Professional Documents
Culture Documents
LD13282
Issue Date:
December 17, 2021
FORM 102.20-N3
ISSUE DATE: 12/17/2021
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During rigging, installation, operation, maintenance, death to themselves and people at the site.
or service, individuals may be exposed to certain com-
ponents or conditions including, but not limited to: This document is intended for use by owner-authorized
heavy objects, refrigerants, materials under pressure, rigging, installation, and operating/service personnel. It
rotating components, and both high and low voltage. is expected that these individuals possess independent
Each of these items has the potential, if misused or training that will enable them to perform their assigned
handled improperly, to cause bodily injury or death. It tasks properly and safely. It is essential that, prior to
is the obligation and responsibility of rigging, instal- performing any task on this equipment, this individual
lation, and operating/service personnel to identify and shall have read and understood the on-prooduct labels,
recognize these inherent hazards, protect themselves, this document, and any referenced materials. This in-
and proceed safely in completing their tasks. Failure dividual shall also be familiar with and comply with
to comply with any of these requirements could result all applicable industry and governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
External wiring, unless specified as an optional connection in the manufacturer’s product line, is not
to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls
and any external wiring must not be installed inside the micro panel. All wiring must be in accor-
dance with Johnson Controls’ published specifications and must be performed only by a qualified
electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control signals. Failure to follow this warn-
ing will void the manufacturer’s warranty and cause serious damage to property or personal injury.
2 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
Revision notes
Revisions made to this document are indicated in the following table. These revisions are to technical information.
Changes in spelling, grammar or formatting are not included in this table.
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
York Air Handling Units Operation and Maintenance 102.20-OM1
Steps to Protect New Equipment Warranty 102.20-CL1
Air Handling Units Start-up Checklist 100.00-CL1
Long-Term Storage Requirement - Field Preparation - Air Handling Units 50.20-NM3
Long-Term Storage Periodic Checklist and Logs - Air Handling Units 50.20-CL3
Limited Warranty 50.05-NM2
Electric Motor Warranty 50.05-NM2.2
Air Cooled Condensing Unit DX Coil Split System Applications and Piping Guidelines 50.40-ES3
Air Modulator Service & Warranty Procedure SI0262
JOHNSON CONTROLS 3
FORM 102.20-N3
ISSUE DATE: 12/17/2021
4 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
TABLE OF CONTENTS
JOHNSON CONTROLS 5
FORM 102.20-N3
ISSUE DATE: 12/17/2021
Back Draft Dampers for Dual Fans and Fan Arrays ....................................................................................... 35
Filling Inertia Fan Base ................................................................................................................................... 36
Steam Humidifier............................................................................................................................................. 37
UVC Emitter Lamps......................................................................................................................................... 37
Two Types of Lamps..............................................................................................................................37
Air Measuring Device Connections ................................................................................................................ 42
Air Measuring at the Fan Inlets.............................................................................................................. 42
Air Measuring at Unit Outside Air Inlets.................................................................................................. 42
Installing External Vent Piping for Outdoor AHUS...........................................................................................43
Condensate Drain Arrangement............................................................................................................. 43
Field Penetrations for Piping and Electrical Connections................................................................................ 45
General Electrical Information......................................................................................................................... 47
Power Connections......................................................................................................................................... 47
Single Point Power.................................................................................................................................47
Motors for Supply, Return, and Exhaust Fans........................................................................................ 48
Wiring the Energy Recovery Wheel................................................................................................................ 48
Wiring the Gas Heat Device............................................................................................................................ 49
Wiring the Electric Heat Device....................................................................................................................... 50
Power Options........................................................................................................................................50
Disconnect Switch Options.....................................................................................................................50
Control Options......................................................................................................................................51
Installing Electrical Heat Option............................................................................................................. 51
Electric Humidifier........................................................................................................................................... 54
Humidifier........................................................................................................................................................ 54
Coil Piping....................................................................................................................................................... 55
Staggered Coils......................................................................................................................................55
Hot and Chilled Water Coils...................................................................................................................56
Water Treatment.............................................................................................................................................. 58
Vertical Tube Integral Face and Bypass (VIFB) and Integral Face and Bypass (IFB)..................................... 60
Shipping Bolts (VIFB Only)..................................................................................................................... 60
Piping Suggestions ................................................................................................................................60
Flexible Connectors (VIFB Only)............................................................................................................ 60
Freezing Conditions...............................................................................................................................60
Refrigeration.................................................................................................................................................... 64
DX Direct Expansion Coils.....................................................................................................................64
Available Coil Arrangements ................................................................................................................. 66
Thermostatic Expansion Valves (TXV) ........................................................................................................... 68
Hot Gas Bypass (HGBP)................................................................................................................................. 68
Dx Coil Circuiting and Staging......................................................................................................................... 68
Advantages of Multiple Control Stages.................................................................................................. 69
Maintaining Adequate Airflow ........................................................................................................................ 69
VAV Systems................................................................................................................................................... 70
Drains and Traps............................................................................................................................................. 70
Condensate Drain Piping.......................................................................................................................70
Elevating AHU for Gravity Floor Drain Connections.............................................................................. 71
Duct Connections............................................................................................................................................ 72
Duct Connection Guidelines................................................................................................................... 72
Flanged Duct or Sleeves........................................................................................................................72
Raw or Straight Edge Duct or Sleeves................................................................................................... 72
Sound and Vibration Transmission ........................................................................................................ 73
6 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
LIST OF FIGURES
JOHNSON CONTROLS 7
FORM 102.20-N3
ISSUE DATE: 12/17/2021
8 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
LIST OF TABLES
JOHNSON CONTROLS 9
FORM 102.20-N3
ISSUE DATE: 12/17/2021
10 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 11
FORM 102.20-N3
SECTION 1 - GENERAL INFORMATION AND SAFETY
ISSUE DATE: 12/17/2021
12 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
3. Heating and Cooling The economizer system provides the first stage of cool-
ing whenever the outdoor air is cool and dry enough to
4. Cleaning satisfy the internal cooling demand. The outdoor and
the return air dampers are operated by individual ac-
tuators. As the outdoor air dampers are opened by the
damper actuator, the return air dampers are closed.
LD13764
JOHNSON CONTROLS 13
FORM 102.20-N3
SECTION 2 - PRODUCT DESCRIPTION
ISSUE DATE: 12/17/2021
RIGHT
FAN SECTION
REAR
RIGHT HAND (RH)
COIL CONNECTION
14 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 2 - PRODUCT DESCRIPTION
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 15
FORM 102.20-N3
SECTION 2 - PRODUCT DESCRIPTION
ISSUE DATE: 12/17/2021
16 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 17
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Protect fan and motor bearings from Monthly check – Rotate the fan impel-
moisture and vibration ler, add grease to the bearings, leave
at 1800 from the previous position
Belt driven fans Store in a protected area away from dirt Storage environment – Indoor storage
and moisture. Store between -40F (-200C) is preferred
and 1130F (450C)
Remove or release tension from the
belt
ECM fans Store the fan and motor in a dry area Storage temperature between -40F
protected from dirt and weather (-200C) and 1130F (450C)
Ensure that all electrical components are Monthly check – Rotate the fan
stored in a clean, dry environment impeller
18 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 19
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
20 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Storage requirements
3
Storage temperature -400C to 700C or -400F to 1580F
Desiccant Can be used to keep the drive dry. Remove before startup of the unit
JOHNSON CONTROLS 21
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Energizing VFDs
Electrolytic capacitors are used in almost all low and some medium voltage drives. These capacitors are filled with
an electrolytic gel. As these capacitors sit without being used, the gel starts to dry up and may result in issues.
1. It is suggested that you energize the VFD yearly for 1 hour. When you perform the annual preventative main-
tenance on drives, energize any stored VFD. If electrolytic capacitors sit for more than a year without being
energized, make sure to reform the capacitors before placing in service.
2. Another issue with just reforming the capacitors on VFDs is that you can only reform the DC bus capacitors.
Capacitors that are on the printed circuit boards are not reformed. It is best practice to energize stored VFDs
every year or if the VFD is a spare, rotate out equipment during annual preventative maintenance service in
order to keep all VFDs in ideal running shape.
Reforming
The drive DC link capacitors need to be reformed, or re-aged, if the drive has been non-operational for more than
one year. Without reforming, capacitors may be damaged when the drive starts to operate. The reforming methods
introduced in this set of instructions require that the drive has been stocked in a clean and dry manner. Capacitors
must be reformed once a year.
Reforming time
The intermediate circuit of the drive is kept in its nominal voltage for the reforming time in order to wake up the
capacitors. The reforming time required is dependent on how long the drive has been stocked or in a non-operational
setting. Refer to Capacitor reforming time.
Note: Please refer to Form 50.20-NM12 on the JCI portal for additional information.
Summary
This warranty provides coverage for replacement parts only and does not cover failure or damage due to storage.
Installation, operation, or maintenance which is not in compliance with Johnson Controls' specifications and in-
dustry standard practice due to accident, misuse, abuse, or negligence may void the factory warranty. In addition,
this warranty does not cover reimbursement for labor, including any removal or installation expenses which may be
incurred in connection with repair or replacement, unless otherwise agreed upon by Johnson Controls.
22 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Take the following precautions before extended stor- Occasionally, an outdoor AHU may be entirely
age: wrapped in plastic, which should not be removed un-
til the AHU is installed, to prevent damage from job
• Grease the fan and motor bearings per the manu- site dirt and various weather conditions. If the AHU
facturer’s specifications. is covered with plastic, cut the wrap in the outline of
• Protect the motors and sheaves from free moisture the door(s), and proceed to access the AHU using the
or high humidity, which may be accomplished by: information (above). Close the cut with duct tape. 3
• Spraying components with an anti-rust solu- Shipped Loose Parts
tion (P/N 026-37707-000).
Check the packing list, which notes the number and
• Disconnecting the belts. Wrapping the types of parts, for non-mounted shipped loose parts in
sheaves and motor and sealing them with all segments of the AHU. Report shortages within 10
plastic. Inserting a desiccant to absorb mois- days after receipt of the order.
ture that may penetrate the plastic protection.
LIFTING WEIGHTS
• Meg the fan motor windings and record for com-
parison prior to placing the AHU in service. AHU section weights are furnished on the job submit-
tal form. Due to the variance in weight of each AHU
• If the fan housing was supplied with a drain con-
design, it is not possible to list AHU weights in these
nection, remove the plug to prevent moisture from
instructions. Refer to the job submittal form when se-
accumulating in this part of the fan during storage.
lecting a crane for rigging and figuring out roof weight
Periodic Fan Check loads. Contact a Johnson Controls sales representative,
if there are questions regarding the AHU weights.
On a monthly basis, perform the following tasks:
• Rotate the fan and motor several times to replen- MOVING THE AHU
ish the bearing surfaces with fresh grease. Prior to moving the AHU, make sure that the installa-
• Turn the fan impeller 180° from the previous tion site is suitable for installing the AHU, and is easily
month's position to prevent the belts from taking capable of supporting the weight of the AHU and all
a set position. associated services.
JOHNSON CONTROLS 23
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD19197
Rigging and lifting should only be done by a professional rigger in accordance with a written rig-
ging and lifting plan. The most appropriate rigging and lifting method will depend on job specific
factors, such as the rigging equipment available and site needs. Therefore, a professional rigger
must determine the rigging and lifting method to be used, and it is beyond the scope of this manual
to specify rigging and lifting details.
Removable lifting lugs are provided to raise the unit. BOLTED LOOSELY / SHIPPED IN ONE PIECE
(Lifting lugs are typically shipped attached to the unit
base. Lifting lugs may be removed for shipping pur- Split units may be shipped “loosely” assembled to re-
poses and will be in the truck driver's possession. The duce freight costs. The split sections are fastened to-
rigger must re-attach the lifting lugs to the base before gether using a minimum number of bolts for transit and
lifting the unit/skid off of the truck.) Spreader bars are can be removed off the truck to the ground. Disassem-
required to prevent damage to the cabinet and protrud- bly is required before lifting to the roof. Each section
ing components during a lift. Use all lifting lugs pro- must be lifted individually to the roof.
vided. Adjust the tension in each line for proper load
Rigging
distribution.
Remember - when lifting; use all lifting
Unit sections are bolted together for ship- lugs to avoid damage and/or personal
ping purposes. Sections must be separated injury. Lifting lugs are shown in Figure
and sealed prior to final installation and 5 on page 25.
operation.
24 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
If you do not rig or lift the unit carefully, COME-A-LONGS (POWER PULLS)
you could damage the unit, hurt yourself
If the AHU has multiple sections, use come-a-longs
or others. Use Caution!
(power pulls) as shown in Figure 4 on page 25 to
pull the sections or skids together.
If other than light foot traffic or storage of materials Figure 4 - TYPICAL COME-A-LONGS
becomes necessary, plywood may be placed on the
roof provided the weight applied does not exceed 50
CORRECT LIFTING WITH SHACKLES
lbs. per sq. ft.
Shackles are fastened to a sling or chain, which is used
SPREADER to lift and lower the sections in a tiered AHU. DO NOT
BARS attach shackles directly to the unit base. Shackles must
be attached to the lifting lugs on the unit base. Refer to
Figure 5 on page 25 and Figure 6 on page 28 for
proper lifting.
HOUSING
HOUSING
60° MIN
JOHNSON CONTROLS 25
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Once the unit is in place, remove the lifting lug and stand off bracket. The cover plate is installed over the lifting
lug hole using the same fasteners.
The cover plate is not used when the lug hole is at unit splits, only when the lug hole is exposed around the perimeter
of the unit.
Note: Ensure that you apply urethane sealant on the back of the cover plate before you install.
26 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Note: Use a spreader bar to avoid damage to the unit, to accommodate multiple lifting lugs, and to maintain maxi-
mum 600 specified angles.
JCI P/N: 026-52724-000
JOHNSON CONTROLS 27
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
If the AHU has HEPA filters, the filter Concrete pads may not be as flat as they should be.
frames, bulkheads, and segment panels Shimming and/or grouting may be necessary. Whether
are factory sealed, and must remain sealed under the AHU base or curb, the AHU base needs to be
to prevent air bypass. on a flat plane.
A Fan Section
24"
H B Coil Section
24" C Face and Bypass Damper Section
D Filter Section - Door should open 180°
24" A B C D E F
E Inlet Section
G F Rain Hood (add unit width or length)
UNIT WIDTH + 6 IN. G Pipe Chase Enclosure (add to unit width)
H Coil Access Panel on Outdoor Unit
(allow clearance = to unit width)
LD6326-4
28 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
BASE SKIN
FORMED INTERNAL
CHANNEL
STRUCTURAL PERIMETER
CHANNEL
ROOF CURB
CURB ANGLE
CHANNEL FLANGE / “A”
NOTE:
Flange width can vary. Locate outside edge of curb angle
using “A” dimension from the back side of the perimeter
channel.
LD010495
JOHNSON CONTROLS 29
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Clearance and Mounting for Indoor AHUs Installing Ceiling Suspended AHUs
It is recommended that the AHU is located in an air It is recommended that support is structur-
-conditioned space. Some suggested installations are ally engineered to prevent flexing, sagging
shown in Figure 9 on page 30. Make sure the floor or twisting of the AHUs.
and housekeeping pads are flat and level.
Allow sufficient space around the AHU to remove the
access panels and various parts. A minimum clearance Use the following instructions to prepare the site for
equal to the width of the AHU plus 6 in. must be pro- ceiling suspended AHUs. Refer to Figure 11 on page
vided on one side of the AHU to remove the coil or fan 31 for proper support in the direction of airflow and/
assembly. or if the AHU is positioned perpendicular to the direc-
Concrete pads may not be as flat as they should be. tion of the air flow.
Shimming and/or grouting may be necessary. Whether
Structure Positioned in Direction of Airflow
under the AHU base or curb, the AHU base needs to be
on a flat plane. The AHU base must be supported continuously on
both sides.
Mounting Indoor AHU
Structure Positioned Perpendicular to Airflow
Install the AHUs to provide enough elevation for prop-
erly designed condensation traps. The AHUs must be supported (at a minimum) at the
following locations:
• Both ends
• At each shipping split, if applicable
• Upstream and downstream of each cooling coil
segment
• Under heavy components like fans, attenuators,
and heating segment.
• As a general rule, cross members should be placed
every 96 in., in addition to each shipping split.
DO NOT obstruct the door operation,
filter access, piping, electrical or control
LD05373
connections with suspension members.
Figure 9 - NO HOUSEKEEPING PAD - BASE
REQUIRED TO ACCOMMODATE TRAP HEIGHT
LD05374
30 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
BDW COOLING
BDW COOLING
Fan Section Fan Section 3
MC RF MB CC RF MB
LD09619A
LD07941
JOHNSON CONTROLS 31
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
32 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
• Johnson Controls Custom units must be level for 4. Split seams that have internal access to both sides
reassembly. of split will be reattached with bolts and nuts.
Split seams with internal access to only one side
• All bolts, nuts, washers, split covers, and polyure-
of split will have cage nuts on the blind side and
thane caulking (if required) can be found in sup-
bolts installed from accessible side. All bolt holes
ply fan section.
require a bolt.
• All splits are labeled with letters (e.g., A-A, B-B) 3
5. If bolt holes do not align, it may be due to racking
to indicate which sections are to match up for re-
during transit to job site. Use jack to lift one side
assembly.
until holes on the wall of the opposite side align.
MATCH MATCH Bolt this wall together and then remove jack from
A A
opposite side. As the unit settles, the out-of-square
racking caused during transit should realign. Con-
→ ← tinue assembly with bolting other side, base, floor
and roof, making use of a drift pin to align the
holes. Bar clamps may be needed to align the
REMOVABLE LIFTING LUGS roofs together. If bar clamps are needed use wood
for protection in between the bar clamp and unit.
If your unit is wider than any split section’s airway
length, you will be provided with removable lifting 6. Check to see if all bolts are secured properly, and
lugs along the width of unit. Once the splits have been apply polyurethane caulk to all exterior seams per
placed as close as possible to each other, remove the in- Figure 15 on page 34.
ner lifting lugs. A hand-actuated winch, or come-along,
7. Drive screw or bolt floor flange together.
can be used to bring the unit sections closer together
for final bolting. Attach hand winch or come-along to 8. CHECK all splits to see if polyurethane caulk was
base “tie down tubes” to bring unit together. applied and split was bolted properly.
ELECTRICAL WIRING/PIPING 9. CHECK all splits to see if all electrical and piping
connections are complete and correct.
It is the installer’s responsibility to reconnect all inter-
Temporary roof supports and diagonal
nal and external electrical or piping splits. All wires
(shipping) supports should not be re-
are colored and/or numbered to designate which wires
moved until the split sections are com-
should be joined at each split. Before turning on power,
pletely reassembled.
check all electrical circuits for continuity.
JOHNSON CONTROLS 33
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
FIG. 18
L
NTA FIG. 20
R IZO UNIT
HO T IN
I
SPL
FIG. 19
FIG. 15
VERTICAL
SPLIT IN UNIT
LD07925b
.75 HEX BOLT .75 HEX NUT (USE FROM LIFTING LUG)
(USE FROM LIFTING LUG)
34 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Only use caulking shipped with unit. Do not use silicone caulking on field re-
connects or on shipping split covers.
LD13129
Figure 16 - SPLIT REASSEMBLY PROCEDURE FOR OUTDOOR UNITS ONLY
JOHNSON CONTROLS 35
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD07932A
OUTDOOR SPLIT ROOF SEALANT 7. One quart applied at 45 mils is equal to a 3 inch
PROCEDURE wide X 33 ft. long section.
1. The mechanical joint between sections must be 8. Cure time will vary with temperature and humid-
bolted and sealed with polyurethane caulking. ity. Under normal conditions, a rubber coating can
be expected within a 24 hr. period.
2. Acu-Shield Roof Coating can be applied after
polyurethane caulking is dry and when surface ACU-SHIELD ROOF COATING *
6. Apply Acu-Shield Roof Coating with 3” wide Figure 18 - OUTDOOR SPLIT SEALANT
roller or 3” wide paintbrush (not provided). PROCEDURE ON ROOFS WITH ACU OPTION
36 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD20621
JOHNSON CONTROLS 37
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
EXTERIOR SKIN
LINER
.25-20 X .75 HEX BOLT
WITH .25 FLANGED LOCK NUT
(SUPPLIED BY YORK)
RECONNECT
LD010141
38 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Installing Hood with Moisture Eliminators 8. Seal each hood gutter to the AHU panel with the
1. Identify the correct hood and its respective loca- polyurethane caulk (provided).
tion by looking at the label as shown in SECTION 9. When multiple hoods are installed in a stacked
2 - PRODUCT DESCRIPTION in this manual. space, the hoods should be approximately 1 1/2
2. Correct orientation is with the tracks or bird in. apart so that the bottom hood will extend 6 in.
screens to the bottom. The mounting flanges are below the bottom of the opening.
pre-drilled. 10. If equipped, install the optional moisture elimina-
3. Each hood is fitted with a factory installed bird tors as shown in Figure 21 on page 39 using the
screen unless the moisture eliminator option is se- following instructions.
lected. a. Remove the clip(s) from the leading edge of
4. Apply the Butyl tape to the pre-drilled hood flang- the hood.
es and back wall angle that contact the AHU pan- b. Insert the proper size moisture eliminator or
els. filter into the tracks.
5. Use the hex head screws with the EPDM washer c. Reinstall the clip(s) on the leading edge of
provided in the fastener pack. the hood.
6. Completely cover each damper opening in the Outdoor Air Temperature and/or Humidity
AHU panels by its respective hood. The bottom of Sensors
the hood should extend approximately 6 in. below
the AHU panel opening. When outside air hoods are shipped loose with AHUs
that include factory packaged controls, these sensors
7. Center each hood over the width of the opening. will be dismounted and pulled back into the AHU. The
All hoods, especially those containing barometric contractor should find them secured with tape inside,
dampers, MUST be installed square. and put them through their respective penetration to the
exterior, and mount them to the bracket provided.
BUTYL
TAPE
CLIP
MOISTURE CAULK
ELIMINATOR
LD13783
JOHNSON CONTROLS 39
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Installing Damper Actuator 3. Reinstall the bearing plate to the damper frame
Use the following instructions to install the actuator as and jackshaft.
shown in Figure 22 on page 40. 4. Slide the damper actuator, mounting bracket into
the actuator mounting grooves and fasten to the
Damper Blade Orientation damper frame using self drilling screws.
Return air and mixing dampers:
5. Securely tighten the actuator shaft clamp to the
Position blades so that they will be open once the actu- dampers jackshaft. Make sure at this point the
ator is installed. This will be the dampers spring return damper shaft is completely rotated to its proper
position. Note whether the damper shaft is rotated fully position.
clockwise or counter clockwise.
6. Manually operate the actuator to its fully actuated
Outside air and exhaust air dampers: position using the crank arm provided with the ac-
Position the damper blades so that they will be closed tuator then release the spring to allow the damper
once the actuator is installed. This will be the dampers to go back to its original position. This will verify
spring return position. Note whether the damper shaft the actuators spring rotation and stroke.
is rotated fully clock-wise or counter clockwise.
7. Set the damper actuators rotation selector switch
Actuator Installation to the proper rotation required to actuate the
damper.
1. Remove the bearing plate from the damper frame
and jackshaft. This will always be opposite the spring
return rotation.
2. Slide the damper actuator onto the open end of
this shaft making sure that the proper spring re-
turn position on the face of the actuator matches
the damper shafts rotation, if not then reinstall the
actuator with it flipped over.
40 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
2. After the AHU top tier is assembled to the bottom 6. Attach the damper assembly to the AHU's outer
tier and sealed, install the MZ damper assembly, perimeter mounting flange, using the screws pro-
which includes the hot (top) deck and cold (bot- vided.
tom) deck damper banks that are already connect- 7. Remove the 16-gauge shipping plate from the air
ed at each blade as shown in Figure 23 on page leaving side.
41.
8. Install the screws through the mounting flanges
Distortion will result in unreliable blade
between the hot and cold decks.
operation.
SHIPPING
SHAFT EXTENSION KIT SHIPPING PLATE AIR
(P/N 026-33715-002) PLATE AIR ENTERING
LEAVING
MOUNTING COLD DECK
FLANGES DAMPER
LD12029a
JOHNSON CONTROLS 41
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Installing Field Supplied MZ Damper • On the rear mount (discharge through end of the
Actuators AHU), always mount the actuators on the top of
When the actuators are field supplied for MZ dampers, the upper deck.
use the following information to select the correct size • Do not allow the duct insulation to restrict the
actuator. damper blades or external linkage.
• Required torque is 7 in-lb/sq. ft of damper area up • Direct coupled actuators are recommended.
to 2500 feet per minute (FPM).
• Make duct connections at the zone dividers with-
• Damper blades are 6 in. wide and vary in height. out restricting the damper blade(s).
• Calculate the torque by the number and size of BACK DRAFT DAMPERS FOR DUAL FANS
blades in each zone. There are hot deck blades di- AND FAN ARRAYS
rectly connected to cold deck blades.
The counterbalance is locked into place for shipping as
• Determine the number of blades per zone by the shown in Figure 25 on page 42. Before startup, the
system cubic ft per minute (CFM), and static pres- counterbalance will have to be released. To do this,
sure requirements for each zone by the engineer’s loosen the set screws and slide the counterbalance off
construction documents. the end of the shaft. Flip the counterbalance and slide
• Cut the blade linkage (flat rods) connecting all it back on the shaft. Rotate the counterbalance above
blades of each deck at the appropriate places to di- the damper as shown in Figure 26 on page 42, and
vide the decks into correct size zones. These rods then tighten the set screws. The counterbalance should
are mounted externally on the assembly. Make be free to rotate.
sure to cut out a section of the flat connecting rod,
which will prevent interference when the zones
modulate in opposite directions.
• One damper shaft extension kit (P/N 026-33715-
002), as shown in Figure 24 on page 42 is pro-
vided for each zone per the factory order form.
LD17103
LD116504
42 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
FILLING INERTIA FAN BASE Adjust the isolators according to the following steps.
Inertia fan bases are pre-engineered according to the • All fans are internally spring isolated and are bolt-
fan and motor size. Use the following instructions to ed down for unit shipping (see Figure 27 on page
fill an inertia fan base with concrete. 43).
• Calculate the amount of concrete by measuring • When unit is in place, assembled, and leveled,
the overall length and width of the fan base as- disassemble the fan hold-down by removing two 3
sembly cavities that have the corrugated metal nuts and one washer from each side.
bottoms. The standard depth of a cavity is 4 in.
• Remove tubes from wire, and discard the wire.
• Fill each cavity 1 in. from the top with wet con-
• Place tubes on studs, and place a shoulder washer
crete. Do not get concrete mix on the bolts and
(shoulder up) on the studs. Place one nut on each
adjusting parts of the adjustable motor base,
stud and tighten it on the shoulder washer.
sheaves, belts, or on the floor under the edges of
the isolated fan base. • Place the remaining nuts on the studs and tighten
to lower nut to lock in place.
WIRE
NUTS
TUBE
SHOULDER
WASHER
TUBE
NUTS
STUD STUD SHOULDER
NUTS STUD WASHER
SHOULDER
WASHER TUBE
1/2”
BUT-OUT ISOLATORS
LD07934A
NOTES:
1. Remove the 7/8 nut as shown in the operating position view.
2. Loosen the 7/8 jam nut between the isolator housing and the fan base support angle until the desired level is achieved.
3. Repeat step 2 until all isolators are set at the proper elevation and the fan base is level.
JOHNSON CONTROLS 43
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD16552
V_Max
44 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 45
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
46 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Sequence of Operation:
Discounnecting Means of UV lighting will be accomplished by "CB1" internal to the panel. "CB1" is cable of being locked out by panel latching
mechanism.
"SW1" is a proximity switch with a magnet, which will close a set of normally open contracts. The magnet will engage the "SW1" contact when-
ever it is within 1/2" of the switch.
"TDR1" is one second (1sec) time delay relay having normally open contacts. When power is initiated, its contacts will close for one second
then re-open. To reset, power, power must be removed from "TDR1"
"C1" is a dpdt 24 vac control relay, used to seal-in its coil and provide interlocking means to the UV lights.
If all doors are closed, all the "SW1"s will allow "C1" to energize, as long as power is available.
By selecting "CS-1" to the "on" position, the 24vac control power circuit will be energized. As long as all doors with door switches (SW1) are
closed and upon detection of power to the 1 second time-delay realy (TDR-1), the "TDR-1" normally open contracts will close for one second,
energizing the contactor "C1" will remain energized. Should any one door having "SW1" mounted, were to open, "C1" will de-energize, deacti-
vating the UV lamps. Closing all doors will not turn on UV lights. "CS-1" will be required, to be cycled "Off" then back "On" to allow the lights to
come back on. If the power is removed from the UV control panell and re-energized (such as when power fluctuates off then back on), the UV
lights will reactivate automatically. The "IL" "UV Light In USe" indcator lamp will alow the user to know if the lights have been energized.
LD16609
JOHNSON CONTROLS 47
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
that are combined into a single connection piped Figure 34 - HIGH AND LOW CONNECTIONS AND
to the negative (-) port of a factory mounted trans- ASSOCIATED TUBING FOR FAN MOUNTED AIR
ducer on the fan wall. The positive (+) port is left MONITORING SYSTEM
open to the fan section. Wiring is not provided
to the transducer unless factory packaged controls
were selected.
The fan manufacturer does not recom-
mend placement of the flow measuring
probes inside the fan inlet cone in the Low Port
path of airflow. These devices create High Port
disturbances and unpredictable perfor-
mance losses.
LD17233
48 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
• EAML used on outdoor air handlers usually to For outdoor AHUs with an overall height more than
measure outside air. This can be provided with 102 in. (8 1/2 ft), the external vent piping parts will be
one or two pairs of positive (+ or High) and shipped loose for field mounting. Figure 36 on page
negative (- or Low) pressure tube connections. 49 shows some generic instructions to install the
Connect (+) & (-) respectively to the (+) & (-) piping parts. An installation manual specific to the fuel
ports of the transducer(s). Wiring & transducer venting system will be provided.
are not provided unless factory packaged controls 3
were selected. Condensate Drain Arrangement
The indirect fired gas heat exchanger has the poten-
INSTALLING EXTERNAL VENT PIPING FOR
tial to create highly acidic condensation, particularly
OUTDOOR AHUS
during extended operation at low capacity or low fir-
For outdoor AHUs with an overall height ing rate conditions. To insure proper drainage, use the
less than 102 in (8 1/2 ft), the external following instructions as shown in Figure 37 on page
vent piping parts will be factory installed. 50.
When constructing the condensate trap for the heat
exchanger drainage system, make sure the trap is tall
enough to handle the total static pressure (TSP) of the
indoor blower at low fire times. For example, if a TSP
is 6 in. at low fire, construct a trap that is 12 in. tall as
shown in Table 2 on page 50.
STEP 1
STEP 3
FLUE CAP STEP 2
SPLIT PLATE VSI PIPE
SPLIT CLAMP
PIPE CHASE
CURB
PIECE
RACEWAY
CONTAINMENT
SIDE IVSI PIPE BAND SET, GASKET
PANEL
AND INSULATION
FIBER STEP 4
SLIP JOINT
0.43 IN CLEARANCE
GAS FURNACE WITH CASING 7.75 TRANSITION
PIECE
ID
12 FAN
EXT.
STORM COLLAR
HAT CHANNEL
5.50
LD13326
JOHNSON CONTROLS 49
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Table 2 - TSP AND DRAIN TRAP 4. Drain lines, fittings, and supports should conform
MODEL DRAIN NPT A B C to local codes, and be suitable for the application.
DF-15/25 1/2 in. 4 in. 2 in. 2 in. 5. Condensate drain and trap discharge should be
DF-30/50 1/2 in. 8 in. 4 in. 4 in. pitched away from the equipment at a slope of 1/4
DF-60/75 1 in. 8 in. 4 in. 4 in. in. per linear foot or as local code dictates.
DF-85/200 1 in. 12 in. 6 in. 6 in.
6. For outdoor or unconditioned space installations,
DF-225/400 1 in. 16 in. 8 in. 8 in.
local climate may dictate the need to heat trace
Failure to follow these instructions may and/or insulate the exposed drain lines and trap.
cause excessive condensation buildup, Frozen drain lines and/or trap will cause build up
resulting in water damage to the facility of condensate inside the heat exchanger, resulting
and/or a cracked heat exchanger. in leakage and damage to the AHU, and possibly
to the building.
7. Provide unions in drain lines to allow removing
1. Observe local codes for gravity condensate drain- the trap for periodic cleaning of drain lines and the
age requirements. trap. When the burner is operated at low capacity
2. Install the AHU at an elevation that enables prop- for extended periods, more condensate is generat-
er condensate drainage and trapping dimensions ed, and with it deposits of solids in the condensate
as shown in Figure 37 on page 50. Minimum drainage system.
trap dimensions MUST be accommodated. 8. Provide the ability to prime the trap. During initial
3. The condensate drain line size must be the full and seasonal start-up, trap inspection and priming
line size of the heat exchanger drain connection. is required. Condensate in the trap will evaporate
during long periods of non-use.
BURNER ASSY
ID
MOTOR
FLOW 2
1 FIELD INSTALLED CONDENSATE
3 DRAIN PIPING - BY OTHERS
4
2 CLEAN OUT
1 LD12912
50 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
For small sizes such as 1/2” iron pipe, 4. Paint raw edges of sheet metal with cold galva-
1/2” conduit or 5/8” O.D. copper and nized paint.
smaller; it is acceptable to use caulk in- 5. Select appropriate grommet for new panel hole
stead of a grommet. and cut out appropriate hole diameter for penetra-
tion with an exacto knife.
6. After paint dries, Install grommet into panel hole
Tools Required opening.
• Drill motor. 7. Apply sealant all around new hole opening behind
• Pilot starter bit. lip of grommet, on both sides of panel.
• Hole saws-approximately 2 1/2 in., 3 1/4 in. and 4 8. Run pipe or conduit through grommet and make
1/2 in. diameter for holes. appropriate connections.
• Power cords as required. 9. All modified panels must provide integrity equal
to original equipment specifications.
Material Required
10. Reconnect any components, bulkheads or other
• Neoprene grommet, 2 1/2 in., 3 1/4 in., 4 1/2 in. or fixtures that were disconnected from panel in step
5 1/2 in. as required. # 1.
• Cold galvanized paint. 11. Thoroughly clean up inside and outside air unit.
• Touchup spray paint, champagne, P/N 044-03504-
000 (for outdoor unit exterior only).
• Caulk, YORK P/N 013-03317-050 aluminum
gray or 013-03317-040 for outdoor units with
champagne paint.
• Exacto knife.
• Clean up supplies.
JOHNSON CONTROLS 51
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
PART PART NUMBER Use only metal cutting hole saws and/or
Caulking Gray 013-03317-050
blades to make penetrations thru panels.
Never use a cutting torch due to foam
Champagne 013-03317-040
insulation.
Champagne Touch-up
044-03504-000
Spray Paint
For these and all other parts contact York Product Service at
814-479-4005
52 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD16607
JOHNSON CONTROLS 53
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Motors for Supply, Return, and Exhaust Fans In some applications, only three bolts
A motor connection diagram may be found on the in- need to be removed. The fourth bolt,
side of the motor terminal box or on a tag attached to located on the opposite side of the electri-
the motor. Be sure to make a flexible conduit connec- cal box, does not have to be removed but
tion at the motor to permit fan belt adjustment and will need to be loosened. After it is loose,
movement of the spring isolated fan assembly. Refer to rotate the motor to access the electrical
the motor data nameplate for all motor specifications box to make the connections.
as shown in Figure 40 on page 54.
2. Remove the belts.
3. Rotate the motor or move it back far enough to
access the electrical box.
4. Connect the motor wiring per the motor wiring
diagram.
5. Replace the motor electrical box cover.
6. Rotate or move the motor back into place and se-
cure it to the base with the bolts.
7. Reinstall the belts to the proper alignment and
tension according to the drive kit label found on
the fan assembly.
Baldor
ELECTRICAL
BOX LD16561
54 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD12591
size and burner configurations. Burner voltage is se- Figure 45 - MAIN POWER AND CONTROL PANEL
lected to match the primary AHU voltage. Modulation WITH COVER OPEN
control voltage 2-10 VDC is standard.
DRAFT DAMPER
ADJUSTABLE
INSIDE GAS QUADRANT
BURNER PIPE
CHASE
ID FAN
ID FAN MOTOR
BURNER CONTROL
PANEL
LD11596b
JOHNSON CONTROLS 55
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Power Options
The available power options are listed below:
MAIN
• 460V-3PH DISCONNECT
SWITCH
AIRFLOW PROVING
• 208/230V-3PH SWITCH
• 380V-3PH
CONTROL VOLTAGE
• 575V-3PH TRANSFORMER
56 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 57
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
BLOWER HEATER
AIR FLOW
HEATER BLOWER
AIR FLOW
LD12470
58 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 59
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
It's the installer's responsibility to wire this device be- Figure 51 - SUPPLY POWER KNOCKOUTS
cause this device is not included in the single point
power option.
All AHU penetrations must be sealed to prevent air and
Figure 50 on page 60 represents a typical electric water leakage. Refer to the Penetrations and Grommet
humidifier panel layout. The supply power knockout is Details section in the service manual.
located in the bottom of the electrical panel as shown
Field provided disconnects must provide circuit pro-
in Figure 51 on page 60. All conduits beginning or
tection according to the humidifier nameplate. All field
ending on the inside of the pressurized or conditioned
wiring to the humidifier must be in accordance with
areas (i.e. AHU) must have the conduit openings sealed
NEC and local codes.
to prevent air from passing through it.
HUMIDIFIER
Control wiring diagrams are located in the humidi-
fier manufacturer's operator's manual, which can be
found inside the control panel or it is attached. Factory
package control drawings may not include humidifier
points as shown in Figure 52 on page 60.
LD11725
60 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
COIL PIPING
Do not test, clean and flush piping through Application Notes - All connections are male pip-
this equipment. ing threaded except DX coils, which are soldered.
Drain and vent taps on water coils are pipe thread, and
Isolate this equipment from pressure test-
shipped with plugs installed. These taps are installed
ing of water, steam gas and air piping.
approximately two in. back from the end of the thread-
ed connections. Install the pipe for balanced flow and 3
1. Consult the job specifications and submittal to assure even airflow.
drawings for specific piping requirements, coil
Staggered Coils
connection sizes and location. The AHU should
be level to assure proper venting and draining of Staggered coils in the AHUs equipped with an optional
coils. The piping arrangements must provide for expanded cabinet will have connections brought to the
a balanced flow in multiple coil installations as AHU exterior for liquid or steam coils as shown in Fig-
shown in Figure 53 on page 61. ure 54 on page 61. DX coils are not included.
STEAM IN The external connections are a threaded pipe or grooved
pipe for the contractor to make his connections when
the media is liquid, or a threaded pipe when the media
is steam.
AIR
FLOW It's the installing contractor's responsibility to insulate
CONDENSATE the piping extensions inside the AHU.
OUT
LD16562
JOHNSON CONTROLS 61
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
ECCENTRIC CHILLED
RETURN REDUCER WATER
UNION
RETURN
COIL
SUPPLY
STRAINER
REDUCING CHILLED
DRAIN
TEE WATER
GLOBE SUPPLY
UNION VALVE
RETURN
COIL
SUPPLY
PT GATE
PLUG VALVE
GATE VALVE W/ LD12470
HOSE BIB
62 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
PT GLOBE
VENT 2 WAY CONTROL VALVE
PLUG VALVE
ECCENTRIC HOT
RETURN REDUCER WATER
RETURN
COIL 3
SUPPLY
STRAINER
DRAIN HOT
GLOBE WATER
UNION VALVE SUPPLY
RETURN
COIL SUPPLY
PT GATE
PLUG VALVE
GATE VALVE W/
LD13791
HOSE BIB
Figure 57 - HOT WATER PIPING WITH TWO-WAY VALVE EXAMPLE (NOT FOR CONSTRUCTION)
PT GLOBE
VENT REDUCING
PLUG TEE VALVE
RETURN HOT
WATER
UNION RETURN
COIL
SUPPLY ECCENTRIC
REDUCER STRAINER
RETURN
COIL SUPPLY
PT GATE
PLUG VALVE
JOHNSON CONTROLS 63
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
WATER TREATMENT • Install the coil casing level with the return down.
A coil must be sufficiently elevated to allow a 12
Any copper tube coils may be attacked by acid con-
in. minimum drop between the return connection
densate. Treat the coils with boiling water and CO2 to
on the coil and the trap. More than a two inch drop
remove the condensate, and to assure longer tube life.
is required to protect the coil from freezing. The
Freeze Protection return main should be located below the trap.
Chilled water, hot water, and steam coils can be dam- Steam Control
aged during freezing weather. Take the following pre- Continuous steam supply ensures long coil life and
cautionary measures to prevent freezing: minimizes potential trapping, venting and freezing
• Positive coil freeze protection must be used in problems. A rapid cycling of the modulating steam
installations where any part of the water coil is supply or a frequent on-off steam supply control re-
subjected to temperatures of 32°F or lower, which sults in repeated thermal and piping stresses which will
may be accomplished by using a suitable anti- shorten the coil life. Modulating steam control valves
freeze solution. If the coil is not in use, it is rec- must not be oversized, and must be carefully selected.
ommended to drain the coil completely, and blow A substantial variation in the supply pressure will re-
dry the inside of the tubes with compressed air. quire installing a pressure-reducing valve ahead of the
automatic control valve.
• After draining, flush the coils with an anti-freeze
solution such as 50% glycol and 50% water, which Light load operation with a modulated steam supply
will protect from the coil from freezing to approx- can be improved by the installation of a vacuum break-
imately -35°F at sea level. Refer to ASHRAE and er check valve. An open relief line to the atmosphere
ARI guidelines for more information. from the return line near the coil is desirable, except on
vacuum systems.
• During winter when shutdowns such as power
failure, night and weekend shutdowns may occur, With a modulated steam supply, it is not practical to lift
install the controls so the return air dampers go to the condensate to an overhead return. Locate the coil
the fully open position, and all fresh air dampers well above the return, or provide condensate unit, or a
go to the fully closed position. A source of aux- boiler return trap below the coil.
iliary heat must be maintained inside the AHU
cabinet. Individual control valves are required on each coil in-
stalled in series with respect to airflow. When a modu-
• Other protection can include electromechanical lating steam valve supplies two or more coils in paral-
switches and constantly flowing water; however, lel, with respect to airflow, the piping must be designed
Johnson Controls will not be responsible for any to provide uniform steam distribution to each coil.
coils damaged by freezing.
Steam Traps
Steam Coils
Use the following information to select the correct
The operation of steam coils is dependent on airflow steam trap.
quantity and temperature as shown in Figure 59 on
page 65. Consult the job submittal form for the in- • Float and Thermostatic (F and T) traps are recom-
formation specific to this AHU. mended for all low or medium pressure applica-
tions.
Steam Distributing Coils
• Use thermostatic traps only for air venting, for
Use the following instructions to clean the steam dis- outdoor applications where a F and T trap might
tributing coils: be subject to freezing.
• Do not bush or reduce the coil return pipe size. • Use bucket traps only for a non-modulated steam
supply.
• Use a full size return pipe to the bottom of a dirt
pocket. The supply pipe may be reduced at the • Size the steam traps in accordance with the manu-
coil connection, if necessary. facturer's recommendations (usually several times
the steady state steam flow).
64 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
• Use the actual operating conditions (coil pressure • Locate the trap at least 12 in. below the coil return
vs. return pressure) to select a trap. connection, and lower it when freeze protection is
required. Do not attempt to lift condensate modu-
• It is preferable to provide an individual trap for
lated steam supply.
each coil, but a single trap may be used for coils
operating in parallel with respect to the airflow.
Coils in series with respect to airflow must be 3
supplied with individual traps.
SYMBOLS FOR "SS" STEAM
IN COIL PIPING ARRANGEMENTS
Y MA VACUUM
P PL BRAKER
SU DRIP TRAP STE AM COI L 1/2" CHECK GATE VALVE
FOR END OR PITC HED IN CAS ING VALVE
VENT TO LOW POINT (OPTIONAL)
ATMOSPHERE OF SUPPLY
CLOSE TO MAIN DIRT
UNIT (NOT ON POCKET
STRAINER
VACUUM (FULL SIZE
RN
SYSTEMS) E TU IN OF COIL
R A 12" MIN. CONN.)
M
VACCUM
BREAKER CONTROL VALVE
1/2" CHECK (MODULATING OR
AIN TWO POSITION)
YM STEAM COIL VALVE
P PL
SU PITCHED IN CA
(OPTIONAL)
SING 12" MIN.
F & T TRAP CHECK VALVE
F LOW
AIR W
FLO
AIR 12" MIN.
12" MIN.
12" MIN.
COILS IN PARALLEL AIR COILS IN SERIES AIR FLOW
FLOW MAY HAVE COMMON MUST HAVE INDIVIDUAL IN
SUPPLY AND SINGLE TRAP TRAPS AND CONTROL MA
(INDIVIDUAL COIL TRAP M AIN RN
RN
VALVES TU
PREFERRED) U RE
R ET LD04887a
JOHNSON CONTROLS 65
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Shipping Bolts (VIFB Only) The outside air and return air must be thoroughly
mixed before passing over the coil. When freezing air
Return steam condensate headers or hot water supply
enters only part of the coil, it creates a greater hazard
and return headers are securely bolted to lower mount-
than when the airflow entering the coil is a uniform
ing brackets to prevent damage to the header and tubes
temperature.
during shipment and piping of the coils. Remove the
bolts before applying steam or hot water, but after Coils used in series with respect to the airflow must
making all of the piping connections, as shown in Fig- have individual controls with ample space between the
ure 61 on page 68. coils for sensing devices, when required. Coils with
two or more rows are more sensitive to freezing than
Piping Suggestions single row coils.
Read the following information before installing the
On outdoor AHUs, locate the low limit at least 24 in.
piping.
downstream of the leaving edge of the VIFB/IFB cas-
• Support the steam and hot water field piping sep- ing. The low limit element must cross the face and by-
arately after the flexible connector to isolate the pass areas and be parallel to the headers.
piping strains and additional expansion from the
Refer to the IFB/VIFB operator's manual (provided)
coils.
for additional piping details. The Johnson Controls
• Insulate the internal steam manifolds and piping. factory does NOT pipe the connections to the AHU
exterior.
• Size the steam traps three times the calculated
condensate loading at the coil design conditions,
based on the pressure differential across the trap,
not the boiler pressure. Traps should be of types
that pass condensate and air at saturated steam
temperature. Inverted bucket traps should incor-
porate thermostatic air vents.
• Make the return connection full size as required,
and reduce only at the trap. Do not use the reduc-
ing bushing on the coil return connection.
66 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
STEAM IN
3
FACE DAMPERS
CLOSED
ACTUATOR
BYPASS OPEN
STEAM OUT
LD09630
Figure 60 - IFB COIL (HORIZONTAL TUBES AVAILABLE WITH STEAM AND HOT WATER)
JOHNSON CONTROLS 67
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
VIFB
HOT WATER COIL AIR
SUPPLY FLOW
HOT WATER
RETURN
FLEXIBLE
CONNECTOR DRAINS
LD09632
LD09631
AIR
W
FLO
HOT WATER
RETURN
68 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
CONDENSATE CONDENSATE
FLOW FLOW
T
VIFB AIR FLOW
1/4 IN (6.4 MM)
PETCOCK
12 in MIN. COIL
CRACKED OPEN (304.8 mm)
STRAINER FOR CONTINUOUS
AIR VENTING
8 in (203.2mm) MIN
T
8 in (203.2mm)
CHECK STRAINER
VALVE FLEXIBLE CONNECTOR INSTALLED PARALLEL
INVERTED BUCKET TRAP TO COIL HEADER AND AS CLOSE AS POSSIBLE
RETURN MAIN TO COIL CONDENSATE CONNECTION.
LD09634
JOHNSON CONTROLS 69
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
70 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Txv Equalizer
Line
Sporlan Asc Suction Line
Thermal Expansion Valve
Hot Gas
Fitting Sight Glass
Txv Equalizer
Line
Suction Line
1-7/8"
45°
Mount thermal expansion valve bulb on side of Construct suction line P-trap from street fittings to
horizontal run of suction line as shown. Insulate bulb maintain minimum trap volume.
/ line after clamping bulb to line. LD05171a
Legend Refrigerant In
Refrigerant Out Warm Air Cold Air
LD03319b
JOHNSON CONTROLS 71
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
H2
H1
D2
H2
D1 D2
D1
H1
2 Distributor 2 Distributor
Circuits Face Split Circuits Row Split
D2 H6 H5 H2 H1
D2 H3 H1 D2
D6
H2 H1 D2 D5 D1
D4
D3 D1
D4 H8 H7 H4 H3
D8 D4
D1 H4 H3 D3 D1
D7 D3
D3 H4 H2
72 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
D2
H2 H1
D1
3
D4
H4 H3
D3
4 Distributor LD09145a
Single H2
Single H2
HDR H1
HDR H1 H2
D2 D2 Body
Body
D1 Single D1 D2
H1
HDR
Body
D1 D1
H1
Single D2 H6 H2 H1 H6 H5 H2 H1
HDR H3 H1 D6 D2
D2
Body D6 D5
D4 D2 D1
D1
D3
Single
HDR
H5 H4 H3 H8 H7 H4 H3
Body
D4 D8 D4
D1 D3 D1 D5
H2 D3 D7 D3
H4
JOHNSON CONTROLS 73
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
THERMOSTATIC EXPANSION VALVES (TXV) If one coil circuit is used as shown in Figure 72 on
page 74, the LLSV and TXV must be sized to handle
Each coil distributor circuit requires its own thermal
the full capacity of the refrigerant circuit. When two
expansion valves (TXV), and condensing AHU circuit
coil circuits are used per refrigerant circuit as shown
requires its own liquid line solenoid valve (LLSV).
in Figure 73 on page 74, each TXV should be sized
Equip TXVs with external equalizer tubes that are field
to handle half of the capacity of the refrigerant circuit,
connected to the suction line. Size the valve according
and the LLSV should be sized to handle the full capac-
to the valve manufacturer's recommendations, allow-
ity of the refrigerant circuit.
ing approximately 35 psi ( throughout the coil and dis-
tributor at full load).
Do not oversize the valve. Follow the valve manufac-
turer's instructions to find the thermostatic bulb. Proper
2
expansion valve operation is necessary in order to real- 2
ize the rated coil capacity.
4
When a DX type coil is operated with a suction temper-
ature below 32°F, a buildup of frost will occur on the
finned surface. It is not recommended to operate DX
coils for air conditioning purposes at below freezing 1
suction temperatures. If the full load operating point
for the coil is selected at a safe temperature, a system 1
analysis is required to check for the lowest probable
suction temperature at light load conditions.
3
HOT GAS BYPASS (HGBP) Four Circuits Two Circuits NOT
Recommended Recommended
When using discharge air temperature control or sys- LD09147a
tems with outside air economizer cooling, always in- Figure 71 - STACKED COIL CIRCUITING
clude hot gas bypass (HGBP). It is not as critical to
use HGBP with return duct air temperature or suction
pressure control, but it provides better capacity control 100% Capacity
at low loads.
The Venturi type distributor furnished with the DX
coils may be ordered for field application of an HGPB.
The connection may be made through a tee installed Condensing Unit
DX Coil
in the field between the expansion valve and distribu- LD09148
tor. The system balance point and control adjustments Figure 72 - ONE COIL CIRCUIT PER
must assure compressor cooling and avoid excessive REFRIGERANT CIRCUIT
compressor cycling. Refer to Guidelines for Proper
Application Piping and Split Systems (Form 050.40- Compressor #1
ES3) for compressor staging solutions.
TXV
DX COIL CIRCUITING AND STAGING TXV LLSV
On stacked coils, use a minimum of four coil circuits to
Compressor #2
achieve full face control as shown in Figure 71 on page Condensing Unit
74. When the condensing AHU has two compressors DX Coil LD09149
74 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
When the condensing AHU has three compressors per The second set of three compressors would be tied into
circuit, use two coil circuits for each refrigerant circuit LLSV2, TXV3 and TXV4 to maintain full-face control
as shown in Figure 74 on page 75. Each coil circuit at higher loads. Refer to Guidelines for Proper Appli-
must have a dedicated TXV and distributor to handle cation Piping and Guidelines for Split Systems (Form
one coil circuit, and the LLSV should be sized to han- 050.40-ES3) for compressor staging solutions.
dle the full capacity of the refrigerant circuit. Connect
the HGPB line to all distributors in the coil circuit. Advantages of Multiple Control Stages 3
The more control stages used, the more precise the con-
Compressor #1 trol of the air temperature will be. Smaller incremental
TXV changes in capacity will result in a more consistent DX
Compressor #3
Feeds Both Circuits LLSV
coil leaving air temperature, which will eliminate tem-
perature swings in the conditioned space and improve
TXV
Compressor #2 the comfort level. But more importantly, a consistent
Condensing Unit
space temperature is crucial to many process applica-
LD09151 tions.
Figure 74 - THREE COMPRESSOR UNIT The smaller changes in capacity that result from us-
ing a greater number of control stages will also extend
In a stacked coil with four coil circuits piped to a con- equipment life. The most important thing to remember
denser with six compressors, the coil circuits would be is to maintain full-face control of the coil at all cooling
face split and interlaced with two interlaced circuits on loads. When row split coils are used, make sure that
the lower coil section and two on the upper section as the first LLSV is energized with the last coil circuit in
shown in Figure 75 on page 75. the leaving air stream, which is always the last one de-
Comp 1 - 3 energized too.
TXV1 MAINTAINING ADEQUATE AIRFLOW
TXV3 LLSV1 An electrical interlock between the AHU and the con-
Comp 4 - 6
denser must be included for permissive run of the
Comp 1 - 3 LLSV2 condenser. In addition, a differential pressure switch
Condensing Unit
mounted across the supply fan must always be includ-
TXV2
ed to ensure airflow across the coil before the condens-
ing AHU is energized. The condenser must never be
TXV4
Comp 4 - 6
operated unless the AHU fan is operating and air is
DX Coils LD09153 flowing across the active coil. Insufficient airflow will
Figure 75 - SIX COMPRESSOR UNIT result in liquid refrigerant returning to the condensing
AHU, which could damage the compressors by liquid
When sizing TXVs, size the TXV for the refrigerant slugging or washing oil from the bearing surfaces.
circuit tonnage divided by the number of DX coil liq-
uid distributors, which should be equal to or smaller In variable volume systems, the minimum acceptable
than the calculated value. airflow for fixed speed or variable air volume (VAV)
systems is 350 FPM face velocity across each DX coil,
The first three compressors would be tied into LLSV1, as applied to split DX systems. Make sure that the TXV
TXV1 and TXV2, which would provide full face con- does not overfeed, because it could cause compressor
trol of the coil at the lowest cooling loads. Both dis- failure.
tributors on each coil circuit would include auxiliary
side connectors for HGBP. The air velocity flowing through chilled water and di-
rect expansion coils must not exceed specific recom-
mended values to prevent water carryover.
JOHNSON CONTROLS 75
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
76 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Drain
Pan Trap H = Positive SP + 1 in. Drain
Drain (Plus loaded filters) Connection
Nipple
No.1 - Fan Off
Drain
Pan
3
H
X X= 1/2 H
Traps
LD06345
JOHNSON CONTROLS 77
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
DUCT CONNECTIONS
The duct must have a positive seal to the AHU open- Note: Make Turns In
ings. Outdoor bases are available in 6, 8, 10, or 12 in. The Same Direction Air
height. It is the contractor's responsibility to provide As Fan Rotation Flow
the ductwork, which includes the base rail height, and
support it independently from the AHU.
Effective Duct Length
Flow
Duct Connection Guidelines
Air
The duct connection guidelines are as follows:
Air
• Duct connections to the AHU may be made di- Flow
rectly except when the AHU has external isola- Air
Flow
tion. Then the duct connections should be made
with flexible material, and be installed so they are Turning Vanes
sufficiently loose. LD06335
78 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Detail A
Gasket
Or
Sealant
Gasket Or Sealant
Flanged Duct
Raw Edge Duct
LD014087
The performance ratings of coils will be met only if the In applications where sound and vibration transmis-
airflow is uniform over the face of the coils. High air sions may be objectionable, good acoustical engi-
velocity spots on the coil may cause carryover of mois- neering practices must be incorporated in the system
ture from the coil. High or low air velocity areas of design. On AHUs with return fans, it is important to
the coil will not deliver the published ratings. The duct consider the effects of sound transmission into the air-
connections must be designed to provide for uniform conditioned space.
flow of air across the face of the coil. The entering duct
must provide a smooth transition from any high veloc- When a AHU is used with a ceiling plenum return
ity effects. Stratifications of outside and return air, es- air system, sound may be transmitted from the AHU
pecially where below freezing outside air enters, must through the ceiling to the air-conditioned space. For
be avoided to prevent coil freeze-up or nuisance low such applications, install a sound absorption chamber
limit trips. near the AHU return air inlet. Various reference sourc-
es are available regarding acoustic design.
Sound and Vibration Transmission
Installing Top Discharge Outdoor AHU Duct
All roof-mounted AHUs generate some sound and vi-
bration, which may or may not require special treat- For outdoor AHU top duct connection, the installer is
ment of the air-conditioned space. The noise generated responsible for sealing the duct to the roof panel. The
by the AHU depends on the following: installer should not seal the duct to the unit opening.
JOHNSON CONTROLS 79
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Counterflashing
Curb
Base Flashing
Roofing Plies
Deck
Cant Strip
LD06494a
80 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
JOHNSON CONTROLS 81
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD13303c
82 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Note: When filters are supplied by other companies, the filter clips are supplied as well.
JOHNSON CONTROLS 83
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Note: When filters are supplied by other companies, the filter clips are supplied as well.
84 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
Filter Installation
Installing a 2 in. Pleated Filter
Use the following instructions to install a 2 in. Multi-
Pleat Elite filter into a 16 g galvanized holding frame
with four latches (P/N 026-35788-702), as shown in
Figure 85 on page 82. 3
1. Install one latch at each corner (4 corners) of the
frame. The latch fits into two rows of three knock-
outs. Use the row of knockouts closest to the gas-
ket for nominal 1 in. filters or filters with a 13/16
LD10174
in. single header. Use the second set of knockouts
for nominal 2 in. filters. Figure 87 - FULLY INSTALLED FILTER
2. Insert the straight end of the latch between the two
knockouts furthest from the corner. Installing a 4 in. Pleated Filter
3. Using a moderate amount of pressure, force the Use the following instructions to install a 4 in Micro-
latch over the third knockout. The latch should MAX filter into a 16 g galvanized holding frame with
now be trapped within the three knockouts, but four latches (P/N 026-35778-604), as shown in Figure
should be able to freely rotate as shown in Figure 85 on page 82.
86 on page 85.
1. Install one latch at each corner (4 corners) of the
4. The latch installation should be complete.
frame. The latch fits into two rows of three knock-
outs. Use the row of knockouts closest to the gas-
ket for nominal 1 in. filters or filters with a 13/16
in. single header. Use the second set of knockouts
for nominal 2 in. filters.
1. Insert the straight end of the latch between the two
knockouts furthest from the corner.
2. Using a moderate amount of pressure, force the
latch over the third knockout. The latch should
now be trapped within the three knockouts, but
should be able to freely rotate as shown in Figure
88 on page 85.
3. The latch installation should now be complete.
LD10171
JOHNSON CONTROLS 85
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
4. Install the other three latches into the corners. 3. Using a moderate amount of pressure, force the
latch over the third knockout. The latch should
5. Rotate all of the latches outward, and insert the
now be trapped within the three knockouts, but
filter into the frame.
should be able to freely rotate.
6. Grasp the loose end of the latch, and place it over
4. The latch installation should be complete.
the filter frame so that the latch secures the fil-
ter into the frame as shown in Figure 89 on page 5. Rotate the latches outward, and insert the SH filter
86. into the frame. Insert the bulk of the filter through
the frame, protruding out the backside. Only the
header of the filter should be contacting the flange
of the frame.
6. After the filter is placed into the frame, grasp the
circular end of the latch and rotate it across the
corner of the filter.
7. Push the end of the latch towards the filter, until
the latch catches beneath the frame knockout.
8. Repeat the process with the remaining latches.
9. The filter should now be securely installed into
the frame as shown in as shown in Figure 90 on
page 86.
LD10179
86 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
3. Using a moderate amount of pressure, force the 1. Install the two latches on each side of the frame,
latch over the third knockout as shown in Figure not on the top or bottom. Refer to the sets of
91 on page 87. knockouts in Figure 93 on page 87 that should
be used for the latches.
LD10150
LD10496
2. Insert the straight end of the latch between the two
knockouts furthest from the corner.
Figure 91 - CORRECTLY INSTALLED LATCH PIN
(P/N 026-35788-604) 3. Using a moderate amount of pressure, force the
latch over the third knockout.
4. Grasp the loose end of the latch, and place it over
the pre-filter frame, so that the latch secures the 4. The latch installation should be complete. The
pre-filter to the SH filter. latch should now be trapped within the three
knockouts.
5. Repeat the process with the remaining latches.
5. Repeat the steps with the remaining latches. Note
6. The filters should now be securely installed into the orientation of the latch to the knockouts as
the frame as shown in Figure 92 on page 87. shown in Figure 94 on page 87.
LD10160
LD10154
Figure 92 - CORRECTLY INSTALLED CARTRIDGE
WITH PLEATS Figure 94 - CORRECT LATCHOUT/KNOCKOUT
CONFIGURATION
Installing a Multi-Cell SBM Double Headered 6. After the latches are installed, the frame should be
(DH) Filter configured as shown in Figure 95 on page 88,
Use the following instructions to install a Multi-Cell which shows there are two latches per side, none
SBM double header (DH) filter (nominal 12 in.) into a on the top or bottom.
16 g galvanized holding frame with four latches (P/N
026-35788-612), as shown in Figure 85 on page 82.
JOHNSON CONTROLS 87
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD10154
88 JOHNSON CONTROLS
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
LD10165
JOHNSON CONTROLS 89
FORM 102.20-N3
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
ISSUE DATE: 12/17/2021
AIRFLOW
AIRFLOW
FILTER RETAINER
CLIPS MUST BE
ATTACHED TO
SIDES ONLY
SEE DETAIL A
HAT
FILTER CLIP INSTALLATION
FLAT SEALING
GASKET SEAL
SURFACE
HEPA FILTER
HOLDING FRAME
GASKET
GASKET SEAL
DETAIL A
90 JOHNSON CONTROLS
FORM 102.20-N3
ISSUE DATE: 12/17/2021
TEMPERATURE
To convert degrees Fahrenheit (°F) to degrees Celsius
(°C), subtract 32° and multiply by 5/9 or 0.5556.
Example: (45.0°F - 32°) x 0.5556 = 7.22°C
To convert a temperature range (i.e., a range of 10°F)
from Fahrenheit to Celsius, multiply by 5/9 or 0.5556.
Example: 10.0°F range x 0.5556 = 5.6 °C range
JOHNSON CONTROLS 91
5000 Renaissance Drive, Pennsylvania USA,17439 1-800-524-1330 Subject to change without notice. Printed in USA
Copyright © by Johnson Controls 2021 www.johnsoncontrols.com ALL RIGHTS RESERVED
Form 102.20-N3 (1221)
Issue Date: 12/17/2021
Supersedes: 102.20-N3 (1218)