You are on page 1of 23

Al-Uwayqilah Calculations

17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(1) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:411
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 3 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 64920 Total: 81000 825.0

Page 1
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(1) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 256


Not all calculated values could be displayed.

Position of surface in external scene:


Marked point:
(498.100 m, 522.400 m, 0.000 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
16 6.66 43 0.428 0.154

Page 2
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(2) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:426

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 4 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 86560 Total: 108000 1100.0

Page 3
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(2) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 135


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(398.969 m, 576.768 m, 0.000 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
27 12 45 0.442 0.262

Page 4
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(3) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:653
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 5 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 108200 Total: 135000 1375.0

Page 5
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(3) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 138


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(372.145 m, 522.450 m, 0.000 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
42 19 53 0.448 0.355

Page 6
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(4) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:657
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 5 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 108200 Total: 135000 1375.0

Page 7
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(4) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 146


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(448.638 m, 418.070 m, 0.000 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
35 14 50 0.404 0.283

Page 8
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(5) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:407

Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 4 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 86560 Total: 108000 1100.0

Page 9
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(5) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 162


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(429.301 m, 368.488 m, 0.000 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
23 11 45 0.491 0.247

Page 10
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(6) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:350
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 3 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 64920 Total: 81000 825.0

Page 11
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(6) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 156


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(383.984 m, 300.538 m, 0.000 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
10 6.55 21 0.643 0.305

Page 12
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(7) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:329
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 3 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 64920 Total: 81000 825.0

Page 13
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(7) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 146


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(350.616 m, 241.609 m, 0.000 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
40 16 53 0.402 0.302

Page 14
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(8) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:418
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 4 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 86560 Total: 108000 1100.0

Page 15
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(8) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 122


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(297.095 m, 140.028 m, 0.000 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
25 10 45 0.412 0.228

Page 16
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(9) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:331
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 4 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 86560 Total: 108000 1100.0

Page 17
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(9) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 140


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(182.893 m, 210.864 m, 0.000 m)

Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
46 19 62 0.402 0.298

Page 18
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(10) / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:224
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 3 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 64920 Total: 81000 825.0

Page 19
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

Conflict Area(10) / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 185


Not all calculated values could be displayed.
Position of surface in external scene:
Marked point:
(217.610 m, 245.664 m, 0.000 m)

Grid: 128 x 128 Points


Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax
31 14 47 0.457 0.302

Page 20
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

car park 1 / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 1.5% Scale 1:619
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 5 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 108200 Total: 135000 1375.0

Page 21
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

car park 2 / Planning data

Light loss factor: 0.70, ULR (Upward Light Ratio): 2.0% Scale 1:453
Luminaire Parts List

No. Pieces Designation (Correction Factor)  (Luminaire) [lm]  (Lamps) [lm] P [W]
SAUDILIGHTING 7429PT/4-250B.SA Post-
1 4 Top Mounted Semi Cut-Off Road Luminaire 21640 27000 275.0
(1.000)
Total: 86560 Total: 108000 1100.0

Page 22
Al-Uwayqilah Calculations
17.09.2023

Operator
Telephone
Fax
e-Mail

car park 2 / Ground Element 1 / Surface 1 / Value Chart (E)

Values in Lux, Scale 1 : 398


Not all calculated values could be displayed.

Position of surface in external scene:


Marked point:
(279.657 m, 427.182 m, 0.000 m)

Grid: 128 x 128 Points

Eav [lx] Emin [lx] Emax [lx] u0 Emin / Emax


18 5.48 32 0.301 0.170

Page 23