Professional Documents
Culture Documents
An ACI Standard
@Seismicisolation
@Seismicisolation
Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2021-06-18 19:22:05 +0000 by
No further reproduction or distribution is permitted.
First Printing
September 2019
ISBN: 978-1-64195-082-4
Requirements for Design of a Special Unbonded Post-Tensioned Precast Shear Wall Satisfying ACI
550.6 (ACI 550.7) and Commentary
Copyright by the American Concrete Institute, Farmington Hills, MI. All rights reserved. This material
may not be reproduced or copied, in whole or part, in any printed, mechanical, electronic, film, or other
distribution and storage media, without the written consent of ACI.
The technical committees responsible for ACI committee reports and standards strive to avoid
ambiguities, omissions, and errors in these documents. In spite of these efforts, the users of ACI
documents occasionally find information or requirements that may be subject to more than one
interpretation or may be incomplete or incorrect. Users who have suggestions for the improvement of
ACI documents are requested to contact ACI via the errata website at http://concrete.org/Publications/
DocumentErrata.aspx. Proper use of this document includes periodically checking for errata for the most
up-to-date revisions.
ACI committee documents are intended for the use of individuals who are competent to evaluate the
significance and limitations of its content and recommendations and who will accept responsibility for
the application of the material it contains. Individuals who use this publication in any way assume all
risk and accept total responsibility for the application and use of this information.
All information in this publication is provided “as is” without warranty of any kind, either express or
implied, including but not limited to, the implied warranties of merchantability, fitness for a particular
purpose or non-infringement.
ACI and its members disclaim liability for damages of any kind, including any special, indirect, incidental,
or consequential damages, including without limitation, lost revenues or lost profits, which may result
from the use of this publication.
It is the responsibility of the user of this document to establish health and safety practices appropriate
Participation by governmental representatives in the work of the American Concrete Institute and in
the development of Institute standards does not constitute governmental endorsement of ACI or the
standards that it develops.
Order information: ACI documents are available in print, by download, through electronic subscription,
or reprint, and may be obtained by contacting ACI.
ACI codes, specifications, and practices are made available in the ACI Collection of Concrete Codes,
Specifications, and Practices. The online subscription to the ACI Collection is always updated, and
includes current and historical versions of ACI’s codes and specifications (in both inch-pound and SI
units) plus new titles as they are published. The ACI Collection is also available as an eight-volume set of
books and a USB drive.
Charles W. Dolan
Chair
Consulting member
S. K. Ghosh
This standard defines procedures that may be used to design special 2. Individual walls, including considerations to ensure ductility,
precast concrete shear walls, coupled or uncoupled, composed of energy dissipation, integrity, stiffness, and strength; and
discretely jointed precast panels that are vertically post-tensioned to the 3. Coupled walls, including considerations of the roles of the post-
foundation with unbonded tendons. Such walls are suitable for use in tensioning tendons and coupling devices in providing energy dissipation,
regions of high seismicity and for structures assigned to high seismic and strength and stiffness for coupled walls greater than the sum of those
design categories. After a major seismic event, these walls can be expected provided by the coupled walls acting as separate units.
to exhibit minimal damage in the flexural hinging region at the base of the The Commentary references documentary evidence, additional to the
wall as well as negligible permanent displacements. Such walls do not references of ACI 550.6 and Chapter 18 of ACI 318R-14, that supports these
satisfy the prescriptive requirements of Chapter 18 of ACI 318-14 for shear Design Requirements. In this standard, however, no comparison is made
walls of monolithic construction. According to 18.2.1.7 of ACI 318-14, their between the performance of precast test modules satisfying the prescriptive
acceptance requires demonstration by experimental evidence and analysis requirements of ACI 318 and modules satisfying these Design Require-
ACI Committee Reports, Guides, Manuals, Standard Keywords: coupling devices; drift angle; energy dissipation; lateral resis-
Practices, and Commentaries are intended for guidance in tance; post-tensioning; precast concrete; prestressed concrete; seismic
planning, designing, executing, and inspecting construction. design; special shear wall; test module; toughness.
This document is intended for the use of individuals who are
competent to evaluate the significance and limitations of its
content and recommendations and who will accept CONTENTS
responsibility for the application of the material it contains. Chapter 1—General, p. 2
The American Concrete Institute disclaims any and all 1.1—Introduction
responsibility for the stated principles. The Institute shall not
be liable for any loss or damage arising therefrom.
ACI 550.7-19 supersedes ITG-5.2-09, was adopted May 4, 2009, and published
Reference to this document shall not be made in contract September 2019.
documents. If items found in this document are desired by the Copyright © 2019, American Concrete Institute.
Architect/Engineer to be a part of the contract documents, they All rights reserved including rights of reproduction and use in any form or by any
shall be restated in mandatory language for incorporation by means, including the making of copies by any photo process, or by electronic or
mechanical device, printed, written, or oral, or recording for sound or visual reproduction
the Architect/Engineer. or for use in any knowledge or retrieval system or device, unless permission in writing
is obtained from the copyright proprietors.
@Seismicisolation
@Seismicisolation
1
Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2021-06-18 19:22:05 +0000 by
No further reproduction or distribution is permitted.
2 DESIGN REQUIREMENTS OF SHEAR WALL SATISFYING ACI 550.6 (ACI 550.7-19)
most precast panel of the wall and the foundation and with damage during a DBE event is limited in extent, confined
the sets located symmetrically about the vertical centerline essentially to the wall to foundation joint filler material or to
of the wall; or the concrete cover over the boundary element reinforcement
(d) For coupled walls, energy-dissipating coupling devices at the wall toes, and can be readily repaired after the earth-
for a given vertical joint between coupled walls, of equal quake. By contrast, monolithic walls, coupled and uncou-
strength, at least two in number for each coupled edge of a pled, designed to Chapter 18 of ACI 318, can suffer
panel in the wall, and positioned so that the width of the significant cracking, crushing, and spalling in the plastic
vertical joint between panels remains approximately hinging regions at the base of the walls, in the coupling
constant in width as the walls rock on their bases. beams, or both, and repair can be costly. Further, mono-
lithic special shear walls designed to Chapter 18 of ACI 318
R1.1 may show permanent lateral deformations following a DBE
Large-scale laboratory experiments (Bora et al. 2007; event whereas the special shear walls described in this stan-
Perez et al. 2003; Priestley et al. 1999; Rahman and dard should not.
Restrepo 2000; Santana 2005) have shown that unbonded Precast shear walls with the following can be propor-
post-tensioned precast concrete cantilever shear walls can tioned to have performance characteristics similar to the
provide safety and serviceability levels, during and after an walls described in this standard:
earthquake, that meet or exceed performance levels required 1. Unbonded tendons that cross the wall-foundation inter-
by 18.2.1.7 of ACI 318 and ACI 550.6. Analytical studies face at locations along the length of the wall that are more
(Kurama 2002; Perez et al. 2004a,b; Rahman and Restrepo than 10% of the wall length from its vertical centerline; or
2000; Stanton and Nakaki 2002; Thomas and Sritharan 2. Uncoupled walls with energy dissipation devices having
2004; Sritharan et al. 2007) have shown that to achieve such characteristics differing from those for the energy-dissi-
performance levels, the shear walls should be proportioned pating reinforcement described in Section 1.1(c) and posi-
and detailed in accordance with specific considerations. tioned differently along the length of the wall; or
This standard is developed from the aforementioned studies 3. Coupled walls with coupling elements connecting
and related references. This standard contains the minimum vertical boundaries of adjacent walls and having character-
requirements for ensuring that one type of unbonded post- istics for the coupling elements differing from those for the
tensioned precast concrete cantilever shear wall system, coupling devices described in Section 1.1(d).
uncoupled or coupled, can sustain a series of oscillations into Research investigations additional to those completed to
the inelastic range of response without critical decay in strength date, and modifications of the procedures described in this
or excessive story drifts. Further, that shear wall should show standard, however, are needed before prescriptive provisions
only minimal or no damage to the wall, and minimal or no for the design of such precast shear walls can be formulated.
permanent displacements after the oscillations cease.
In this specific type of coupled or uncoupled wall system, the 1.2—Scope
compared with the uncoupled wall of Fig. R1.1(a)), blockouts ances associated with installation. For the post-tensioning
may need to be provided on the line of the tendons and at the tendon, essential elements are how and where the tendon
bottom of each panel for the location of access to couplers will be anchored and, if appropriate, coupled, and how it
for the prestressing tendons. will be assured that the tendon remains debonded during the
grouting of the joint between the wall and the foundation and
1.2.3 All precast and reinforced concrete components and during any grouting of joints between wall panels.
systems for the shear wall, energy dissipation and coupling
devices, and associated gravity load systems, shall be CHAPTER 2—NOTATION AND DEFINITIONS
designed to satisfy the requirements of ACI 318 except as 2.1—Notation
modified by this standard. Aps = area of post-tensioning tendons crossing wall-
foundation interface, in.2 (mm2)
1.2.4 All precast, prestressed, and reinforced concrete As = area of energy-dissipating reinforcement crossing
components and systems for the shear wall system, including wall-foundation interface, in.2 (mm2)
energy dissipation and coupling devices and associated a = depth of equivalent rectangular stress block for
gravity load systems, shall meet the quality assurance confined concrete, in. (mm)
requirements of Appendix 11A of ASCE/SEI 7. Require- asc = radius of 180-degree bend for connecting link
ments of Sections 11A.1.3.2, 11A.1.3.3, and 11A.1.3.4 shall measured to its inside face, in. (mm)
apply for any shear wall panel element constructed on or off b sc = width of connecting link bar, in. (mm)
site, for assembly and post-tensioning operations on site, and C = compression force on toe of wall when probable
for construction and installation of coupling devices. flexural strength Mpr acts at wall-foundation
R1.2.4 For the shear wall systems described in this stan- interface, lb (N)
dard to be accepted as special shear wall systems defined by c = distance from extreme compression fiber of grout
ASCE/SEI 7, the periodic special and continuous special pad to neutral axis of wall at wall-foundation
inspection requirements during steel placement, welding interface, in. (mm)
operations, grouting, and concrete placement need to be Dc = self-weight of wall plus any dead loads acting on
properly executed by personnel who are qualified to perform it, including the self-weight of components
the work and such inspection should be specified in the directly attached to the wall, lb (N)
contract documents. d b = bar diameter of energy-dissipating reinforcement,
in. (mm)
1.3—Drawings dsc = distance center to center of prongs of connecting
Drawings of the shear walls and associated framing shall link of U-shaped flexure plate (UFP) coupling
show all features of the work, including those details essential device, in. (mm); refer to Fig. R7.1
for satisfactory seismic performance of the wall system, E = load effects of earthquakes or related internal
ASCE/SEI
ASCE 7-05 Minimum Design Loads for Buildings and
Other Structures (ASCE/SEI 7-05)—Seismic
Provisions
ASTM International
A240/A240M-04 Standard Specification for Chromium
and Chromium-Nickel Stainless Steel
Plate, Sheet, and Strip for Pressure
Vessels and for General Applications
A615-07 Standard Specification for Deformed
and Plain Carbon-Steel Bars for
Fig. R4.1—Typical stress-strain relationship for energy-
Concrete Reinforcement dissipating reinforcement.
A706/A706M-04 Standard Specification for Low-Alloy
Steel Deformed and Plain Bars for
Concrete Reinforcement minimum tensile strength fu. The strain εu at the tensile
A955/A955M-07a Standard Specification for Deformed strength shall be taken as a strain 0.02 less than the strain at
and Plain Stainless-Steel Bars for the minimum elongation specified in ASTM A706 for the
Concrete Reinforcement given bar size. Stress-strain properties of energy-dissipating
C1107/C1107M-97 Standard Specification for Packaged Dry, reinforcement for each bar size used for the wall system shall
Hydraulic-Cement Grout (Nonshrink) be obtained from tension tests as specified in ASTM A706.
The average strain εu of reinforcement at its average tensile
CHAPTER 4—MATERIALS strength fu shall be obtained. Averages shall be based on the
4.1—General results of a minimum of three tension tests for each bar size
All materials and material tests shall conform to the for every steel heat used in the wall system.
requirements of ACI 318, except as specified in this standard. R4.3.2 Stress-strain properties of the energy-dissipating
reinforcement need to be defined accurately. The strength at
4.2—Ducts the wall-foundation interface and the displacement of an
Ducts, including those for energy-dissipating reinforce-
uncoupled wall are likely to be controlled by the maximum
ment, shall conform to requirements of 18.17 of ACI 318.
strain developed in the energy-dissipating reinforcement
and its effective debonded length (refer to Section 6.6.3.2).
R4.2
Ducts for the unbonded prestressing steel need to be large The maximum strain demand placed on that reinforcement
enough to preclude kinking (the act where the tendon comes during the maximum considered earthquake (MCE) ground
Normally, it is considered good practice during construction cannot be readily determined from theoretical consider-
to jack prestressing tendons to the highest force consistent ations. Therefore, full-scale testing of links, using the material
with not causing permanent deformations. For the tendons that will be used in the connecting links of the wall system, as
crossing the wall-foundation interface, the maximum required by ACI 550.6, is necessary to ensure that the deform-
permissible final effective stress will often be constrained by ability criteria of this provision can be satisfied.
the design and may be as low as 0.3fpu to ensure that the
prestressing steel does not yield in the DBE. Experience 4.6.2 Materials used for connecting links that are exposed
shows (Post-Tensioning Institute 2007), however, that to to weather or corrosive environments shall be stainless steel
prevent strand slippage, either long term or during the DBE conforming to ASTM A955 or shall be corrosion-protected.
event, it is necessary to initially set wedges with forces that R4.6.2 A weldable stainless steel was used for the
create stresses of approximately 70% fpu in the prestressing connecting links of the UFP coupling devices in the PRESSS
steel. This requirement is automatically met when post- building test (Priestley et al. 1999). Suitable materials for
tensioning tendons are jacked to 0.8fpu. If the effective stress corrosion protection are described in R20.6.3 of ACI 318.
in the prestressing steel is to be limited to as little as 0.3fpu ,
separate wedge blocking operations are then necessary. 4.7—Corrosion protection of prestressing tendons
Hydraulic blocking devices can be used that block one 4.7.1 Unbonded prestressing steel shall be corrosion
strand at a time and transfer their reaction force to the protected in accordance with 20.6.3 of ACI 318.
anchorage rather than the strand. R4.7.1 The prestressing steel may be strand, bars, or wire,
The prestress force is also to prevent sliding due to lateral and may be single-strand or multistrand tendons. Multi-
shear forces acting at the wall-foundation interface. A real- strand tendons may require different protection methods
istic assessment of prestress losses becomes essential when than single-strand tendons. Ducts need to be larger in size
low final effective prestress levels are used. Consequently, the than the prestressing steel so that kinking of the steel at the
use of an effective stress less than 0.3fpu is not recommended. wall-foundation interface does not occur.
4.3.4 Bonded pretensioned prestressed reinforcement is 4.7.2 Corrosion protection methods shall be used where
permitted in individual precast wall panels used to construct prestressing tendons cross the wall to foundation interfaces.
a shear wall.
R4.3.4 It can be advantageous to use pretensioned 4.7.3 Post-tensioning anchorages shall be sealed to
prestressed reinforcement in panels to control cracking. prevent water intrusion.
Separate deformed bar boundary reinforcement, however, R4.7.3 Encapsulation in accordance with ACI 423.7
may be needed. Section 6.5.1 should provide adequate protection.
5.1.2 Integrity of the entire load path shall be ensured 5.3.4 The design total drift angle θLdesign and the design
when the structure, and every story in it, is subject to the story drift angle, calculated as required in Section 5.3.3, shall
limiting story drift angle required by Eq. (5-1) of ACI 550.6 for not exceed two-thirds of the limiting drift required by Eq. (5-1)
the smallest value of hw /lw of any wall in the structure. of ACI 550.6 for the smallest value of hw /lw of any wall in
R5.1.2 The integrity of the load path to the foundation for the structure.
all components should be examined for the position to which R5.3.4 The limiting drift required by Eq. (5-1) of ACI
the structure deforms at its maximum anticipated drift angle. 550.6 is
That angle can be taken as controlled by the smallest hw /lw
value for any wall in one of the orthogonal directions for 0.90 ≤ 0.8[hw /lw] + 0.5 ≤ 3.0 (R5-1)
framing in the building.
5.3.5 The drift angle demand and drift angle capacity for
5.2—Strength any wall shall be calculated as the sum of the components
5.2.1 At all sections, nominal strengths calculated in
caused by: a) the inelastic deformations at the wall-foundation
accordance with the requirements of ACI 318 and Chapters 6
interface at the probable moment strength for that interface;
and 7 of these Design Requirements, multiplied by the
and b) the sum of the deformations, flexural and shear, of the
strength reduction factors specified in ACI 318, shall equal
wall framing into that interface.
or exceed the required strengths for all the load combinations
of 5.3 of ACI 318 involving the earthquake loading E.
5.3.6 Any wall shall be designed to have a drift angle
capacity θLmax and story drift angle capacities equal to or
R5.2.1 While the requirements of Section 5.2 need to be
greater than the limiting story drift angle required by Eq. (5-1)
satisfied for all sections in the structure, greater nominal
of ACI 550.6 for the hw /lw value of that wall.
strengths may be required for sections where capacity
design procedures are used to ensure that horizontal joints
do not open during earthquake events and that inelastic 5.3.7 The story drift angle capacity for the structure shall
action is confined to the toe regions of the walls. be the least drift angle capacity for any wall in that story.
5.4.5 Under horizontal ground motions, the precast walls 550.6 and small enough that the effective prestress in the post-
shall be designed to rock about their individual bases in tensioning tendon can close any gap at the wall-foundation
essentially a rigid body motion. interface when earthquake motions cease.
R5.4.5 With the horizontal joints between panels R5.4.8 For uncoupled walls, the energy-dissipating
remaining closed during the DBE, the effects of horizontal reinforcement crossing the wall-foundation interface fulfills
motions are absorbed primarily by the wall rocking on its three functions. First, it is the primary source of energy
interface with the foundation. dissipation that is relied upon for the wall during a seismic
event. For that function, the reinforcement needs, as
5.4.6 Under the DBE and for uncoupled walls, the inter- required by ACI 550.6, to provide a relative energy dissipa-
face between the wall and the foundation shall be the only tion ratio exceeding 1/8. Second, the reinforcement contrib-
location where nonlinear behavior is permitted. Under the utes to the flexural strength of the wall. Third, the
DBE and for coupled walls, the interfaces between the walls reinforcement can act as integrity steel that resists out-of
and the foundation and the coupling devices linking the plane displacements of the wall in the unusual case that the
vertical boundaries of adjacent walls shall be the only locations post-tensioning steel anchorages or couplers slip during an
where nonlinear behavior is permitted. unexpected event. Because the strain capacity of the energy-
R5.4.6 Capacity design principles can be used to ensure dissipating reinforcement is likely to control the maximum
that there is no opening of horizontal wall joints between strength or drift capacity of the wall, that reinforcement is
panels and that horizontal joint opening occurs at wall to best placed as close as possible to the centroid of the wall.
foundation interfaces only.
5.4.9 Devices that couple the vertical faces of adjacent
5.4.7 Post-tensioning tendons in walls shall be concentric walls to create a coupled wall system shall have a strength
within walls and the force in the tendons shall have: a) as large enough to provide the relative energy dissipation ratio
required by Sections 6.5 and 7.5, a steel stress fprs that, in of not less than 1/8 as required by ACI 550.6, and small
combination with the wall stress due to gravity loads, enough that the effective prestress in the wall can ensure that
provides a clamping force across the wall-foundation inter- the residual drift for the coupled walls is zero when earth-
face sufficient to resist, without slipping, the lateral force quake motions cease.
acting on the wall when the probable flexural strength of the R5.4.9 For coupled walls, the devices that cross the
wall is developed; and b) a maximum stress fprs, at the design interface fulfill three functions. First, they are the primary
drift angle θLdesign, that is less than the specified yield source of energy dissipation that is relied upon for the
strength fpy for the post-tensioning tendons. coupled walls during a seismic event. For that function, the
R5.4.7 There should be no slip of the base of the wall relative devices need, as required by ACI 550.6, to provide a rela-
to the foundation under the maximum forces in a seismic tive energy-dissipation ratio exceeding 1/8. Second, the
event. To ensure that condition and that the building will not devices couple adjacent walls so that the strength of the
6.3.2 The value for fse, in combination with the location and the bonding of those reinforcements on either side of the
for the energy-dissipating reinforcement, shall result in the interface. Where grout is used to bed panels on the founda-
energy-dissipating reinforcement yielding before the tion and between panels, the characteristics of that grout in
prestressing steel stress reaches 0.95fpy. terms of materials, strength, and thickness can have a large
effect on wall performance. The typical grout pad with a
6.4—Energy-dissipating reinforcement thickness of 1 in. (25 mm) or less can be expected to provide
6.4.1 The energy-dissipating reinforcement provided at a coefficient of friction of approximately 0.6 under reversed
the base of the wall shall provide at least 25% of the nominal loadings (Hutchinson et al. 1993; Soudki et al. 1995a,b).
flexural strength of the wall at the wall-foundation interface. Pads with greater thickness and without fiber reinforcement
R6.4.1 The 25% requirement is intended to ensure that the exhibit lesser coefficients of friction. Adequate frictional
energy-dissipating reinforcement provides a relative resistance is essential to preventing undesirable slip along
energy-dissipation ratio of at least 1/8 as required by ACI the wall-foundation interface. Fiber reinforcement is essential
550.6. This 25% value is based on the work of Kurama to preventing breakup of the grout and maintenance of the
(2002). Alternatively, the required amount of reinforcement coefficient of friction. Section 6.8 permits the use of grout
could be calculated using the procedures developed by types that differ from those tested by Hutchinson et al. (1993)
Restrepo (2002). and the maximum joint thickness permitted in Section 5.8 is
larger than the maximum considered in those tests. For these
6.4.2 The energy-dissipating reinforcement shall be anchored reasons, a smaller value of μ, equal to 0.5, is specified.
by: 1) being cast into the concrete of the foundation or wall At horizontal joints within the wall, other than the joint at
panel during the placement of that concrete; 2) being grouted in the wall-foundation interface, the nominal shear strength
ducts positioned in the foundation or wall panel prior to the can be computed using shear friction principles because
placement of the concrete for those members; or 3) use of a capacity design principles should be used to ensure that
Type 2 splice that connects energy-dissipating reinforcement those joints remain closed during the DBE event.
cast separately in the wall panel and the foundation.
6.5.2 At the probable flexural strength for the wall-foun-
6.4.3 Development length ld for energy-dissipating rein- dation interface Mpr , calculated as described in Section
forcement anchored in corrugated metal ducts shall be taken 6.6.3, φ times the nominal shear strength Vn for the wall, and
as 25db unless a lesser value is established from a compre- φ times the nominal horizontal shear strength for the inter-
hensive set of tests. face Vni, shall be equal to or greater than the base shear
R6.4.3 Bars anchored in concrete confined by corrugated causing Mpr. In addition, φ times the nominal horizontal
metal ducts, such as the spirally wound light-gauge steel shear strength on each horizontal joint between precast
ducts used for grouted post-tensioned construction, require panels within the wall shall be equal to or greater than the
less development length than bars anchored in monolithic shear acting at the level of that joint when Mpr is developed
If Lups is the length over which the post-tensioning tendon Table 6.1—Ratio of core strength to concrete
is unbonded, the strain in the strands at the probable flexural strength based on lateral confinement
strength can be computed by Eq. (6-3). Because the tendon fL′/fc′ 0.036 0.072 0.108 0.144 0.180
is unbonded anchorage to anchorage, Lups equals the fcc′ /fc′ 1.23 1.43 1.60 1.76 1.90
anchorage-to-anchorage distance, and Δprs is the joint
opening at the tendon location. The strain εprs is directly
related to Δprs because Section 5.4.6 requires no openings of 6.6.3.4 The total strain in the prestressing reinforcement,
joints along the length of the tendon except at the wall-to- εprs, after rotation at the interface, shall be calculated as
foundation interface at the design displacement.
The probable flexural strength Mpr is the sum of the Δ prs
ε prs = ε se + ---------- (6-3)
contributions from the energy-dissipating reinforcement Ms L ups
and the post-tensioned reinforcement Mprs. Those moments
are given by
where εse is the strain in the prestressing reinforcement at its
effective stress, and Lups is the unbonded length of the
Ms = Asfu(lw – a)/2 (R6-2)
tendon from its anchor in the foundation to its anchor at the
top of the wall. The stress fprs in the post-tensioning tendon
provided at θLdesign shall not exceed fpy.
(lw/2 – e)/(lw/2 + e) > 0.78 (R6-3) 6.6.3.5 Strain in the compressed concrete shall be
assumed directly proportional to the distance from the
and neutral axis and the maximum usable strain at the extreme
compression fiber shall be that given by Eq. (6-5).
Mprs = Aps fprs(lw – a)/2 (R6-4)
6.6.3.6 The compressed concrete shall be confined by
where transverse reinforcement satisfying the requirements of
18.10.6.4(e) of ACI 318. The transverse reinforcement shall
a = βc (R6-5) extend horizontally from the extreme compression fiber a
distance not less than 0.95c, and not less than 12 in. (305 mm),
and fprs is the stress corresponding to εprs. where c is the neutral axis depth.
The 0.78 limit is needed to ensure that the steel stress can
be taken as fu for the two groups of energy-dissipating 6.6.3.7 The relationship between concrete compressive
reinforcement located on either side of the centroid of the wall. stress distribution and concrete strain shall be assumed to be
based on the models proposed by Sritharan et al. (2007). It an area equal to the thickness of the wall at the interface and
is assumed in this standard that the magnitude of the 0.96 times the neutral axis depth at the probable flexural
compression force is determined by the strength of the strength of the interface.
confined concrete in the toe of the wall, and not by the
strength of the grout pad or the concrete foundation. Where 6.8—Interface grout
very heavy transverse confining reinforcement is used in the 6.8.1 Interface grout shall satisfy the requirements of
toe of the wall, any limitation imposed by the bearing Section 4.5. The thickness of the nonshrink interface grout
strengths of the grout pad and foundation should be checked. shall not exceed 1.5 in. (38 mm).
Those strengths depend on the geometric proportions of the R6.8.1 The performance of the joint between the wall and
pad and of the foundation in addition to the measured the foundation directly depends on the toughness of the grout
compressive strengths of the materials used in the pad and used in the interface. The interface is also one of the few
the foundation. Bearing strength limitations for the founda- locations where erection tolerances can be provided. The
tion are specified in 22.8.3 of ACI 318. Bearing strength grout in the joint should remain intact and not crush or fall
limitations for the interface grout are specified in Section out before the compression end of the wall starts crushing or
6.8.3 of this standard. spalling in an extreme event. Section 4.5 requires use of fiber
The compression force at the toe of the wall is provided reinforcement in the grout to ensure adequate grout tough-
by a stress of α fcc′ acting over a wall length of β c. The ness. Fibers may be steel or polypropylene. Polypropylene
values for α and β vary with the concrete strength in the fibers are desirable in exposed locations because joints with
wall, the confinement of the toe, and the extreme fiber steel fibers can be susceptible to rusting, and polypropylene
compressive strain for the wall. The values of 0.92 and 0.96 fibers provide added resistance to spalling during fire. The
used for α and β , respectively, are reasonable lower-bound testing described in the references (Rahman and Restrepo
values for the range of fc′ values of 4000 to 8000 psi (28 to 2000; Sause and Pessiki 2005; Schultz and Magana 1996)
55 MPa) and the fL′ /fc′ values shown in Table 6.1. The ratio used polypropylene fibers.
′ /fc′ depends on the effective lateral confining stress fL′
of fcc If the joint is too thick, the grout can fail under a combina-
provided by the transverse reinforcement. Values of fL′ /fc′ in tion of shear and axial stress at stresses less than the
Table 6.1 are multiples of the minimum confinement compressive strength of the grout. The compressive strength
required by Table 18.10.6.4(f) of ACI 318. of the grout should be approximately the same as the
6.6.3.9 The value of θLmax shall not exceed the value of compressive strength of the precast wall. If the grout has
θL at which the maximum usable strain εcmax is reached in considerably greater strength than the wall, it can cause
the extreme compression fiber premature crushing of the concrete at the compression
corner of the wall at high displacement levels. If the grout
θLmax = εcmax Lp /c (6-4) has considerably less strength than the wall, it will crush
first at high strain levels and cause a prestress loss, the
7.2—Materials
Materials shall satisfy the requirements of Section 6.2.
7.3—Coupling devices
7.3.1 Each coupling device shall exhibit a relative energy-
dissipation ratio greater than 1/8 when cycled between
maximum displacements equal to the displacement imposed
on the connectors when the wall system is displaced to 1.5
times its design displacement.
R7.3.1 The UFP coupling devices, defined in R2.2 and
described in Chapter 8, provide a relative energy-dissipa-
tion ratio greater than 1/8 when they are constructed of
ASTM A240 Type 304 stainless steel and are designed to
yield before the wall system reaches its design displacement.
7.4—Prestress force
7.4.1 The required area Aps of the post-tensioning steel Fig. R7.1—Forces and displacements for wall systems of
7.4.5 The area Aps determined in accordance with CHAPTER 8—DESIGN REQUIREMENTS
Section 7.4.1 and the initial stress fse determined in accor- FOR COUPLING DEVICES
dance with Section 7.4.4 shall be used for all walls in the 8.1—Scope
The requirements of this section apply to coupling devices
coupled wall system.
used to transfer shear between adjacent vertical edges of
seismic-force-resisting coupled walls.
7.5—Shear strength
7.5.1 The Vn value for each wall in the system shall be
R8.1
calculated as specified in Section 6.5.1 and φVn for each wall In accordance with ACI 550.6, coupling devices should be
shall exceed the fraction of the horizontal base shear acting demonstrated to have the strength, ductility, and energy-
on that wall when the wall system develops its probable dissipating toughness required for their use in an actual
flexural strength. structure either by prior testing of those elements at half
R7.5.1 Failure in shear of any one of the walls in a scale or larger or by their testing as part of the validation
coupled wall system is likely to trigger shear failure of the testing of the unbonded post-tensioned precast coupled
whole system. A sliding shear movement at the base of a wall walls. The use of commercially fabricated devices whose
system, however, would involve movement of all walls in the strength, displacement ductility, and energy-dissipating
system and, therefore, the shear strength is controlled by the toughness is guaranteed by the device supplier is preferable
sum of the Vni values for the individual walls. to the use of shear transfer devices developed in accordance
with the requirements of this section. Design requirements
7.5.2 The sum of the Vni values for each wall in the system are described in this section for UFP coupling devices that
shall exceed the horizontal base shear acting on the wall replicate the devices used in the PRESSS building. Concepts
system when the system develops its probable flexural for other types of shear transfer devices are described in
strength. The Vni value for each wall shall be calculated as Banks and Stanton (2005).
specified in Section 6.5.3. The sum of the Vn values for any
horizontal joint between precast panels for each wall in the 8.2—General
system shall exceed the horizontal shear acting on that level In accordance with the requirements of Section 5.4 of ACI
of the wall system when the system develops its probable 550.6, commercially available coupling devices shall be
flexural strength. The Vn on horizontal joints shall be calcu- used unless commercial devices are not available, in which
lated as specified in Section 6.5.3. case design and fabrication procedures shall satisfy the
requirements of Sections 8.3 and 8.4.
7.5.3 φ for shear shall be taken as 0.75 as specified in Coupling devices are defined in Section 2.2. as consisting
Table 21.2.1 of ACI 318. of anchorages and connecting links. This section concerns
the design of the connecting links. Anchorages must meet
the strength requirements of 18.5.2 of ACI 318.
R8.4
The connecting link of the UFP coupling device is an
energy-dissipating flexible connector in which rolling-
bending action resists vertical shear force. The link provides
little resistance to in-plane movement that is normal to the
joint so that it is well suited to coupled wall applications.
The forces Msc and Vsc assumed to be acting on a link
Fig. R8.1—(i) UFP connecting link forces; and (ii) typical when the two sides are displaced relative to one another are
details as tested by Thomas (2003). shown in Fig. R8.1(i) (Stanton and Nakaki 2002). Moment
equilibrium requires that at the nominal strength of the link
CHAPTER 9—COMMENTARY REFERENCES from the PRESSS Five-Story Precast Concrete Test
Banks, G., and Stanton, J., 2005, “Panel-to-Panel Connec- Building,” PCI Journal, V. 44, No. 6, Nov.-Dec., pp. 42-67.
tions for Hollow-Core Shear Walls Subject to Seismic Rahman, A. M., and Restrepo, J. I., 2000, “Earthquake
Loading,” PCI Convention, Palm Springs, CA. Resistant Precast Concrete Buildings: Seismic Performance
Bora, C.; Oliva, M. G.; Nakaki, S. D.; and Becker, R., of Cantilever Walls Prestressed Using Unbonded Tendons,”
2007, “Development of a Precast Concrete Shear-Wall Research Report 2000-5, Department of Civil Engineering,
System Requiring Special Code Acceptance,” PCI Journal,
University of Canterbury, Christchurch, New Zealand, Aug.
V. 52, No. 1, Jan.-Feb., pp. 122-135.
Raynor, D. J., 2000, “Bond Assessment of Hybrid Frame
Cheok, G. S.; Stone, W. C.; and Nakaki, S. D., 1996,
Continuity Reinforcement,” MSCE thesis, University of
“Simplified Design Procedure for Hybrid Precast Concrete
Connections,” NISTIR 5765, NIST, Gaithersburg, MD, Washington, Seattle, WA.
Feb., 81 pp. Restrepo, J. I., 2002, “New Generation of Earthquake
Conley, J.; Sritharan, S.; and Priestley, M. J. N., 2002, Resisting Systems,” Proceedings, First fib Congress, Osaka,
“Precast Seismic Structural Systems PRESSS-3: The Five- Japan, Session 6, Seismic Design of Concrete Structures,
Story Precast Test Building V. 3-1; Wall Direction Oct., pp. 41-60.
Response,” Report No. SSRP-99/19, Department of Struc- Santana, G., 2005, “Conventional Reinforced Concrete
tural Engineering, University of California at San Diego, Walls Versus Hybrid Post-Tensioned Precast Concrete
CA, July. Walls,” Proceedings, Third International Conference,
Eberhard, M. O., and Sozen, M. A., 1993, “A Behavior- Structural Concrete in the Americas, American Concrete
Based Method to Determine Design Shear in Earthquake- Institute, Farmington Hills, MI, Nov. 2005.
Resistant Walls,” ASCE Journal of Structural Engineering, Sause, R., and Pessiki, S., 2005, “Seismic Behavior and
V. 119, No. 2, Feb., pp. 619-640. Design of Precast Concrete Walls,” PCI Convention, Palm
Hutchinson, R. L.; Rizkalla, S. H.; Lau, M.; and Heuvel, M., Springs, CA.
1993, “Horizontal Post-Tensioned Connections for Precast
Schultz, A. E., and Magana, R. A., 1996, “Seismic Behavior
Concrete Bearing Shear Walls,” PCI Journal, V. 36, No. 3,
of Connections in Precast Concrete Walls,” Mete A. Sozen
Nov.-Dec., pp. 64-76.
Symposium—A Tribute from His Students, SP-162, J. K.
Kurama, Y. C., 2002, “Hybrid Post-Tensioned Precast
Wight and M. E. Kreger, eds., American Concrete Institute,
Concrete Walls for Use in Seismic Regions,” PCI Journal,
V. 47, No. 5, Sept.-Oct., pp. 36-59. Farmington Hills, MI, pp. 273-312.
PCI Ad Hoc Committee on Precast Walls, 1997, “Design Soudki, K. A.; Rizkalla, S. H.; and LeBlanc, B., 1995a,
for Lateral Force Resistance with Precast Concrete Shear “Horizontal Connections for Precast Concrete Shear Walls
Walls,” PCI Journal, V. 42, No. 5, Sept.-Oct., pp. 44-64. Subjected to Cyclic Deformations Part 1: Mild Steel Connec-
tions,” PCI Journal, V. 40, No. 4, July-Aug., pp. 78-96.
· Technical committees that produce consensus reports, guides, specifications, and codes.
· Periodicals: the ACI Structural Journal, Materials Journal, and Concrete International.
Benefits of membership include a subscription to Concrete International and to an ACI Journal. ACI
members receive discounts of up to 40% on all ACI products and services, including documents, seminars
and convention registration fees.
As a member of ACI, you join thousands of practitioners and professionals worldwide who share
@Seismicisolation
@Seismicisolation
Copyrighted material licensed to University of Toronto by Techstreet LLC, subscriptions.techstreet.com, downloaded on 2021-06-18 19:22:05 +0000 by
No further reproduction or distribution is permitted.
38800 Country Club Drive
Farmington Hills, MI 48331 USA
+1.248.848.3700
www.concrete.org
@Seismicisolation
@Seismicisolation 9 781641 950824