: EPDM or NBR.
C. Motor: Single speed with permanently lubricated ball bearings and rigidly
mounted to pump head. Comply with requirements in Division 21 Section
"Common Motor Requirements for Fire Suppression Equipment."
1. Working Pressure: 175-psig (1200 kPa) minimum, 350 psig (2070 kPa)
2.2 MOTORS
2.5 GROUT
1. Operational Test: After electrical circuitry has been energized, start units to
confirm proper motor rotation and unit operation.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning
controls and equipment.
3.3 ADJUSTING