You are on page 1of 14

®

High Efficiency Filter Standards

USA EUROPE
YEAR Eurovent Italy Germany Great Britain France

NBS 1950
1952
1953
1954
1955
AFI 1956
1957 BS 2831
1958
1959
1960
1961
1962
1963
1964
1965
1966
1967
ASHRAE 52/68 1968
1969
1970
1971
1972
1973
1974
1975
ASHRAE 52/76 1976
1977
1978 UNI 7832
1979 EUROVENT 4/5
1980 DIN 24185
1981
1982 AFNOR X44-011
1983
1984
1985 BS 6540
1986
1987
1988
1989
1990
ASHRAE 52.1-91 1991
1992 EUROVENT 4/9
1993
1994 CEN EN 779
1995
ASHRAE 52.2 P 1996 EUROVENT 4/10
1997
1998
1999
2000
2001 pr EN 779

193
filtration
®

Absolute Filter Standards

USA EUROPE
YEAR Eurovent Italy Germany Great Britain France
1950
1952
1953
1954
1955
Mil.Std 282 1956
1957
1958
1959
1960
1961
1962
1963
1964
1965
1966
1967
1968
1969 BS 3928
1970
1971
1972 AFNOR X44-011
1973
1974 DIN 24184
1975
1976 EUROVENT 4/4
1977
1978 UNI 7833
1979
1980
1981
1982
IEST-RP-CC-001-83-T 1983
1984
1985
1986
1987
1988
1989
1990
1991
IEST-RP-CC-007.1 1992
IEST-RP-CC-001.3 1993
1994
1995 UNI 10339
1996 DIN 24183
1997
1998
IEST-RP-CC-0034.1 1999
2000 CEN EN 1822

194
filtration
®

Air filter testing


methods

Classification of air filters As we have said, the test includes


two methods: a gravimetric one, used for
Air filter classification is regulated coarse filters, and the opacimetric one for
by a series of very strict standards that filters with medium-high efficiency rates.
specifically define the features of the filters The gravimetric method uses standard
according to the relevant efficiency class synthetic dust whereas the opacimetric
and use. one is carried out by using the natural
The designer and the installation technician dust in the air.
must know all these standards to be able The first is more suitable, within certain
to propose the filter that best meets the limits, to study the performances
project requirements. of filters that will be used mainly to treat
Below, are the main standards used today re-circulating air, generally richer
with a series of tables that indicate in fibrous dusts.
the efficiency class of each filter. The tests are used to establish the
Before starting, we want to remind you that arrestance of coarse filters and
the air filters considered by the standards the efficiency of medium and fine filters;
belong to three main groups: furthermore, they also allow us
• coarse to determine:
• fine • the pressure drop trend in clean filters
• absolute: these are then divided into • the pressure drop trend according
two different classes: to the dust build-up
HEPA (High Efficiency Particulate Air filters) The arrestance or the separation efficiency
ULPA (Ultra Low Penetration Air filters). does not remain constant with
the progressive build-up of dusts
Industrial dust exhaust systems and other on the filter: it can increase or decrease
similar products are not contemplated by according to its characteristics.
these standards. Specific tables have been Tab. 2 indicates the equivalence
created for these products based on the between CEN EN 779 classes
experience of the industry and can be and UNI 10339 classes.
found at the end of this section.

Tab. 2 Equivalence between CEN EN 779


CEN EN 779 Standard and UNI 10339
This standard is based on the Filter Filter
Eurovent 4/5 Standard and class class Filtration
on the ASHRAE 52-76 Standard. CEN EN 779 UNI 10339 efficiency
It aims at determining: the efficiency
of medium and fine filters with atmospheric G1 1 M
coarse

dust by using an opacimetric system G2 2 M


and the arrestance of coarse filters with G3 3 M
synthetic dust by using a gravimetric G4 4 M
method. The CEN standard has a double
classification system that uses letters F5 5 A
and numbers: G and F, respectively, F6 6 A
fine

for coarse and fine filters, followed F7 7 A


by numbers, from 1 to 9. See tab. 1. F8 8 A
It recalls the division of the filters in different F9 9 A
classes from EU1 to EU9, according to the
arrestance and efficiency from the previous
and now obsolete Eurovent 4/5 Standard.

Tab. 1 Classification of coarse and fine filters according to CEN EN 779 and EU 4/5
Average Average Final Class*
arrestance opacimetric pressure
with synthetic efficiency drop
dusts
Type of filter CEN EN 779 Am% Em% Pa Eurovent 4/5
G1 Am < 65 250 EU 1
coarse G2 65 < Am < 80 250 EU 2
G3 80 < Am < 90 250 EU 3 LEGEND
G4 90 < Am 250 EU 4 Am = Average arrestance referred
F5 40 < Em < 60 to the Weight /Gravimetric method
450 EU 5 Em = Average efficiency referred
F6 60 < Em < 80 450 EU 6 to the Colorimetric /Opacimetric method
fine F7 80 < Em < 90 450 EU 7
F8 90 < Em < 95 EU 8 * According to the EUROVENT 4/5
450 classification that does not specify
F9 95 < Em 450 EU 9 the final pressure drop

195
filtration
®

Air filter testing


methods

ANSI / ASHRAE 52.2P Standard The testing bench of the ANSI / ASHRAE
52.2P Standard is mainly made of a:
This standard determines the fractional fan, two series of filters positioned upstream
efficiency of all types of filters and and downstream of the filter being tested,
the arrestance for coarse filters. an aerosol generator, an aerosol sampling
Besides the standard, there is also system with opacimetric measuring device
a classification that is not part of and a calibrated nozzle.
the standard itself but it can be used During the test the filter must be filled with
at discretion. The main difference compared synthetic particles made of:
to the Eurovent 4/9 standard is: • 93.5% of SAEJ-726 Fine
• the size range of the particles (equivalent to Arizona road dust)
• the type of areosol • and 6.5% of cotton fibers.
• the classification system. The carbon black, used in the 52-76
standard, was eliminated because
For coarse filters the test is carried it is a conductor of electricity
out using synthetic particles to determine in the electrostatically charged filter tests.
the arrestance and with aerosol Fiber filters are loaded with synthetic dust
to determine the efficiency. For medium until they loose the final recommended
and fine filters the test is solely carried out pressure drop, whereas the electrostatically
through aerosol to establish the fractional charged filters are loaded with a pre-set
efficiency. The size range of the particles amount of particles.
generated by the aerosol goes from The criteria for the classification of the filters
0.3 to 10 micron. are those of lower efficiency during the test.
Up to 10 micron, which is the top limit,
the particles are considered breathable.
The aerosol, for the fractional efficiency For coarse filters and electrostatically
tests, is made of potassium chloride charged filters, the efficiency can decrease
(KCI), which produces solid particles during the test. According to the results,
used to measure the bounce effect, i.e. the filters are divided in 4 categories:
the breakaway of the particles from the filter • coarse C
and the following passage.
This is a common phenomenon for coarse • low efficiency L
filters and big diameter particles. • average efficiency M
• high efficiency H
Each group contains 4 sub-groups,
identified by numbers, for a total of 16
different classes of filters.
Tab. 3 Classification of filters according to the ANSI / ASHRAE 52.2P Standard While coarse filters are only tested with
Minimum efficiency % in the size range Arrestance Final synthetic dust according to the previous
of micron particles std. 52.1 pressure 52.1 standard, L, M and H filters are
µm µm µm drop tested in a particle size range
from 0.3 to 10 micron divided into three
Categ. Class 0,30 - 1,14 1,14 - 3,46 3,46 - 10,0 % Pa
groups with diameters:
• 0,30 - 1,14 micron
C1 - - Emin.< 20 Aavg < 65 150
• 1,14 - 3,46 micron
coarse

C2 - - Emin.< 20 65 < Aavg < 70 150 • e 3,46 - 10,0 micron.


C3 - - Emin.< 20 70 < Aavg < 75 150
Tab. 3 represents the classification
C4 - - Emin.< 20 75 < Aavg 150 of the filters obtained in the appendix
L5 - - 20 < Emin.< 30 - 150 of standard 52.2P.
efficiency

L6 - - 30 < Emin.< 45 - 150 The final pressure drop of the filters


low

L7 - - 45 < Emin.< 65 - 150 is double compared to the initial one or


at least equal to the value in the table.
L8 - - 65 < Emin.< 80 - 150
The features of the filter are expressed
M 9 - Emin.< 30 80 < Emin. - 250 through an indicator.
efficiency
average

M 10 - 30 < Emin.< 45 80 < Emin. - 250


M 11 - 45 < Emin.< 65 80 < Emin. - 250 EXAMPLE
M 12 - 65 < Emin.< 90 80 < Emin. - 250 M10/93/0.94
H 13 Emin.< 65 90 < Emin. 90 < Emin. - 350 means the filter belongs to class:
efficiency

H 14 65 < Emin.< 85 90 < Emin. 90 < Emin. - 350 M10


high

90 < Emin. and it has a filtration efficiency equal to:


H 15 85 < Emin.< 95 90 < Emin. - 350
93% (for particles between 3,46 ÷ 10,0µm)
H 16 95 < Emin. 90 < Emin. 90 < Emin. - 350 at 0,94 m3/s.

196
filtration
®

Air filter testing


methods

DOP MIL. STD 282 For performance values very close


to 100%, the relevant figures are not
This photometric method was studied significant. Instead the penetration
to test filters with high performance levels percentage allows for a wider extension
belonging to the HEPA (High Efficiency of the size.
Particulate Air Filters) and ULPA class (Ultra A particular application of the DOP method
Low Penetration Air Filter). is that related to the determination of any
The DOP Penetration Test is the most “leakage” due to pinholes in the filtering
important method used in the US and in the media or to tightness defects between
countries under their sphere of influence. the media and the frame.
The test aims at determining the filtration This test is called “Leakage (Scan) Test”
performance of the filter and and it is carried out using more or less
the penetration percentage of the tracer the same technique used for the DOP test.
particulates used in the test through The diversity lies in the fact that the test
the filter. probe, downstream of the filter, is right
The test is generally carried out for two by the filter and it is moved slowly around
air flow rates: the nominal one, declared the media/frame contact areas and through
by the manufacturer, and for a value equal the entire surface of the filter itself.
to 20% of the nominal value. The identification of a leakage point allows
The “tracer” substance used is dioctylptha- you to repair the problem by closing
late an oil with high boiling levels. the relevant area with special resins.
Its most important feature, in relation This test can be carried out also
to this test, is the uniformity of the diameter on the system, after installing the filter.
of the drops that are obtained after In this case you use a dioctylpthalate intake
the evaporation and subsequent mobile generator instead of the heavy
condensation of steam. thermal generator.
The drops produced have a uniform The only difference is the fact that the
diameter of 0.3 micron. drops forming the cloud do not have
Concentration is kept at around 80 mg/m3. a uniform diameter, and their average
The cloud of drops is dragged to the filter size is 0.45 –0.6 micron.
being tested. The air upstream and then However, to find “leakages” the size
downstream of the filter is tested. of the particulates is less critical than
The last test is carried out in a point where what is required to find the penetration
the air is mixed, so the particulates that value of the filter.
have passed through the filter are uniformly In the same way you can determine
distributed. tightness defects between the filter
The air taken upstream and downstream and the relevant housing system,
of the filter passes through a light diffuser which has to have the same qualities
photometer, which determines of the installed filter (see EUROVENT 4/8).
the concentration of the drops.
From the ratio between the concentration
upstream and downstream of the filter,
the penetration percentage
can be determined: EUROVENT 4/4 Standard
P = N x 100 As a result of the growing market
M demand for absolute filters many countries
felt the need to establish a standardization
where: P = penetration percentage; of the efficiency test.
N = concentration of drops In 1974 the European EUROVENT
downstream of the filter; Committee adopted the (English sodium
M = concentration of drops flame test – NaCI) depicted in the (British
upstream of the filter. Standards 3928) and called it Eurovent 4/4.
From the calculated penetration value, According to these standards the air filters
you can find the corresponding filtration are divided into 5 classes and can reach
performance value: the maximum efficiency of E ≥ 99,999 %
E = (1 - P) x 100 Sodium Flame Test.
See tab. 5
where: E = filtration performance; Other testing methods, based on different
P = filter penetration. principles, have been developed in various
By way of an example, we wish to indicate Countries and are usually accepted.
the correspondence between some They are shown in tab. 6.
penetration percentage values The equivalence with the UNI 10339
and the performance values Standard is shown in tab. 7.

Penetration Performance
5% 95 %
0,05 % 99,95 %
0,01 % 99,99 %
0,003 % 99,997 %

197
filtration
®

EUROVENT 4/9 method CEN EN 1822 Standard it was then established that each filter
certification ought to be based on this
For medium and high efficiency filters, For many years now filter manufacturers MPPS point (Most Penetrating Particle Size)
normally used in conditioning systems, have been producing and marketing filters which is the most critical.
the Eurovent 4/9 testing method, similar with efficiencies exceeding the limits The new standards classify the HEPA
to the ANSI / ASHRAE 52.2P Standard, is set forth for class EU 14 (Eurovent 4/4), (High Efficiency Particulate Air Filters) and
used to determine fractional efficiency, i.e. certifying the design performance ULPA (Ultra Low Penetration Air Filters)
the efficiency for particles with different on the basis of different innovative control filters separately: the first from H10 to H14,
size ranges. systems. and the second from class U15 to U17
Hence, it generates a series of efficiency On the other hand, several customers included, see tab. 4, determining
values according to the diameter especially the producers of integrated specifically, the activities for
of the particles as well as the final pressure circuits, were demanding more and more the implementation of control systems,
drop. This method replaces the standard sophisticated products capable to perform for the verification of the filtering media,
opacimetric method and measures very high efficiencies. for the test of the finished filter elements,
the efficiency of the filter for particles etc.
with a 0.4 micron diameter (particle test). As a response to this situation the
European Committee of Normalization Basically the test consists of a double
Fractional efficiency (fractional test) control: the first is carried out on the media
is measured for particles with a diameter set up a research group with the aim
of drawing up a standard discipline ruling and measures the size of the most
ranging from 0.2 to 5 micron, through penetrating particle (MPPS), verifying that
a laser counter. the matter.
The new standards, EN 1822 (based on the speed across the media is the same
Another difference compared to as during the actual operation.
the opacimetric test is that two different DIN 24183), are composed of 5 parts, each
dealing with one specific subject which is The second control is carried out on the
aerosols can be used for this test: finished product and determines the global
Latex or DEHS. described in detail. It was stated that any
single filtering media has a point of: MPPS efficiency.
The first, a polymeric vinyl acetate, is made
of plastic spherical particles; the second, • maximum penetration (or of lowest Filters with global efficiency over 99,95 %
diethylhexyl sebacate, is equivalent to the efficiency) according to a specific are to undergo an additional test on each
well known dioctylpthalate used in the DOP particle size point of their filtration surface with the aim
method. The efficiency testing bench of • variable according to: of finding out a possible leakage (pinholes)
the EUROVENT 4/9 method is similar - air flow velocity whose local penetration value should
to the one used for the ASHRAE tests. - media density no higher than 5 times (classes H13 - U16)
The air is filtered through a HEPA filter; - the diameter of the media fiber and 20 times (class U17) the global one.
downstream of the filter, a Latex or DEHS
particle generator produces the necessary
quantity of aerosol.
Two air samples are taken, both upstream
and downstream of the filter, which feed the
particle counter connected to a computer.
This computer checks the sampling both
upstream and downstream of the filter
controlling a solenoid valve.
The laser particle counter allows
to measure diameters up to 0.1 micron.
The behavior of the filter is determined
first when the filter is clean and then
after loading it with dust, when it reaches
a pressure drop level of 200 or 300 Pa.
This method uses a filter classification
system similar to the one used in Tab. 4 Classification of high and very high efficiency filters
the CEN EN 779 (which is appendix D of according to EN 1822 (and DIN 24183
EUROVENT 4/9). According to this
classification the filters are grouped in two Class global punctual efficiency
classes from EU1 to EU9. CEN EN MPPS efficiency Localized drop
The average arrestance values with 1822 % % DIN 24183
synthetic dust is indicated for coarse
filters from EU1 to EU4. H 10 85 - EU 10
For fine filters from EU5 to EU9 only the H 11 95 - EU 11
percentage efficiency referred to particles H 12 99,5 - EU 12
with a diameter of 0.4 micron is indicated. H 13 99,95 99,75 EU 13
The final pressure drop is 250 Pa for coarse
H 14 99,995 99,975 EU 14
filters and 450 Pa for fine filters.
The air flow rate is 0.944 m3/s (3400 m3/h) U 15 99,9995 99,9975 EU 15
when not specifically indicated U 16 99,99995 99,99975 EU 16
by the manufacturer. U 17 99,999995 99,9999 EU 17

198
filtration
®

Tab. 5 Classification of very high efficiency filters according to EUROVENT 4/4


Filter Initial efficiency Penetration Decontamination factor
class EI P DF
EU 10 95 < EI < 99,9 5 < P < 0,1 20 < DF < 1000
EU 11 99,9 < EI < 99,97 0,1 < P < 0,03 1000 < DF < 3000
EU 12 99,97 < EI < 99,99 0,03 < P < 0,01 3000 < DF < 10000
EU 13 99,99 < EI < 99,999 0,01 < P < 0,001 10000 < DF < 100000
EU 14 99,999 < EI 0,001 < P 100000 < DF
NOTE
The filter class must also indicate air flow rate (m3/h).

Tab. 6 Main testing methods for absolute filters


Testing method Aerosol Particle size µm Country
DOP MIL Std 282 DOP monodisperse 0,3 U.S.A.
UNI 7833 DOP / DEHS polidisperse 0,45 Italy
BS 3928 NaCl 0,65 Great Britain
EUROVENT 4/4 NaCl 0,65 Europe
AFNOR X44-011 Uranine 0,17 France
DIN 24 184 .1 Liquid paraffin 0,45 Germany
DIN 24 183 DEHS MPPS Germany
CEN EN 1822 DEHS MPPS Europe
IES-RP-CC 001.3 DOP 0,45 U.S.A.
IES-RP-CC 007.1 Various 0,1-0,2 U.S.A.

Tab. 7 Equivalence between EUROVENT 4/4 and UNI 10339


Filter class Filter class Filtration
EUROVENT 4/4 UNI 10339 efficieny
EU 10 10 AS
EU 11 11 AS
EU 12 12 AS
EU 13 13 AS
EU 14 14 AS

199
filtration
®

Application of
air filters

For a correct application of air filters you


need to know the type of dust and polluting
Tab. 8 Concentration of dust in outdoor air in different areas substances, and their concentration,
Average Most Maximum in outdoor and room air.
concentration frequent particle size For example, tab. 8 shows the average
particle size concentration and the typical sizes of the
Area mg/m3 micron micron dust particles in outdoor air, according
to the areas and the weather conditions.
humid weather 0,01 0,8 4 Special calculation procedures are used
Rural areas
dry weather 0,15 2,0 25 to select the right filter, especially
residential areas 0,4 7,0 60 for industrial use. In civil applications,
Urban areas more simply, yet with a good safety margin,
industrial areas 0,75 20,0 100
refer to tab. 9, of the UNI 10339 standard,
Distretti industriali e autostrade 3 60 1000 shown below.
ad alto scorrimento and over Use this table to choose the most suitable
air filters for most of the applications
in the civil sector.

Tab. 9 Filter classes and filtration efficiency for various categories of buildings
Classification of buildings per category Filter classification Filtration efficiency
minimum maximum
Residential and - Houses 4 7 M*, M + A
similar buildings - Colleges, homes, penitentiaries, police stations, convents 4 7 M*, M + A
- Hotels 5 7 M+A

Office and similar - Offices in general 5 7 M+A


buildings - Meeting rooms 5 7 M+A
- Data processing offices 6 9 M+A

Hospitals, clinics, - Rooms (2-3 beds) 6 8 M+A


nursing homes and - Wards 6 8 M+A
similar - Sterile and infective rooms 10 11 M + A + AS
- Maternity, anesthesia, radiation 10 11 M + A + AS
- Premature, operating rooms 11 12 M + A + AS
- Medical examination rooms 6 8 M+A
- Treatments, physical therapies 6 8 M+A

Recreational - Cinemas, theaters, congress halls 5 6 M+A


buildings - Museums, libraries 7 9 M+A
and churches - Churches 4 6 M*, M + A
- Bars, restaurants, dancing rooms
• bars in general 3 5 M*, M + A
• dining rooms, restaurants 5 6 M+A
• dancing rooms 3 5 M*, M + A
• kitchens 2 4 M

Commercial - Department stores 4 6 M*, M + A


and similar - Shops in general 4 6 M*, M + A
buildings - Special shops
• food 5 6 M+A
• photographers 5 6 M+A
• pharmacies 5 6 M+A
- Public areas, banks 4 6 M*, M + A
- Trade fair areas 2 3 M

Sport buildings - Swimming pools, saunas and similar 4 6 M*, M + A


- Gyms and similar areas 2 4 M

Scholastic buildings - Nursery schools and elementary schools 7 9 M+A


- Classrooms in general 5 6 M+A
- Other rooms
• music and language rooms 6 7 M+A
• laboratories 6 7 M+A
From UNI 10339* = To adopt for efficiencies up to 4

200
filtration
®

Classification
of rooms

Federal Standard 209 E This classification is used to count The standard also indicates the conditions
0.5 micron particles but it can be used to in accordance to which the controls must
The best known classification of air in count different size particles, for example: be carried out:
“clean rooms” or rooms with controlled • Class M3 (0,5 µm) • as built:
contamination levels is undoubtedly Class providing no more than 1.000 Clean rooms or clean zones ready
Federal Standard 209. particles of 0.5 µm in a m3 to start operating, but without production
It was issued in the United States in 1963 • Class M2 (0,3 e 0,5 µm) equipment and personnel.
for the first time and it was revised different Class providing no more than 309 • at rest:
times until the last version of 1992, particles of 0.3 µ in a m3 and no more Clean rooms or clean zones fitted
Fed. Std. 209 E presently in use, than 100 particles of 0.5 µm in a m3. with the relevant processing machines,
was reached. but without personnel.
The updated version of this classification An implementation of the expression
is based on the S.I. (International System) of class can be given by the introduction • operational:
providing the metric system, but also of the “U” indicator shown in the Clean rooms or clean zones in ordinary
the Anglo-Saxon system is allowable. Fed. Std. 209 E. working activities with personnel
The classifications of air cleanness are This indicator represents the number of and running processing machines.
thirteen, as shown in tab. 10 and are ultra-fine particles, from 0,02 up to 0,1 µm
counted in a surface of 1 m3 in this case This standard also determines
given as a power of 10 from the characteristics of the flow,
class 1 to class 10,000,000. the relevant class will be shown as follows:
distinguishing between unidirectional
For the intermediate classes the formula • U (20) (instead of linear) and non unidirectional
shown below provides a good degree Class with no more that 20 ultra-fine flow (instead of turbulent).
of approximation: particles in a m3. It establishes the conditions for
• M 1,5 (0,3 µm) e U (2000) the measurement of particles
Particles / m3 = 10M (0,5/d)2.2 Class with no more than and the instruments to use. There are two
where: M = class to be analyzed 106 particles/m3 ≥ 0,3 µm and no more different methodologies according to
d = particles size in µm than 2000 ultra-fine particles in a m3. whether there is a unidirectional flow or not.
In the case of unidirectional flow the clean
area is identified on a perpendicular level
to the air flow upstream of the work area.
The number of samples must be
Tab. 10 Maximum concentration of particles per class according determined according to the comparison
to the Federal Standard 209 E between two rates that take into account
Class 209E Max. number of particles per m3 the surface of the level intercepted by the
air flow and by the contamination class.
S.I. English 0,1 µm 0,2 µm 0,3 µm 0,5 µm 5,0 µm
In the case of non unidirectional flow the
M 1 350 75,7 30,9 10,0 - sampling points should be uniformly
M 1.5 1 1240 265 106 35,3 - spaced on the horizontal level through
M 2 3500 757 309 100 - the clean area.
M 2.5 10 12.400 2650 1060 353 -
M 3 35.000 7570 3090 1000 -
M 3,5 100 - 26.500 10.600 3530 - ISO 14644.1
M 4 - 75.700 30.900 10.000 - (International Standards Organisation)
M 4.5 1000 - - - 35.300 247
M 5 - - - 100.000 618 In 1996 ISO issued a new standard
M 5.5 10000 - - - 353.000 2470 aimed at setting the acceptability limits
M 6 - - - 1.000.000 6180 for airborne particles in clean rooms
(ISO 14644.1). The particulate reference
M 6.5 100000 - - - 3.530.000 24.700 numbers in the ISO 14644.1 see tab. 11
M 7 - - - 10.000.000 61.800 are similar to table FS 209 E,
the only difference is a new field for 1 µm
particulate, thus making the classification
of clean rooms more complete.
Tab. 11 Classification according to ISO 14644.1 Interesting differences between the two
Classification Max. n. part./ m3 of air or same size or larger than shown standards are found regarding control
and monitoring activities: in fact,
ISO 14644.1 0,1 µm 0,2 µm 0,3 µm 0,5 µm 1 µm 5 µm the quantity of checking points is higher
ISO Class 1 10 2 - - - - or lower according to the standard used
according to the considered room size
ISO Class 2 100 24 10 4 - - or to the controlled contamination area.
ISO Class 3 1.000 237 102 35 8 - Other concept differences distinguish
ISO Class 4 10.000 2.370 1.020 352 83 - the two standards; and for this reason it is
ISO Class 5 100.000 23.700 10.200 3,520 832 29 essential to identify the reference standards
ISO Class 6 1.000.000 237.000 102.000 35.200 8.320 293 and parameters in the filter design phase
ISO Class 7 - - - 352.000 83.200 2.930 to be able to control the results obtained.
ISO Class 8 - - - 3.520.000 832.000 29.300
ISO Class 9 - - - 35.200.000 8.320.000 293.000

201
filtration
®

Type of controlled
contamination
rooms
There are two main types of systems With a vertical flow, air exhaust systems are
for controlled contamination rooms with made of wall grilles or through raised floors.
reference to the position of the air filters: With a horizontal flow, the exhaust system
horizontal ceiling filters or vertical wall is made through a false wall opposite
filters. In the first case the filters can cover the filtering one.
the entire ceiling or only parts Panel-type HEPA or ULPA filters are used,
of it according to the requirements of use. they are assembled on special frames
As regards the functional aspect, able to assure air tightness and prevent
air distribution can be of two types: non any minimum air by-pass.
unidirectional flow or unidirectional flow. Certain filter models are designed to be fed
The non unidirectional flow diffusion individually through a flexible duct from
allows to reach a cleanness level a collecting duct, fitted with a connection
up to 1.000 (= M 4,5). tube on the upper plenum.
Unidirectional flow diffusion allows The unidirectional flow obtained through
to reach cleanness class 1, these technologies is made of a series
the maximum available today. of very fine parallel air flows that can
uniformly and completely clean the entire
room.
Rooms with non Air speed is kept at around 0,45 m/s.
The vertical air flow that completely cleans
unidirectional flow (turbulent) the entire room, offers cleanness conditions
over the entire work area of the room.
HEPA or ULPA filters are installed on the On the other hand, in the case of large
ceiling, in appropriate diffusers distributed surfaces, the starting up and operating
above the occupied space right by the work costs are considerable.
areas. Sometimes wall supply systems The horizontal air flow keeps the desired
are used, and even in this case the diffuser conditions on a vertical level corresponding
directly faces the room. with the work surface.
In both applications, a non unidirectional Whatever is downstream of this level
air flow is produced in the room, which, will be affected by the pollution produced
even though filtered, is not able to uniformly by the operator, the materials being
clean the room. machined etc. You can take this into
Air exhaust systems are usually positioned consideration by positioning in the right
at the bottom of walls. Rooms with order, processes that require progressively
non unidirectional flows allow to reach lower cleanness conditions.
cleanness levels up to 1.000 (= M 4,5). The cost of this solution, both start-up
and operating costs, is usually lower
than the previous one.
Rooms with unidirectional flow In rooms with unidirectional flows,
(laminar) vertical or horizontal, you can reach
cleanness level 1 (M = 1,5).
Entire filtering ceilings or walls with
a vertical or horizontal air flow respectively
are created in these rooms.

New ISPESL
Guidelines
for operating
From a general point of view, and leaving • The design of the rooms must assure
rooms. aside safety requirements, the new ISPESL that they can be cleaned, i.e. the use
guidelines can be summarized as follows: of round corners, smooth surfaces,
washable, resistant against chemical
• General architecture of the operating and physical agents and anti-skid floors.
rooms designed in order to assure
a control hierarchy, i.e. the use of inner • The obligation to organize programmed
doors dedicated to the personnel, cleaning schedules both for the rooms
patients, materials, i.e. an architecture and the equipment.
that complies with the technical
requirements of controlled • Obligation to organize programmed
contaminations rooms. maintenance schedules for all systems.
More specifically, the department As regards contamination control,
architecture must be structured so that the guidelines recall all the design
is it impossible to pass from a room with and control requirements set forth
lower cleanness level to one with higher by the European G.M.P. for rooms used
cleanness levels and that the doors for the preparation of pharmaceutical
of inner communication doors products.
do not open simultaneously. A paragraph is dedicated to ventilation
and conditioning systems. The indications
• Creation of appropriate secondary areas, supplied use the minimum requirements
both technical and service areas, external set forth in the President’s Ordnance
to the departments themselves, such as of January 14 1997 as starting base with
locker rooms, restrooms, inspection all the essential modifications required
areas, emergency exit areas. by the pharmaceutical industry.

202
filtration
®

Minimum system requirements it is necessary to reduce the quantity in accordance with the UNI,
of circulating air, in operating conditions, IES RPCC-006, ISO 14644/3, BS 5276
The HVAC system must guarantee providing room pressure remains standards. If the system is an all external
adequate hygienic-environmental conditions constant, a guarantee against the inlet air system (typical of turbulent distribu-
in the operating room and more specifically: of non-filtered air. tion
• Maintain “adequate” room ventilation • The geometry of air supplies systems) the number of room changes
able to limit the room concentration and exhausts from the rooms must can be calculated with the following
of anesthetic gasses and/or other gas be optimized to minimize the harmful formula:
pollutants, even in the case of unusual effects such as short circuits between N = Inlet air flow rate / Room volume
emissions. inlet and exhaust, the creation
of non-ventilated bags, In the case of unidirectional flow
• Maintain correct thermal hygrometric local under-cooling caused by a very high distributions, a part of the air
conditions for the user and the personnel. residual speed of the inlet air. can be locally re-circulated. In this case
• Maintain the concentration of total the relation Inlet air flow rate / Room
airborne particulate under the limits set Air supply systems must be chosen volume does not produce the number
for the rooms, through adequate inlet air according to the use of the each room of changes but the number of re-cycles.
filtration, through constant of the ward. For pre/post-operating rooms, Of course, even in this case the changes
and measurable overpressures, washing, surgeon preparation must be higher than the minimum
established so that the air moves and sub-sterilization, the most suitable requirements.
from cleaner rooms to less cleaner systems could be terminal hoods with high • Pressure drop of filtration systems,
rooms. The minimum pressure difference efficiency filters (HEPA) fitted with Coanda measured and registered at least
between the two communicating rooms effect or high induction diffusers, once a month.
must be at least 5 Pa. for a turbulent air distribution system. • Total microbic load, of opportunistic
The minimum functional specifications that For operating rooms used for general microorganisms and air pathogens after
the system must guarantee in the various surgery or similar practices, suitable each sterilization, measured averagely
rooms are shown in table 12. diffusion systems could be vertical/horizon- for each room and directly on the supply
tal unidirectional flow systems partially grilles.
The geometry of the ventilation and filtration on the operating field (mixed flow system).
systems must be such as to assure • Verification of the efficiency of terminal
For operating used for orthopedic, heart filtration systems that should be carried
the performance levels in time through surgery, arthroprosthesis, neurosurgery,
planned management and maintenance out at least during the system
vascular surgery, etc. operations, suitable acceptance phase (DOP Leak Test,
interventions. distribution systems could be vertical/hori-
Particularly: IES RPCC-006, ISO 14644/3,
zontal unidirectional flow systems, EUROVENT 4/8 or similar), and every
• Easily controllable systems, foreseeing on the entire operating room time the filter is replaced.
suitable measurement sections of critical (unidirectional flow system). You should also check the following
parameters that allow for the use In this case you should remember that: additional features for operating rooms:
of auxiliary equipment to control • The quantity of air needed is higher
performances, the fixed instrumentation • Daily thermal hygrometric check
than 15 changes/h
or for certification. • Environmental contamination class
• Residual air speed on surgeons/patients referred to the total airborne particulate,
• Ducts made of anti-corrosive material, is higher than an induction diffusion
fitted with external insulations and with to be carried out at least every 6 months
system, so it requires a very low and when the system is accepted.
air drop lower than 5% when tested under-cooling level of the inlet air
at 1,5 times nominal operating pressure. (2-3 °K). For mixed flow or unidirectional systems
• Acoustic/optical alarm devices that • The high quantities of air used could the value of the class in idle conditions
immediately warn the operator when the require the use of local recycling must be at least M 3,5 Federal Standard
critical parameters are below safety limits. ventilation devices, room per room, 209 E or ISO 5.
(For example: manometers with alarms, to limit energy consumption. This means that the maximum quantity
pressure switches for room pressures, of particles contained in a cubic meter
measurement devices for inlet flow rates of air with a diameter higher than or equal
with alarms for minimum rates etc.) Suggested control parameters for to 0,5 micron is 3520.
• Very high efficiency filters as last element Please remember that the filtered air room
of air distribution systems and installed the management of the system recycling levels with HEPA filters must
directly in the ceilings or false ceilings exceed 30 Volumes/h.
of ventilated rooms. For high efficiency The periodical assessment of the
performances of the system is a way to For rooms with turbulent flows, the class
filters (HEPA) we mean filters with in idle conditions must at least be equal
an average efficiency higher than 99,97% control its functionality even to assure the
compliance with the minimum requirements to M 5,5 Federal Standard 209 E or ISO 7.
in relation to the DOP test method In this case, the maximum number
or comparable to other systems: foreseen for environmental parameters.
The critical parameters to consider and of particles contained in a cubic meter
DIN 24183, BS 5296, EUROVENT 4/4 or, of air with a diameter higher than or equal
according to the most recent standards check periodically according
to a management program are: to 0,5 micron is 352.000.
updating UNI EN 1822. The concentrations of airborne particulate,
• A planned management and maintenance • The positive pressure of the rooms, both microbic and inert, in a room with
procedure to check the functionality and measured and recorded with an controlled contamination, depend on the air
the performances of the systems and appropriate manometer, supply and exhaust geometries, besides
assure functionality in time. placed in a visible area, at least once on the air flow rates, filtration efficiency,
a day. overpressure, architecture of the ward,
• The possibility of isolating every single
operating room for room sanitization • Inlet air flow rate measured and recorded hence they depend on the path that
cycles. at least every six months. air follows in a room.
This value can be measured directly
• To limit energy consumption, on terminal filters or in the ducts

203
filtration
®

Tab. 12 Minimal functional specifications the system must assure for each room
I In the operating room
Minimum filtration efficiency: > 99,97% DOP Test
Total microbic volume of inlet air: < 1 CFU**/m3
Overpressure compared to the outside of the ward: positive
n° external air changes: 15 Volumes/h
Summer/ winter temperature between: 20-24 °C
Summer/winter relative humidity: 40-60 %

II Pre/post, surgeon washing-preparation


n° external air changes : 6 Volumes/h
Temperature/humidity: comfortable
Overpressure compared to the outside of the ward: positive
Overpressure compared to operating room: negative

III Surgical instruments washing, sub-sterilization


n° external air changes : 15 Volumes/h
Temperature/humidity: comfortable
Overpressure compared to the outside of the ward: positive
Overpressure compared to operating room: negative

IV In remaining rooms of surgery ward


n° external air changes : 2 Volumi/h
Temperature/humidity: comfortable
Overpressure compared to the outside of the ward: positive
Overpressure compared to operating room: negative

Tab. 13 Division of operating ward


Operating rooms with total laminar flow class A
Rooms with mixed flow critical areas (operating field) in class A,
surrounding areas in class B
Rooms with turbulent flow class B
Surgical team locker rooms first stage in class C,
second stage in class B
Patient preparation/wake-up class C/B
Instrument washing class D
Sub - sterilization generally class C
Ward halways class D
Deposit of sterile material class B
Waiting room outside of ward
Inner ward access door not classified
General access locker room not classified
Restrooms dedicated but outside of ward

ECC GMP Annex 1 environmental parameters you can, We can divide the operating ward
undoubtedly, refer to this guide to act in classes, A,B,C,D.
From a general point of view the prescrip- in compliance with the spirit used to See the indications in tab. 13.
tions of the guide are contained in the more draw up the guide, providing the minimum The requirements for the various classes
general European GMP dedicated to the requirements set forth by the law, identified above and the bacteriologic
preparation of pharmaceutical products. if in contrast with the GMP prescriptions, contamination values are shown in tab. 14
For a more accurate definition of the are observed. and refer to room air samples.

Tab. 13 Requirements of the various rooms


idle idle in operation in operation in operation
Level Pt* / m3 > 0,5 µm Pt */ m3 > 5 µm Pt */ m3 > 0,5 µm Pt* / m3 > 5 µm CFU** / m3
A 3500 0 3500 0 <1
B 3500 0 350000 2000 10
C 350000 2000 3500000 20000 100
D 3500000 20000 N.C. N.C. 200

* Pt = Particles
** CFU = Colony Forming Units, i.e. all those particles in the air that deposited on an adequate
layer of bacterial culture can develop colonies.

204
filtration
®

Industrial filters
and dust exhaust
systems
The field of industrial dust exhaust systems The first group includes all the information
and gas emission controls, is very broad related to the climate of the site, presence
and divided into various specialized of dominating winds, pressure, temperature,
branches. In this case we particularly refer relative humidity, etc.
to the main exhaust control systems Hence, information on the use of energy
for dust coming from processing plants and the materials or substances used
or working cycles. In reality, the need in the process which generates
to control industrial emissions often the pollutants. And finally, the assessment
includes other things, such as: of the personal and environmental
• compliance with the laws in force against protection standards in force.
environmental pollution; As regards gas pollutants, you need
• controlling product quality, avoiding to know the nature and concentration
product contamination from agents of the substances. For dusts, it is important
or substances produced during working to know the distribution of the sizes,
cycles; their concentration with average and
extreme values, and their possible features
• keeping the initial cost and the in terms of erosion capacity, abrasion,
maintenance cost of the dust exhaust adhesion, etc., alongside the electric
system within a certain limit so not to properties (resistivity) as well as possible
increase the unitary cost of the product; solubility features.
• prevent damages or disturbing conditions It is important to know the concentration
for the people or things in the area value per volume units, for recovery
of installation of the system or in external evaluations. Toxicity, inflammability,
areas; inclination towards explosion are further
• prevent the distribution of polluting features to take into account.
substances in the work place; When choosing a dust extraction system
• allow for the recycling of materials, it is very important to know the distribution
energy, heat, from the treated aeriform of the size of the dusts.
particles; In fact, the efficiency of these systems
is strongly affected by the diameter
• allow the recycling of filtered air of the particles.
in the work place;
• reduce fire, explosion, etc, risks. If you don’t have precise figures, you need
to take samples using methods that can
After setting the primary needs, produce significant results.
the specifications of the process or the The concentration, in weight, of the dusts
system must be evaluated along with the produced by industrial systems has a very
possible interventions. In fact frequently, broad spectrum of values.
you can reach substantial savings It goes from 20 mg/m3 up to 40,000 mg/m3
on filtration or dust exhaust systems by and more.
intervening at the source, i.e. the process The available dust extraction systems
which produces the polluting substances are limited to just about 5 different
themselves. configurations according to the basic
For a preliminary exam of the problem interception principle or mechanism:
you need to have two types of information: • centrifugal separators
• specifications of the system that (cyclone, inertial, gravity)
produces the pollutants
• nature of the pollutants and their • sleeve / bag filters
specifications. • electrostatic precipitators
• wet separators
(wet towers, scrubbers, wet cyclones)
• cartridge filters
Tab. 14 Typical performances of dust extraction systems
Ponderal separation Minimum Admitted dust Especially experience has allowed us to
efficiency dust diameter volume determine for the various industrial sectors
Type % µm mg/m3 which types of dust extraction system
better meets their needs.
Cartidge 100 0,5 5.000
Cyclone 85 10 2.000 The performances related to the various
Scrubber 90 5 2.000 dust extraction systems are shown
(wet washer) in tab. 14.
Sleeve separators 99 1 500
Electrostatic 95 2 200 Tab 15 summarizes the most common
precipitators industrial situations.

205
filtration
®

Industrial filters and dust


extraction systems

Legend:
O Optimal use (suggested)
B Good use
D Fair use
S Poor use

Tab. 15 Mosto common use of industrial dust extraction systems


Sector Particle Dust Centrifugal Electrostatic Wet separators Sleeve / bag Cartidge
and processes Ø concentration or inertial precipitators scrubbers water filters filters
separator mist application
µm mg/m3 booths
Pharmaceutical
• Granulation 10 ÷ 50 200 ÷ 1000
• Coating 5 ÷ 10 50 ÷ 500 S S D S O
Pharmaceutical / Food
• Packaging 20 ÷ 50 200 ÷ 1000
• Grinding 2 ÷ 50 300 ÷ 1000 S S S B O
• Weighing 2 ÷ 20 100 ÷ 200

Chemical
• Mixing 10 ÷ 100 100 ÷ 500
• Grinding 5 ÷ 20 300 ÷ 1000 S S S B O
• Packaging 20 ÷ 100 200 ÷ 1000

Plastic machining
• Mixing 2 ÷ 20 100 ÷ 500
• Hot processing 0,5 ÷ 20 50 ÷ 200 D S S B B
• Cold processing 10 ÷ 100 200 ÷ 1000

Agriculture
• Cereal processing 10 ÷ 500 500 ÷ 2000
• Drying 10 ÷ 100 100 ÷ 500 B S S B D
• Packaging 50 ÷ 500 500 ÷ 2000

Metalworking
• Electric furnace 10 ÷ 50 500 ÷ 5000
• Blast furnace 20 ÷ 200 300 ÷ 2000 B B D D O
• Mineral transport 50 ÷ 500 500 ÷ 5000

Mechanical machining
• Laser / Plasma 0,5 ÷ 10 10 ÷ 50
• Welding 0,5 ÷ 5 50 ÷ 20 S D D S O
• Varnishing 2 ÷ 30 100 ÷ 500

Wood machining
• Cutting 50 ÷ 1000 200 ÷ 2000
• Finishing 20 ÷ 500 50 ÷ 1000 B S B D/B S
• Painting 2 ÷ 30 100 ÷ 500

Ceramic
• Atomization 2 ÷ 20 200 ÷ 2000
• Packaging 5 ÷ 100 50 ÷ 1000 S S D S O
• Painting 2 ÷ 30 100 ÷ 500

206
filtration

You might also like