All sheets of drawing submitted must properly indicate the store name, shop number, nature of
occupancy/operation (e.g. boutique, men’s shoe store, restaurant, etc.) specified location (ground, second, third,
fourth fifth floor) is a key plan.
All working drawings must be properly located, arranged and stapled on the upper, middle and lower left side of
each set of drawings. This is to enable the Engineering group to immediately: 1.) Establish the number of sets of
drawings 2.) Determines how many sheets per set have been submitted and 3.) Ensure that no sheets are detached
from the set so as to avoid misplaced drawings/sheet.
`
The Lessee shall submit to Gaisano Grand Group of Companies Engineering Department/ (GGGCED) the following
for approval:
Colored perspective in a 15in. x 20in. illustration board showing the store frontage.
Final Plans – five (5) complete sets (after approval of colored perspective)
Architectural Plans and Drawing (scale 1:50m)
a. A plan showing the location of Lessee’s store
b. Floor Plan
c. Longitudinal and cross section (if applicable)
d. Four (4) elevations (if applicable)
e. Reflected ceiling plan
f. Structural details and location of wall partitions
g. The location of furniture and furnishings fixed and movable
h. Location of heavy equipment, its weight, loading and dimensions, specification (if applicable)
i. Signage details
Structural Plans and Drawings (if necessary)
a. Design and computations duly certified by licensed Structural and Civil engineer
b. Certification of the Gaisano Grand Mall Structural Engineer that the project will not affect the
structural integrity of the Gaisano Grand building
c. Specifications
d. Floor framing plan
Plumbing Plans and Drawings
a. Design and specifications
b. Isometric drawings
c. Drainage systems/vent (indicated, if any, existing floor clean out)
d. Cold water line system
Mechanical Plans and Drawings
a. Air conditioning plan
b. Air ductworks system of air conditioning
c. Piping lay out
d. Kitchen ventilation system (if applicable)
e. Air ductworks system of the kitchen ventilation
f. Specification of the above
g. LPG lay out (if applicable)
h. Piping lay out
i. Isometric drawings
j. Fire protection system including smoke detectors, sprinklers and fire extinguishers
Page 2 of 8
Pre-Construction Guidelines
Updated 2June2018
10. CONSTRUCTION BOND – The lessee shall deposit with the Mall Management a Construction Bond equivalent to one (1) month rental to
answer for all violations or non-compliance with any guidelines and requirement or deviation from approved plans.
11. OTHER REQUIREMENTS – The following additional requirements must be submitted to Mall Management.
11.1 List of workers/ Authorized signatories during construction( forms attached) (2 copies)
11.2 Worker’s Ids – the lessee shall provide ID cards to their workers. Said ID cards shall be sign by the lessee and counter signed
by the Mall Manager. The Id’s must be properly filled up and sealed to avoid tampering. This should be worn at all times
within the construction site.
11. NOTICE TO PROCEED – This is the written notice from the Mall Management signifying the go signal to start the construction. A copy of
Notice to Proceed must be posted in front of the board ups.
A. STANDARD GUIDELINES FOR CONDUCTING LEASE REMEASUREMENT (LR) IN ALL RETAIL SPACES AT GAISANO GRAND MALLS
I. GENERAL PROCEDURE
1. Present in the day of Lease Re measurement is Lessee or his/her duly authorized Lessee Representatives and the Lessor or
his/her duly authorized representative. Re measurement shall not begin if any one of the aforementioned parties is absent.
2. The Resident Mall Engineer/ Engineering Representative shall proceed to get dimensions of the perimeter walls and witnessed
by the lessee and specified hereafter. All dimensions shall be indicated in the plan.
3. Once the lease remeasurement exercise is completed, all Representatives shall affix their signatures on the plan as witnesses and
accomplish the acceptance of space form.
4. The lessee is given a period of five-(5) working days receipt of the Drawing from Gaisano Grand Group of Companies Engineering
to contest the validity of the floor area presented. Absolutely no complaints regarding the plan and floor area shall be entertained
after this period.
e. Janitorial rooms/closets
f. Other rooms not actually available to the tenant for his furnishing and personnel & enclosing walls of such
rooms
2.2 Toilet rooms within and exclusively serving only that floor shall be measured from the outside finish of the toilet walls.
2.3 No deductions shall be made from columns and projections necessary to the building.
10.1 One (1) unit – 10 lbs. ABC type Fire extinguisher with gage must be provided for every fifty (50) square meter area. An
extinguisher must be provided and a fire watch must be assigned where welding and/or gas-cutting operations are
performed. When sprinkler relocation is performed, extra fire safety measures must be done. The fire extinguisher
must be ready and there should be one assigned by contractor as Fire watch. The Fire watch person must be present
until the sprinkler relocation has been finished and until the sprinkler pipes have been loaded and tested.
10.2 Smoking and cooking are strictly prohibited within the construction site.
10.3 Water supply and distribution facilities for fire fighting purpose shall be provided and maintained in the construction
site in accordance with the Local Fire Code.
10.4 In the event that there is a need to perform welding works, the tenant or his contractor shall secure from Mall
Engineering a Hot Works Permit. Welding Works shall be allowed only after mall hours.
10.5 Spray Painting shall not be allowed.
11. PROHIBITIONS
The following are strictly prohibited at all Gaisano Grand Group properties:
1. People under the influence of drugs, liquors of or other intoxicating beverage.
2. Gambling
3. Persons who are not properly attired.
4. Persons carrying pets or animals, except for mall’s animal shop personnel authorized to handle animals.
5. Persons riding in bicycles or any other form of carriages, except strollers or wheelchairs.
6. Lunch caterers for the lessee, lessee’s employee or third party.
7. Persons distributing pamphlets or promotional material without the consent of Mall Management.
8. Ambulant peddlers and vendors
9. Persons taking movies or photographs of Gaisano Grand Malls.
10. Loitering and littering
11. Smoking inside the leased area.
12. Public disturbance (shouting, use of indecent words)
Page 5 of 8
Pre-Construction Guidelines
Updated 2June2018
h. Lighted signage intended for overnight lighting shall be controlled by a switch placed outside the Leased area and accessible to
mall night personnel.
3. FLOORING
a. The finished floor elevation at the premises entrance must exactly the finished floor elevation of the mall.
b. The structural system of GAISANO MALL BUILDING has been designed to carry a live load of 100 pounds per square foot. The
tenant should not exceed the requirement.
c. Channeling or cutting of structural slab shall not be permitted. Coring of the slab shall be permitted subject to Mall management’s
prior written approval of core size and location.
d. If, in the opinion of Management, it is likely the floor of the leased area will be exposed to liquids, either accidentally or for
cleaning purposes. Lessee shall provide adequate waterproofing protection beneath the finish flooring.
e. If the area to be leased has existing floor tiles, the lessee shall replaced the existing floor tiles with new tiles
4. CEILING
a. Cleaning works shall include all works related to ceiling treatment including light coves, hung curtain walls, suspended ceiling,
acoustical treatment, ornamental specialties and other related items.
b. The minimum height of the ceiling is 3.00 m. However for malls with floor to floor height of 3.00 m and below, the minimum
allowable height shall be agreed upon by the tenant and the respective branch engineering and leasing departments.
c. Provision of the ceiling system shall be at lessee’s discretion. Non-combustible material is required. All drop ceiling must be
provided with additional sprinkler heads (pendent type); all cost for such shall be to the lessee’s account.
5. MATERIAL FOR INTERIOR FINISH
a. Only new, first class materials, equipment, fixtures (including trade fixtures) and furnishings shall be used in the leased area.
b. All finishes shall have a minimum Class I Flame spread rating or have a Fire Retardant Treatment.
c. All existing partition shall not be removed or replaced.
d. The Lessee shall provide independent wall partition attached to the existing.
6. KITCHEN
a. Provide firebricks/insulation on all cooking batteries.
b. The tenant shall provide exhaust hood with exhaust fan at every cooking equipment/outlet with six (6”) hood allowances from the
edge of the cooking equipment duly approved by the GGGCED. For every exhaust duct to a kitchen outlet, the corresponding fresh
air duct should be provided. Exhaust duct shall be made of BI Sheet. The Tenant shall provide both fresh air supply and exhaust air
ducts to be tapped to Gaisano Grand Mall fresh air supply and exhaust air duct preparation .In the absence of such in a Gaisano
Grand Mall branch, the Tenant will provide fresh air supply and exhaust air duct and blowers for the leased area.
c. No high-pressure burners are allowed inside the mall.
d. No plastic/rubber hose connections at the gas line.
e. No LPG tanks and flammables.
f. Tenant should install gas leak detector and automatic fire extinguisher in their outlet.
7. OTHERS
a. Roll-up door shall be provided with peep holes. All rollup door mechanism should be within the leased premises.
b. Entrance door is must be frameless 1/2in. thick clear glass. Glass transom above the door entrance is not allowed.
c. Any alterations. Additions, reinforcement or modification to owner’s structure, piping conduit or ductworks to accommodate.
Lessee’s works shall not be performed without in each instance obtaining owner’s structure as strong as or stronger than original
design and with the finishes unimpaired. Owner may require that the owner’s contractor under contract perform the approved
Structural or Mechanical or Electrical modifications with Tenant at Tenant’s expense. MALL MANAGEMENT MAY FURTHER
REQUIRE AN ENGINEERING ANALYSIS; THE MALL’S ENGINEER MAY PERFORM REVIEW OR EVALUATION OF THE DESIGN AT
TENANT’S EXPENSE.
d. Tenant shall provide facilities to enhance the mobility of the Disabled within the premises as may be required by the owner or by
the governmental authority having jurisdiction over the premises.
e. Any damage caused to the wall, floor or ceiling finishes and or accessories beyond Lessee’s Lease Line that has been duly
established as a result of lessee construction activities shall be repaired and restored immediately by the lessee deemed
responsible at his/their own expense charged to his/their account.
n. Load balancing. For Three phase lines, all lines should have balance load with variance of not more than ± 5
amperes among the three lines
o. There shall be no open wiring.
p. Multiple tapping to an extension cord is not allowed.
5. All junction boxes or pull boxes shall be covered with metal plates supplied along with boxes.
6. Neon light signage installation:
a. Neon sign transformer or its terminals shall be metal enclosed and ventilated. Transformer shall be located near
the neon tubes.
b. Transformer shall be placed in a well-ventilated location, which is far from combustible materials,
c. Wire connection to neon tubes shall be properly insulated.
d. Material backing on the signage band for neon light shall be non - Combustible.
7. All telephone provision shall be for the account of the lessee.
8. Lessee shall provide feederline from leased area to electrical room. Wiring from the Meter Room to the leased area should
pass through the Electrical Conduit/Pipe preparation of Gaisano Grand for that leased area.
9. Lessee shall provide sending end and receiving end circuit breaker. Sending End Breaker shall be placed before the meter.
10. Lessor shall provide the kilowatt-hour meter (brand GE or its approved equivalent) with certificate of calibration from local
electric company or the ERC which shall be to the account of the Lessee.
11. Flat cords, BX wires, flexible conduits are not allowed.
12. All wiring shall be done in intermediate metal conduits RSC or PVC conduits. PVC conduit strand shall conform to
GGED approved
brands.
13. Use mica-tubing insulation for wires with maximum length of 0.30m or 12”
14. Use existing ¾” diameter conduit pipe for OMRON cash register.
15. Prior to the installation of electrical works, the tenant shall submit to GGGCED the complete set of electrical plan scaled
and signed by a duly licensed professional electrical engineer.
16. All electrical installations shall be under direct supervision of a Registered Electrical Engineer or Registered Master
Electrician. Only accredited electrical contractors shall be allowed to do electrical works of the Leased area. Should the
Tenant prefer his/her own contractor, the contractor must secure accreditation from GGGCED.
D. SANITARY/PLUMBING
1. The design and installation of all sanitary and plumbing works shall be done in accordance with the National Plumbing Code
of the Philippines, Pertinent Philippine Laws and Ordinances of the City.
2. Verify on site existing stub-out provision prior to Plan Preparation.
3. Plumbing Plan
a. Design and specification
b. Isometric drawings (sewer and cold water line)
c. Sewer and cold water line layout showing existing sewer and cold water line provision.
d. Floor drain location
4. Plans, layouts, design computation, technical specification, isometric view should be signed and sealed by the Master
Plumber.
5. All pipe size should be reflected in the plan.
6. Use G.I. sheet. Sch.40 pipes for cold water line, cast iron for sewer line using steam washing and PVC pipe for ordinary sewer
line.
7. Provide five (5) gpm. Capacity for stainless grease trap for every kitchen sink.
8. Provide clean out for every change in direction and every three (3) length of pipe.
9. Provide standard clamp hangers for cold water and sewer line under slab for every three (3) meters.
10. No comfort rooms or showers shall be allowed in areas without sanitary and water line preparation. No septic tank shall be
allowed inside the mall premises.
11. All sinks, toilet, kitchen and lavatory areas should be waterproof.
12. Supply valve be located in the areas controlled by the lessor for emergency purposes.
13. Only one tapping point per tenant shall be allowed. Check stub out provision in lessee’s area.
14. Tapping of cold water and sewer line shall be done by the lessor chargeable to the lessee including supply valve and water
meter.
15. Tenant’s requiring more volume of water than that of the lessor’s provision shall install additional water line tap to
appropriate existing main. A written request indicating the requirement shall be submitted to GGGCED for its
review/approval. GGGCED reserves the right to reject or disapprove any application without prejudice to any contract
agreement between the lessor and the lessee.
16. All water meters shall be provided by the Lessor to the account of the Lessee The Water Meter shall be “EVER” ½ inch –
diameter and shall be calibrated by the local water utility or government agency authorized to calibrate water meters..
17. Only accredited contractors are allowed to do all the sanitary and plumbing works inside the leased areas. Should the Tenant
prefer his/her own contractor, the contractor must secure accreditation from GGGCED.
DEFINITION OF TERMS
NOTICE OF AWARD - This is the formal communication from the GAISANO GRAND GROUP OF COMPANIES informing the prospective LESSEE of the
acceptance of his application and indicating basic information, terms and conditions of the Lessor and Lessee. A copy of the Notice of Award with
the lessee’s confirmation must be returned to the Leasing Department.
CONTRACT OF LEASE – This is the legal instrument between GAISANO GRAND GROUP and the lessee formally detailing all the terms and conditions
that govern the lease. The specified number of copies of the signed contract must be returned to the Leasing Department upon contract signing.
REVISIONS TO CONSTRUCTION GUIDELINES – THE MALL MANAGEMENT reserves the right to revise or add to the above guidelines. Copies of any
revisions made shall be distributed to the lessee.
CONFORME: